MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: SenPDOP#
data obj. data attribute
TotW
instMag
instMag.f
mag
mag.f
units
units.SIUnit
units.multiplier
db
zeroDb
3
BlkRefγ
setSrcRef
setSrcCB
Table 3-113: Sensitive directional power stage 1 data objects
LNName: Sen1PDOP#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
Table 3-114: Sensitive directional power stage 2 data objects
LNName: Sen2PDOP#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
3.5.2.68 Speed 2 motor acceleration time (S2AcTm)
This element is instantiated in the following products: M60.
3-102
LDevice inst: Prot
UR element: Sensitive Directional Power element # core functions
Type
FC UR Name
MV
AnalogueValue
MX
FLOAT32
DIRECTIONAL POWER # 3φ
AnalogueValue
MX
FLOAT32
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
SenPDOP#.TotW.db
INT32U
CF
ORG
ObjectReference SP
DIR POWER # BLK for group γ. reference to the data attribute to input
ObjectReference SP
LDevice inst: Prot
UR element: Sensitive Directional Power element # stage 1 functions
Type
FC UR Name
ACD
BOOLEAN
ST
DIR POWER # STG1 PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
DIR POWER # STG1 OP
SPS
BOOLEAN
ST
DIR POWER # STG1 DPO
LDevice inst: Prot
UR element: Sensitive Directional Power element # stage 2 functions
Type
FC UR Name
ACD
BOOLEAN
ST
DIR POWER # STG2 PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
DIR POWER # STG2 OP
SPS
BOOLEAN
ST
DIR POWER # STG2 DPO
CHAPTER 3: IEC 61850 COMMUNICATION
Description
DIRECTIONAL POWER # 3-PHASE, in
primary watts
DIRECTIONAL POWER # 3φ, deadbanded R
38, the code for primary watts (J/s)
0, the code for a multiplier of 1
3-phase power cut-off level in percent
multiplied by 1000
DIR POWER # BLK setting for setting
group γ.
source GoCB of input if via GOOSE
Description
DIR POWER # STG1 PKP operand, which
becomes On when the directional power
comparator has operated.
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
DIR POWER # STG1 OP operand
DIR POWER # STG1 DPO operand, which
is the inverse of DIR POWER STG1 OP
Description
DIR POWER # STG2 PKP operand, which
becomes On when the directional power
comparator has operated.
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
DIR POWER # STG2 OP operand
DIR POWER # STG2 DPO operand, which
is the inverse of DIR POWER STG2 OP
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R/W/C
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R