CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-64: Mechanical jam data objects
LNName: MecJamPMSS1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.36 Motor acceleration time (MAccTm)
This element is instantiated in the following products: M60.
Table 3-65: Motor acceleration time data objects
LNName: MAccTmPMSS1
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
StrAccTmζ
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
Analogue Value MX
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32
zeroDb
INT32
StrEffAζ
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
Analogue Value MX
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32
zeroDb
INT32
StrPeakAζ
MV
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: MECHANICAL JAM element
FC UR Name
ST
MECHANICAL JAM PKP
ST
ST
MECHANICAL JAM OP
ST
MECHANICAL JAM DPO
MECH JAM BLK for group γ
LDevice inst: Prot
UR element: Acceleration Time element
FC UR Name
ST
MOTOR ACCEL TIME OP
ST
MOTOR ACCEL TIME DPO
ACCELERATION BLOCK.
MX
START ζ ACCELERATION TIME
instMag.f on deadband
exception
CF
CF
MAccTmPMSS1.StrAccTmζ.db
CF
MX
START ζ EFFECTIVE CURRENT
instMag.f on deadband
exception
CF
CF
MAccTmPMSS1.StrEffAζ.db
CF
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
MECHANICAL JAM PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
MECHANICAL JAM OP operand
MECHANICAL JAM DPO operand, which is
the inverse of MECHANICAL JAM PKP
MECH JAM BLK setting for setting group γR
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
MOTOR ACCEL TIME OP operand
MOTOR ACCEL TIME DPO operand
ACCELERATION BLOCK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
START ζ ACCELERATION TIME in Sec
4, the code for Time (Sec)
0, the code for a multiplier of 1
0
START ζ EFFECTIVE CURRENT in x FLA
1, the code for dimension less
0, the code for a multiplier of 1
0
START ζ PEAK CURRENT in x FLA
R/W/C
R
R
R
R
R
R
R
R/C
3
R/C
R/W/C
R
R
R
R
R
R/C
R/C
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
3-71

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents