Chapter 13 – Custom Logic
Parameter
Average Temperature
Average Pressure
Average Density
Average Relative Density
Average API Gravity
Unauthorized Gross
Unauthorized Net
Unauthorized Mass
Vapor Pressure
Recipe Percentage
Recipe Volume
Blend Target Volume
Blend Target Percentage
Batch Recipe Percentage
Blend Target Volume Error
Blend Target Percentage Error
Batch Recipe Volume Error
Batch Recipe Percentage Error
Firmware Version 3/4.31.37
The average temperature of that component for the current batch.
The average pressure of that component for the current batch.
The average density of that component for the current batch.
The average density of that component for the current batch.
The average density of that component for the current batch.
The gross amount delivered, of the specified component, which was not
authorized for the current driver.
The net amount delivered, of the specified component, which was not
authorized for the current driver.
The amount delivered in mass, of the specified component, which was not
authorized for the current driver.
The current vapor pressure of the specified component. The value is in
hundredths.
The percentage, of the specified component, for the current product recipe
that has been selected to load. The value is in whole units.
The volume amount, of the specified component, for the current product
recipe being loaded.
The calculated volume to be delivered, of a blended product, for the current
load.
The calculated percentage to be delivered, of a blended product, for the
current load.
The actual percentage, of the specified component, that has been delivered
for the current load. The value is in hundredths.
The difference between the volume actually delivered, and the amount
intended to be delivered according to the Blend Target Recipe Percentage.
The difference between the percentage that was actually loaded, and the
Blend Target Percentage.
= Batch Recipe Percentage – Blend Target Percentage.
The difference between the volume actually delivered, and the amount
intended to be delivered according to the recipe percentage.
The difference between the percentage of the recipe, and the percentage
that was actually loaded.
= Batch Recipe Percentage – Recipe Percentage.
Description
398
Need help?
Do you have a question about the MultiLoad II and is the answer not in the manual?
Questions and answers
Greetings, how can multiload ll totalizers be reset?
The resettable totalizers on the Toptech Systems MultiLoad II can be reset using the CLR (Clear) key. Non-resettable totalizers cannot be reset.
This answer is automatically generated