GE B30 Communications Manual page 300

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: GndTocPTOC#
data obj. data attribute
Op
general
Dpo
stVal
BlkRefγ1
setSrcRef
setSrcCB
3.5.2.30 Hybrid permissive over-reaching transfer trip (HPOTT_)
3
This element is instantiated in the following products: D60, L90.
Table 3-54: Hybrid POTT data objects
LNName: HPOTT_PSCH1
data obj. data attribute
Op
general
phsA
phsB
phsC
Tr3p
general
Tx1
stVal
Tx2
stVal
Tx3
stVal
Tx4
stVal
BlkRef1
setSrcRef
setSrcCB
InRef5
setSrcRef
setSrcCB
InRef8
setSrcRef
setSrcCB
InRef6
setSrcRef
setSrcCB
InRef7
setSrcRef
setSrcCB
InRef1
setSrcRef
setSrcCB
InRef2
3-62
LDevice inst: Prot
UR element: Ground Time Overcurrent element#
Type
FC UR Name
ACT
BOOLEAN
ST
GROUND TOC# OP
SPS
BOOLEAN
ST
GROUND TOC# DPO
ORG
ObjectReference SP
GROUND TOC# BLOCK.
ObjectReference SP
LDevice inst: Prot
UR element: Hybrid Permissive Over-reaching Transfer Trip element
Type
FC UR Name
ACT
BOOLEAN
ST
HYBRID POTT OP
BOOLEAN
ST
HYBRID POTT TRIP A
BOOLEAN
ST
HYBRID POTT TRIP B
BOOLEAN
ST
HYBRID POTT TRIP C
ACT
BOOLEAN
ST
HYBRID POTT TRIP 3P
SPS
BOOLEAN
ST
HYBRID POTT TX1
SPS
BOOLEAN
ST
HYBRID POTT TX2
SPS
BOOLEAN
ST
HYBRID POTT TX3
SPS
BOOLEAN
ST
HYBRID POTT TX4
ORG
ObjectReference SP
HYB POTT SCHEME BLOCK
ObjectReference SP
ORG
ObjectReference SP
HYB POTT ECHO COND
ObjectReference SP
ORG
ObjectReference SP
HYB POTT W/I COND
ObjectReference SP
ORG
ObjectReference SP
GND DIR O/C FWD
ObjectReference SP
ORG
ObjectReference SP
GND DIR O/C REV
ObjectReference SP
ORG
ObjectReference SP
HYB POTT RX1
ObjectReference SP
ORG
CHAPTER 3: IEC 61850 COMMUNICATION
Description
GROUND TOC# OP operand
GROUND TOC# DPO operand
GROUND TOC# BLOCK setting in setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
HYBRID POTT OP operand
HYBRID POTT TRIP 3P operand
HYBRID POTT TX1 operand
HYBRID POTT TX2 operand
HYBRID POTT TX3 operand
HYBRID POTT TX4 operand
HYB POTT SCHEME BLOCK setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
HYB POTT ECHO COND setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
HYB POTT W/I COND setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
GND DIR O/C FWD setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
GND DIR O/C REV setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
HYB POTT RX1 setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
HYB POTT RX2 setting
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R
R/C
R
R/C
R
R/C
R
R/C
R
R/C
R