GE B30 Communications Manual page 328

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Table 3-97: Phase comparison advanced fault detector negative sequence current (for FDH) data objects
LNName: PhCmp4PIOC1
data obj. data attribute
Op
stVal
Table 3-98: Phase comparison open breaker echo data objects
LNName: PhCmp5FXOT1
data obj. data attribute
InRefγ1
3
setSrcRef
setSrcCB
InRefγ2
setSrcRef
setSrcCB
InRefγ3
setSrcRef
setSrcCB
InRefγ4
setSrcRef
setSrcCB
InRefγ5
setSrcRef
setSrcCB
InRefγ6
setSrcRef
setSrcCB
StrVal
setMag
setMag.f
units
units.SIUnit
units.multiplier
Op
general
3.5.2.55 Phase current unbalance (PhAUn)
This element is instantiated in the following products: C70.
Table 3-99: Phase current unbalance data objects
LNName: PhAUnPTOC#
data obj. data attribute
Str
3-90
LDevice inst: Prot
UR element: Negative Sequence Current element specific to FDH element
as a part of Phase comparison function
Type
FC UR Name
SPS
BOOLEAN
ST
87PC I_2 FDH OP
LDevice inst: Prot
UR element: OPEN BREAKER ECHO element as a part of Phase comparison
function
Type
FC UR Name
ORG
ObjectReference SP
BRK 1 AUX CONTACT setting
ObjectReference SP
ORG
ObjectReference SP
BRK 1 CONT SUPV setting
ObjectReference SP
ORG
ObjectReference SP
BRK 2 AUX CONTACT setting
ObjectReference SP
ORG
ObjectReference SP
BRK 2 CONT SUPV setting
ObjectReference SP
ORG
ObjectReference SP
WEAK-INFEED KEYING setting
ObjectReference SP
ORG
ObjectReference SP
WEAK-INFEED SUPV setting
ObjectReference SP
ASG
AnalogueValue
SG
FLOAT32
Unit
CF
ENUMERATED
ENUMERATED
ACT
BOOLEAN
ST
87PC BKR ECHO PKP
LDevice inst: Prot
UR element: Phase Current Unbalance element #
Type
FC UR Name
ACD
CHAPTER 3: IEC 61850 COMMUNICATION
Description
87PC I_2 FDH OP operand
Description
BRK 1 AUX CONTACT setting of setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
BRK 1 CONT SUPV setting of setting group
γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
BRK 2 AUX CONTACT setting of setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
BRK 2 CONT SUPV setting of setting group
γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
WEAK-INFEED KEYING setting of setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
WEAK-INFEED SUPV setting of setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Non-mapped mandatory DO, Non-
configurable read only value
0
1, the code for dimensionless
0, the code for a multiplier of 1
87PC BKR ECHO PKP operand
Description
CUR BAL # PKP operands (including
individual three phases), which indicates
Op will operate when delay expires.
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R/W/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R
R
R
R
R
R
R
R/W/C
R

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents