CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
6112
87PC Trip Security
"
6113
87PC Second Coincidence Timer
"
6114
87PC Enhanced Stability Angle
"
6115
87PC FDH Supervision
"
6117
87PC Pickup Delay
"
6118
87PC Stop Tx
"
611A
87PC Tx Reset Delay
Continuous Monitor (Read/Write Setting)
L90
6130
Continuous Monitor Function
"
6131
Continuous Monitor I (current) OP
"
6133
Continuous Monitor I (current) Supervision
"
6135
Continuous Monitor V (voltage) OP
"
6137
Continuous Monitor V (voltage) Supervision 0 to 4294967295
"
6139
Continuous Monitor Target
"
613A
Continuous Monitor Events
Transformer Hottest Spot (Read/Write Grouped Setting)
G30, T35, T60
6140
Transformer Hottest Spot Function
"
6141
Transformer Hottest Spot Pickup
"
6142
Transformer Hottest Spot Delay
"
6143
Transformer Hottest Spot Block
"
6145
Transformer Hottest Spot Target
"
6146
Transformer Hottest Spot Events
Transformer Aging Factor (Read/Write Grouped Setting)
G30, T35, T60
6150
Transformer Aging Factor Function
"
6151
Transformer Aging Factor Pickup
"
6152
Transformer Aging Factor Delay
"
6153
Transformer Aging Factor Block
"
6155
Transformer Aging Factor Target
"
6156
Transformer Aging Factor Events
Transformer Loss of Life (Read/Write Grouped Setting)
G30, T35, T60
6160
Transformer Loss of Life Function
"
6161
XFMR LOL Initial Value
"
6163
Transformer Loss of Life Pickup
"
6165
Transformer Loss Of Life Block
"
6167
Transformer Loss of Life Target
"
6168
Transformer Loss of Life Events
Transformer Thermal Inputs (Read/Write Setting)
G30, T35, T60
6170
Transformer Thermal Model Source Input
"
6171
Ambient Temperature Input Sensor
"
6172
Top Oil Temperature Input Sensor
"
6173
January Average Ambient Temperature
"
6174
February Average Ambient Temperature
"
6175
March Average Ambient Temperature
"
6176
April Average Ambient Temperature
"
6177
May Average Ambient Temperature
"
6178
June Average Ambient Temperature
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
10 to 200
ms
1
40 to 180
°
5
0 to 4294967295
---
1
0 to 50
ms
1
0 to 4294967295
---
1
0 to 1000
ms
1
0 to 1
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
50 to 300
°C
1
0 to 30000
min
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
1 to 10
PU
0.1
0 to 30000
min
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 500000
hrs
1
0 to 500000
hrs
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 5
---
1
0 to 32
---
1
0 to 32
---
1
-60 to 60
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
-60 to 60
°C
1
MEMORY MAP
Format
Default
F534
0 (First
Coincidence)
F001
40
F001
110
F300
0
F001
0
F300
0
F001
0
F102
0 (Disabled)
F300
0
F300
0
F300
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
140
F001
1
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
20
F001
10
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F003
0
F003
180000
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F167
0 (SRC 1)
F450
0
F460
0
F002
-20
F002
-30
F002
-10
F002
10
F002
20
F002
30
2-81
2