CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
3893
Remote Ground CT x Origin 2
"
3894
AC Bank Redundancy Type
"
3895
Remote Phase CT 1 Primary
"
3896
Remote Phase CT 1 Secondary
"
3897
Remote Ground CT 1 Primary
"
3898
Remote Ground CT 1 Secondary
"
3899
Remote Phase VT 1 Connection
"
389A
Remote Phase VT 1 Secondary
"
389B
Remote Phase VT 1 Ratio
"
389D
Remote Auxiliary VT 1 Connection
"
389E
Remote Auxiliary VT 1 Secondary
"
389F
Remote Auxiliary VT 1 Ratio
"
38A1
...Repeated for Field Unit 2
"
38B2
...Repeated for Field Unit 3
"
38C3
...Repeated for Field Unit 4
"
38D4
...Repeated for Field Unit 5
"
38E5
...Repeated for Field Unit 6
Field Unit Contact Inputs (Read/Write Setting) (40 Modules)
All except B90,
3950
Field Contact Input 1 ID
L60
"
395A
Field Contact Input 1 Origin
"
395B
Field Contact Input 1 Input
"
395C
Field Contact Input 1 Failsafe Value
"
395D
Field Contact Input 1 Debounce Time
"
395E
Field Contact Input 1 Events
"
395F
...Repeated for Field Contact Input 2
"
396E
...Repeated for Field Contact Input 3
"
397D
...Repeated for Field Contact Input 4
"
398C
...Repeated for Field Contact Input 5
"
399B
...Repeated for Field Contact Input 6
"
39AA
...Repeated for Field Contact Input 7
"
39B9
...Repeated for Field Contact Input 8
"
39C8
...Repeated for Field Contact Input 9
"
39D7
...Repeated for Field Contact Input 10
"
39E6
...Repeated for Field Contact Input 11
"
39F5
...Repeated for Field Contact Input 12
"
3A04
...Repeated for Field Contact Input 13
"
3A13
...Repeated for Field Contact Input 14
"
3A22
...Repeated for Field Contact Input 15
"
3A31
...Repeated for Field Contact Input 16
"
3A40
...Repeated for Field Contact Input 17
"
3A4F
...Repeated for Field Contact Input 18
"
3A5E
...Repeated for Field Contact Input 19
"
3A6D
...Repeated for Field Contact Input 20
"
3A7C
...Repeated for Field Contact Input 21
"
3A8B
...Repeated for Field Contact Input 22
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 16
---
1
0 to 2
---
1
1 to 65000
---
1
0 to 1
---
1
1 to 65000
---
1
0 to 1
---
1
0 to 1
---
1
25 to 240
---
0.1
1 to 24000
---
1
0 to 6
---
1
25 to 240
---
0.1
1 to 24000
---
1
---
---
---
0 to 8
---
1
1 to 18
---
1
0 to 1
---
1
0 to 16
ms
0.5
0 to 1
---
1
MEMORY MAP
Format
Default
F248
0 (None)
F261
1
(Dependabili
ty Biased)
F001
1
F123
0 (1 A)
F001
1
F123
0 (1 A)
F100
0 (Wye)
F001
664
F060
1
F166
1 (Vag)
F001
664
F060
1
F636
"FCI 1"
F256
0 (None)
F001
1
F108
0 (Off)
F001
60
F102
1 (Enabled)
2-55
2