CHAPTER 3: IEC 61850 COMMUNICATION
Data object
CDC
Semantics
name
LocSetAcsOff
SPS
Indicates operations of FlexLogic operand ACCESS LOC SETG OFF
LocSetAcsOn
SPS
Indicates operations of FlexLogic operand ACCESS LOC SETG ON
LosLife
MV
XFMR LIFE LOST actual values
LosLifeRte
MV
DAILY RATE LOL actual values
LosPkt1
SPS
The lost packet threshold has been exceeded.
The 87L DIFF CH 1 LOSTPKT operand, which becomes On when the differential
element has detected the lost packet threshold has been exceeded on channel 1.
LossLd
ACT
The high impedance fault phase A, B, C loss of load element has operated
Lower
SPS
PID Lower operand. The PID 1 LOWER operand value.
MAC
VSG
Expected value of Destination MAC address field in messages subscribed to by
RxGOOSE#
MajorErr
SPS
Any of the major self-test errors generated (major error).
The ANY MAJOR ERROR operand.
ManMod
SPS
Capacitor control in manual mode.
The CAP 1 IN MAN operand.
MaxAsymOp1
SPS
Asymmetry on the channel exceeded pre-set value.
The 87L DIFF CH 1 MAX ASYM operand, which becomes On when the Asymmetry
on channel 1 exceeded preset value.
MaxCompHz
MV
The frequency of the learned maximum broken rotor bar spectral component.
MAXIMUM COMPONENT FREQ. in Hz.
MaxCompLevel MV
Indicates the learned maximum level of the broken rotor bar spectral component
since the last data clear.
MAXIMUM COMPONENT LEVEL in dB.
MaxIntrA
MV
Indicates Breaker Arcing Current per phase.
BKR 1 AMP MAX phase A/B/C.
MaxLoadDev
MV
Indicates the motor load standard deviation at the time when data for the
maximum broken rotor bar was acquired.
LOAD DEV. AT BRB MAX in x FLA.
MaxMotLoad
MV
Indicates the average motor load at the time when data for the maximum broken
rotor bar was acquired.
MOTOR LOAD AT BRB MAX in x FLA.
MaxVal1
ASG
Maximum value in deadband calculations
MinorErr
SPS
Any of the minor self-test errors generated (minor error).
The ANY MINOR ERROR operand.
MinVal1
ASG
Minimum value in deadband calculations
MMSConnects
MV
Number of MMS client connections active
MnlCls
SPS
Manual close initiated.
The BREAKER 1 MNL CLS operand.
MnlOpn
SPS
Manual open initiated.
The BREAKER 1 MNL OPEN operand.
Month1
SPS
Current month, where 1 = January.
The MONTH operand.
MotLoad
MV
The average motor load at the time of the broken rotor bar data acquisition stage.
MOTOR LOAD AT BRB CALC. in x FLA
MotStatus
ENS
Indicated the status of the motor (in Actual Values) where 0 = Offline, 1= Starting,
2 = Running and 3 = Overload.
Thermal Model MOTOR STATUS.
MotUnb
MV
% thermal model motor unbalance.
THERMAL MODEL MOTOR UNBALANCE in percentage (%).
NegTotVArh
MV
SRC 1 Total VAr-hour in negative direction
NegTotWh
MV
SRC 1 Total Watt-hour in negative direction
NeutOpn
SPS
Indicates source has lost voltage signal.
The SRC1 VT NEU WIRE OPEN operand.
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Used in logical nodes...
SecGSAL
SecGSAL
LosLifSPTR
LosLifSPTR
LinDfPDIF
HiZPHIZ
PIDRegFPID
LGOS
LPHD
CapCtlGAPC
LinDfPDIF
BknRotSVBR
BknRotSVBR
CBArcΘSCBR
BknRotSVBR
BknRotSVBR
TDCInGGIO1,
TDCOutGGIO1
LPHD
TDCInGGIO1,
TDCOutGGIO1
LPHD
Bkr0XCBR
Bkr0XCBR
TmDayGAPC
BknRotSVBR
MotThmPTTR
MotThmPTTR
EnrMtrMMTR
EnrMtrMMTR