MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Data object
CDC
name
DynArmd
SPS
DynDpo
SPS
DynOp
SPS
Ena1
SPS
EqLim
SPS
3
EqpMismat
SPS
EvtEna1
ENG
EvtLED
SPS
EvtRcdClr
SPC
Fail
SPS
FDLOp
SPS
FlexErrTkn
SPS
Flt3Ph
SPS
FltAB
SPS
FltABG
SPS
FltAG
SPS
FltBC
SPS
FltBCG
SPS
FltBG
SPS
FltCA
SPS
FltCAG
SPS
FltCG
SPS
FltCntClr
SPC
FltCntPhφ
INS
FltLinID
VSS
FltLocation
MV
FltLoopReact
MV
3-214
Semantics
This data object indicates that dynamic mode is armed.
The SYNC1 S-CLOSE ARMD operand, which becomes On when dynamic mode is
armed.
The SYNC1 S-CLOSE DPO operand, which becomes Off when all criteria for
dynamic mode are fulfilled
This data object indicates that all criteria for dynamic mode are fulfilled if value is
TRUE else false.
The SYNC1 S-CLOSE OP operand, which becomes On when all criteria for dynamic
mode are fulfilled.
Function is Enabled.
The AR ENABLED operand.
The number of pulses counted is equal to the set number.
Counter 1(CNT1) EQL operand, which indicates the number of pulses counted is
equal to the set number.
The configuration of modules does not match the stored order code.
The EQUIPMENT MISMATCH operand.
Setting to enable generation of events in event record, 0 = Disabled, 1 = Enabled
An LED - Event Cause LED status. For graphical front panel.
The EVENT CAUSE LED 1 operand.
Clear Event Records (erase all Events).
The CLEAR EVENT RECORDS command.
Ground Protection Module Failure.
GPM-F (Field Ground Protection Module) Fail status.
The GPM-F FAILURE operand.
Overcurrent fault detector low has operated.
The 87PC FDL OP operand.
A FlexLogic equation is incorrect.
The FLEXLOGIC ERR TOKEN operand.
Fault indication - Three phase fault.
The PHASE SELECT 3P operand.
Fault indication - Phase A to B.
The PHASE SELECT AB operand.
Fault indication - Phase A to B to ground.
The PHASE SELECT ABG operand.
Fault indication - Phase A to ground.
The PHASE SELECT AG operand.
Fault indication - Phase B to C.
The PHASE SELECT BC operand.
Fault indication - Phase B to C to ground.
The PHASE SELECT BCG operand.
Fault indication - Phase B to ground.
The PHASE SELECT BG operand.
Fault indication - Phase C to A.
The PHASE SELECT CA operand.
Fault indication - Phase C to A to ground.
The PHASE SELECT CAG operand.
Fault indication - Phase C to ground.
The PHASE SELECT CG operand.
TRUE = clear incipient fault count. The clear incipient fault counters command.
Number of detected incipient faults.
INCIPIENT FAULT 1 PH A/B/C FAULTS.
Faulted line ID
Fault location in percentage.
The FAULT LOCATION in percentage of field winding from negative terminal in
case of single point injection. If double point injection, displays Invalid value.
D30, D60, L60, L90 - The fault loop reactance
CHAPTER 3: IEC 61850 COMMUNICATION
Used in logical nodes...
SynChkRSYN
SynChkRSYN
SynChkRSYN
Rec13pRREC, Rec3pRREC
DigCntFCNT
LPHD
GGIO3
LEDsIHMI
Master/LLN0
FldGnd0PHIZ
PhCmp1PDIF
LPHD
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
PhSelGAPC
ICFltPTEF
ICFltPTEF
FltRFLO
FldGnd0PHIZ
FltRFLO
UR FAMILY – COMMUNICATIONS GUIDE