CHAPTER 6: IEC 60870-5-104 COMMUNICATION
Parameter loading
Threshold value
Smoothing factor
Low limit for transmission of measured values
High limit for transmission of measured values
Parameter activation
Activation/deactivation of persistent cyclic or periodic transmission of the addressed object
Test procedure
Test procedure
File transfer
File transfer in monitor direction:
Transparent file
Transmission of disturbance data of protection equipment
Transmission of sequences of events
Transmission of sequences of recorded analog values
File transfer in control direction:
Transparent file
Background scan
Background scan
Acquisition of transmission delay
Acquisition of transmission delay
Definition of time outs
Parameter
Default value Remarks
t
30 s
0
t
15 s
1
t
10 s
2
t
20 s
3
Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s.
Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w)
Parameter
Default value Remarks
k
12 APDUs
w
8 APDUs
Maximum range of values k:1 to 32767 (2
Maximum range of values w:1 to 32767 APDUs, accuracy 1 APDU
Recommendation: w should not exceed two-thirds of k.
UR FAMILY – COMMUNICATIONS GUIDE
Timeout of connection establishment
Timeout of send or test APDUs
Timeout for acknowledgements in case of no data messages t
Timeout for sending test frames in case of a long idle state
Maximum difference receive sequence number to send state variable
Latest acknowledge after receiving w I-format APDUs
15
– 1) APDUs, accuracy 1 APDU
INTEROPERABILITY DOCUMENT
Selected value
120 s
15 s
< t
10 s
2
1
20 s
Selected value
12 APDUs
8 APDUs
6-9
6