GE B30 Communications Manual page 201

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
C60, N60
EA4C
...Repeated for PMU 2
N60
EA4E
...Repeated for PMU 3
"
EA50
...Repeated for PMU 4
"
EA52
...Repeated for PMU 5
"
EA54
...Repeated for PMU 6
Phasor Measurement Unit Voltage Trigger (Read/Write Setting) (1, 2, or 6 Modules)
C60, D60, F60,
EA56
PMU 1 Volt Trigger Function
G60, L30, L90,
N60, T60
"
EA57
PMU 1 Voltage Trigger Low Volt
"
EA58
PMU 1 Voltage Trigger High Volt
"
EA59
PMU 1 Voltage Trigger Pkp Time
"
EA5A
PMU 1 Voltage Trigger Dpo Time
"
EA5B
PMU 1 Voltage Trigger Block (3 items)
"
EA61
PMU 1 Voltage Trigger Target
"
EA62
PMU 1 Voltage Trigger Events
C60, N60
EA63
...Repeated for PMU 2
N60
EA70
...Repeated for PMU 3
"
EA7D
...Repeated for PMU 4
"
EA8A
...Repeated for PMU 5
"
EA97
...Repeated for PMU 6
Phasor Measurement Unit Current Trigger (Read/Write Setting (1, 2, or 6 Modules)
C60, D60, F60,
EAA4
PMU 1 Current Trigger Function
G60, L30, L90,
N60, T60
"
EAA5
PMU 1 Current Trigger Pickup
"
EAA6
PMU 1 Current Trigger Pkp Time
"
EAA7
PMU 1 Current Trigger Dpo Time
"
EAA8
PMU 1 Current Trigger Block (3 items)
"
EAAE
PMU 1 Current Trigger Target
"
EAAF
PMU 1 Current Trigger Events
C60, N60
EAB0
...Repeated for PMU 2
N60
EABC
...Repeated for PMU 3
"
EAC8
...Repeated for PMU 4
"
EAD4
...Repeated for PMU 5
"
EAE0
...Repeated for PMU 6
Phasor Measurement Unit Frequency Trigger (Read/Write Setting) (1, 2, or 6 Modules)
C60, D60, F60,
EAEC
PMU 1 Frequency Trigger Function
G60, L30, L90,
N60, T60
"
EAED
PMU 1 Frequency Trigger Low Frequency
"
EAEE
PMU 1 Frequency Trigger High Frequency
"
EAEF
PMU 1 Frequency Trigger Pickup Time
"
EAF0
PMU 1 Frequency Trigger Dropout Time
"
EAF1
PMU 1 Frequency Trigger Block (3 items)
"
EAF7
PMU 1 Frequency Trigger Target
"
EAF8
PMU 1 Frequency Trigger Events
C60, N60
EAF9
...Repeated for PMU 2
N60
EB06
...Repeated for PMU 3
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
0.25 to 1.25
pu
0.001 F001
0.75 to 1.75
pu
0.001 F001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0.1 to 30
pu
0.001 F001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
20 to 70
Hz
0.01
20 to 70
Hz
0.01
0 to 600
s
0.01
0 to 600
s
0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
MEMORY MAP
Format
Default
F102
0 (Disabled)
800
1200
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
1800
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
4900
F001
6100
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
2-181