GE B30 Communications Manual page 313

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-67: Negative sequence directional overcurrent data objects
LNName: NegDocRDIR#
data obj. data attribute
Type
Dir
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
FwdOp
SPS
stVal
BOOLEAN
RvOp
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.39 Negative sequence instantaneous overcurrent (NegIoc)
This element is instantiated in the following products: C70, D30, D60, F35, F60, L30, L60, L90, T60.
Table 3-68: Negative sequence instantaneous overcurrent
LNName: NegIocPIOC#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.40 Negative sequence overvoltage (NegOv)
This element is instantiated in the following products: C70, D30, D60, F60, G30, G60, L30, L60, M60, T60.
Table 3-69: Negative sequence overvoltage data objects
LNName: NegOvPTOV#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Negative sequence Directional Overcurrent element #
FC UR Name
ST
logical OR of operands NEG DIR
OC# FWD and NEG DIR OC# REV
ST
ST
NEG SEQ DIR OC# FWD
ST
NEG SEQ DIR OC# REV
NEG SEQ DIR OC# BLOCK for
group γ.
LDevice inst: Prot
UR element: Negative sequence Instantaneous Overcurrent element #
FC UR Name
ST
NEG SEQ IOC# PKP
ST
ST
NEG SEQ IOC# OP
ST
NEG SEQ IOC# DPO
NEG SEQ IOC# BLOCK.
LDevice inst: Prot
UR element: Negative Sequence Overvoltage element # functions
FC UR Name
ST
NEG SEQ # PKP
ST
ST
NEG SEQ OV # OP
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
NEG DIR OC# FWD or NEG DIR OC# REV
operands, which becomes On when
Negative sequence directional
overcurrent is flowing in either forward or
reverse direction respectively
1 for forward 2 for backward 0 for none 3
for both
NEG SEQ DIR OC# FWD operand
NEG SEQ DIR OC# REV operand
NEG SEQ DIR OC# BLOCK setting for
setting group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
NEG SEQ IOC# PKP operand, which is
indicates Op will operate when delay
expires.
0, the code for unknown.
NEG SEQ IOC# OP operand
NEG SEQ IOC# DPO operand
NEG SEQ IOC# BLOCK setting in setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
NEG SEQ OV # PKP operands (including
individual three phases)
0, the code for unknown. It is unknown as
the element is non-directional
NEG SEQ OV # OP operand (including
individual three phases)
R/W/C
R
R
R
R
R
R
R
3
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
3-75