Communication - GE B30 Communications Manual

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
411C
Port 1 Function
"
411D
Port 2 Function
"
411E
Port 3 Function
"
411F
IEC Communications Reserved (33 items)
"
4140
DNP Object 1 Default Variation
"
4141
DNP Object 2 Default Variation
"
4142
DNP Object 20 Default Variation
"
4143
DNP Object 21 Default Variation
"
4144
DNP Object 22 Default Variation
"
4145
DNP Object 23 Default Variation
"
4146
DNP Object 30 Default Variation
"
4147
DNP Object 32 Default Variation
"
4148
SCADA Protocol
"
4149
RS232 Baud Rate
"
414A
DNP Event Time Base
"
414B
IEC 104 Event Time Base
"
414C
IEC 103 Event Time Base
Communications Actual Values (Read Only)
All
4160
Modbus Available TCP/IP Connections
"
4161
DNP Available TCP/IP Connections
"
4162
IEC Available TCP/IP Connections
"
4163
MMS Available TCP/IP Connections
"
4164
PMU Available TCP/IP Connections
"
4165
SFTP Available Connections
Simple Network Time Protocol (Read/Write Setting)
All
4168
Simple Network Time Protocol (SNTP)
Function
"
4169
Simple Network Time Protocol (SNTP)
Server IP Address
"
416B
Simple Network Time Protocol (SNTP) UDP
Port Number
Data Logger Commands (Read/Write Command)
All except B90
4170
Data Logger Clear
Data Logger (Read/Write Setting)
All except B90
4181
Data Logger Channel Settings (16 items)
"
4191
Data Logger Mode
"
4192
Data Logger Trigger
"
4194
Data Logger Rate
Clock (Read/Write Setting)
All
419F
Synchronizing Source
Clock (Read/Write Command)
All
41A0
Real Time Clock Set Time
Clock (Read/Write Setting)
All
41A2
SR Date Format
"
41A4
SR Time Format
"
41A6
IRIG-B Signal Type
"
41A7
Clock Events Enable / Disable
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
1 to 2
---
1
1 to 3
---
1
0 to 3
---
1
0 to 3
---
1
0 to 3
---
1
0 to 3
---
1
1 to 5
---
1
0 to 5
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 4
---
1
0 to 2
---
1
0 to 2
---
1
0 to 5
---
1
0 to 4
---
1
0 to 4
---
1
0 to 1
---
1
0 to 4294967295
---
1
1 to 65535
---
1
0 to 1
---
1
---
---
---
0 to 1
---
1
0 to 4294967295
---
1
15 to 3600000
ms
1
0 to 3
---
1
0 to 235959
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
MEMORY MAP
Format
Default
F102
1 (Enabled)
F102
1 (Enabled)
F102
1 (Enabled)
F001
0
F001
2
F001
2
F523
0 (1)
F524
0 (1)
F523
0 (1)
F523
0 (1)
F001
1
F525
0 (1)
F629
0 (DNP 3.0)
F635
1 (115200)
F639
1 (LOCAL)
F639
1 (LOCAL)
F639
1 (LOCAL)
F001
4
F001
2
F001
2
F001
5
F001
4
F001
4
F102
0 (Disabled)
F003
0
F001
123
F126
0 (No)
F600
0
F260
0
(Continuous)
F300
0
F003
60000
F623
0 (None)
F050
0
F051
0
F052
0
F114
0 (None)
F102
0 (Disabled)
2-61
2

Hide quick links:

Advertisement

Table of Contents
loading