GE B30 Communications Manual page 131

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
7393
Disconnect Switch 1 Events
"
7394
Reserved
"
7395
...Repeated for Disconnect Switch 2
"
73BA
...Repeated for Disconnect Switch 3
"
73DF
...Repeated for Disconnect Switch 4
"
7404
...Repeated for Disconnect Switch 5
"
7429
...Repeated for Disconnect Switch 6
"
744E
...Repeated for Disconnect Switch 7
"
7473
...Repeated for Disconnect Switch 8
B30, C60, C70,
7498
...Repeated for Disconnect Switch 9
D60, F35, F60,
L90, N60, T35,
T60
"
74BD
...Repeated for Disconnect Switch 10
"
74E2
...Repeated for Disconnect Switch 11
"
7507
...Repeated for Disconnect Switch 12
B30, C60, D60,
752C
...Repeated for Disconnect Switch 13
F35, F60, L90,
N60, T35, T60
"
7551
...Repeated for Disconnect Switch 14
"
7576
...Repeated for Disconnect Switch 15
"
759B
...Repeated for Disconnect Switch 16
B30, C60, F35,
75C0
...Repeated for Disconnect Switch 17
L90, N60, T35,
T60
"
75E5
...Repeated for Disconnect Switch 18
"
760A
...Repeated for Disconnect Switch 19
"
762F
...Repeated for Disconnect Switch 20
"
7654
...Repeated for Disconnect Switch 21
"
7679
...Repeated for Disconnect Switch 22
"
769E
...Repeated for Disconnect Switch 23
"
76C3
...Repeated for Disconnect Switch 24
Instantaneous Overcurrent (Read/Write Grouped Setting) (24 Modules)
B90
7600
Instantaneous Overcurrent 1 Function
"
7601
Instantaneous Overcurrent 1 CT
"
7602
Instantaneous Overcurrent 1 Pickup
"
7603
Instantaneous Overcurrent 1 Pickup Delay 0 to 65.535
"
7604
Instantaneous Overcurrent 1 Reset Delay
"
7605
Instantaneous Overcurrent 1 Block
"
7607
Instantaneous Overcurrent 1 Target
"
7608
Instantaneous Overcurrent 1 Events
"
7609
Reserved (2 items)
"
760A
...Repeated for Instantaneous Overcurrent
2
"
7614
...Repeated for Instantaneous Overcurrent
3
"
761E
...Repeated for Instantaneous Overcurrent
4
"
7628
...Repeated for Instantaneous Overcurrent
5
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
---
---
---
0 to 1
---
1
0 to 23
---
1
0.005 to 30
pu
0.001 F001
s
0.001 F001
0 to 65.535
s
0.001 F001
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 65535
---
1
MEMORY MAP
Format
Default
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F400
0
1200
0
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
2-111
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents