GE B30 Communications Manual page 368

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Table 3-150: Fault report data file data objects
LNName: FltRFLOψψLDevice inst: CtrlUR element: Selected values from Fault Report Data f ile ψψ
data obj. data attribute
FltZ
cVal
cVal.mag.f
cVal.ang.f
FltRis
mag
mag.f
3
units
units.SIUnit
units.multiplier
FltLoopRis
mag
3.5.3.15 Frequency out-of-band accumulation (HzBnd)
This element is instantiated in the following products: G30, G60.
Table 3-151: Frequency out-of-band accumulation data objects
LNName: HzBndPTUF1
data obj. data attribute
Str
general
dirGeneral
Op
general
BlkRef1
setSrcRef
setSrcCB
Table 3-152: Frequency out-of-band accumulation prefix instance number $ data objects
LNName: HzBnd$PTUF1
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
HzObAccu
m
3-130
Type
FC UR Name
CMV
Vector
MX
FLOAT32
Fault impedance magnitude in
primary ohms calculated as
shown below
FLOAT32
Fault impedance angle in
degrees calculated as shown
below
MV
AnalogueValue
MX
FLOAT32
Actual Value FAUL Tψψ FAUL T
RESIST converted to primary
ohms
Unit
CF
ENUMERATED
ENUMERATED
MV
AnalogueValue
MX
LDevice inst: Ctrl
UR element: Frequency OOB Accumulation element
Type
FC UR Name
ACD
BOOLEAN
ST
FREQ OOB ACCUM PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
FREQ OOB ACCUM OP
ORG
ObjectReference SP
FREQ ACCUM BLOCK.
ObjectReference SP
LDevice inst: Ctrl
UR element: Frequency OOB Accumulator $
Type
FC UR Name
ACD
BOOLEAN
ST
FREQ OOB BAND $ PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
FREQ OOB BAND $ OP
SPS
BOOLEAN
ST
FREQ OOB BAND $ DPO
MV
CHAPTER 3: IEC 61850 COMMUNICATION
Description
Mandatory data attribute which in this
case is f ixed at zero
FAUL Tψψ FAUL T RESIST converted to
primary ohms
30, the code for primary electric
resistance in ohm (V/A)
0, the code for a multiplier of 1
FAUL Tψψ LOOP RESIST converted to
primary ohms
Description
FREQ OOB ACCUM PKP operand, which is
indicates Op will operate when delay
expires.
0, the code for unknown.
FREQ OOB ACCUM OP operand
FREQ ACCUM BLOCK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
FREQ OOB BAND $ PKP operand, which is
indicates Op will operate when delay
expires.
0, the code for unknown.
FREQ OOB BAND $ OP operand
FREQ OOB BAND $ DPO operand
FREQUENCY OOB BAND $
ACCUMULATION in percentage (%)
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents