CHAPTER 3: IEC 61850 COMMUNICATION
LNName: NuVUn$PTOV#
data obj. data attribute
Type
VISIBLE
STRING255
cdcNs
VISIBLE
STRING255
cdcName
VISIBLE
STRING255
3.5.2.48 Open pole detector (OpnPl)
This element is instantiated in the following products: C60, D60, L60, L90. It does not apply to open pole detector supervisor
N60.
Table 3-79: Open pole detector data objects
LNName: OpnPl0SCBR1
data obj. data attribute
Type
BlkRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
ColOpn
SPS
stVal
BOOLEAN
PlOpn
ACT
general
BOOLEAN
BlkPhDis
SPS
stVal
BOOLEAN
Table 3-80: Open pole detector data objects
LNName: OpnPlΘSCBR1
data obj. data attribute
Type
ColOpn
SPS
stVal
BOOLEAN
PlOpn
ACT
general
BOOLEAN
BkrOpnPl
ACT
general
BOOLEAN
BlkPhDis
SPS
stVal
BOOLEAN
RemUnA
SPS
stVal
BOOLEAN
UnA
SPS
stVal
BOOLEAN
3.5.2.49 Overfrequency (OvHz)
This element is instantiated in the following products: C60, D60, F60, G30, G60, L90, M60, N60, T60.
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Neutral Voltage Unbalance element # stage $
FC UR Name
SP
If reference is external to this
IED, mapped to the source's
GOOSE control block, else empty
string
EX
Name of the GE Multilin
namespace at the time of this
firmware release
EX
GEORG
LDevice inst: Prot
UR element: Open Pole Detector element
FC UR Name
OPEN POLE BLOCK
ST
Status of Logical OR condition to
OpnPl1SCBR1.ColOpn,
OpnPl2SCBR1.ColOpn,
OpnPl3SCBR1.ColOpn
ST
OPEN POLE OP
ST
OPEN POLE BLK N
LDevice inst: Prot
UR element: Open Pole Detector element for ψ and ψτ
FC UR Name
ST
Status value TRIP ψ setting
ST
OPEN POLE OP ψ
ST
OPEN POLE BKR ψ OP
ST
OPEN POLE BLK ψτ
ST
OPEN POLE REM OP ψ
ST
OPEN I < ψ
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
Description
OPEN POLE BLOCK setting
reference to the data attribute to input
source GoCB of input if via GOOSE
Logical OR of status value of mapped
FlexLogic operands in TRIP PHASE A, TRIP
PHASE B, TRIP PHASE C".
OPEN POLE OP operand
OPEN POLE BLK N operand
Description
Status value of mapped settings TRIP ψ R
OPEN POLE OP ψ operand
OPEN POLE BKR ψ OP operand
OPEN POLE BLK ψτ operand
OPEN POLE REM OP ψ operand
OPEN POLE I < ψ operand
R/W/C
R/C
R
R
3
R/W/C
R
R/C
R/C
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
3-81