GE B30 Communications Manual page 411

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: LLN0
data obj. data attribute
Type
setSrcRef
ObjectReference SP
MltLev
SPG
setVal
BOOLEAN
<TTΣDataS
DATA-SET
et##>
DSMemberRef[η] ObjectReference
3.5.5.2 AC signal sources (ACsrc)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-194: AC signal sources data objects
LNName: ACsrcMMXU#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
TotW
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
TotVAr
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
TotVA
MV
instMag
AnalogueValue
instMag.f
FLOAT32
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Meter
UR element: Nameplate information for the logical nodes
FC UR Name
For communications, mapped to
Master ldName if not empty,
otherwise to the concatenation
of the IED name and "Master".
For SCL, mapped to the
concatenation of the IED name
and "Master".
SP
DataSet Member η
LDevice inst: Meter
UR element: AC Source #
FC UR Name
ST
SRC# 50DD
ST
MX
SRC # Three Phase Real Power
MX
CF
CF
MMXU# TotW DEADBAND
CF
MX
SRC # Three Phase Reactive
Power
MX
CF
CF
MMXU# TotVAr DEADBAND
CF
MX
SRC # Three Phase Apparent
Power
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
reference to the data attribute to input
Instantiated only in the Master logical
device
Description
SRC# 50DD operand, which becomes On
when a disturbance (change in
magnitude of a sequence current greater
than twice the current cutoff level) is
detected on AC Source #.
0, the code for unknown
SRC # Three Phase Real Power, in primary
watts
instMag.f deadbanded
38, the code for primary watts (J/s)
0, the code for a multiplier of 1
power cut-off level.
SRC # Three Phase Reactive Power, in
primary VAr
instMag.f deadbanded
63, the code for primary volt amperes
reactive (VIsinΘ)
0, the code for a multiplier of 1
power cut-off level.
SRC # Three Phase Apparent Power, in
primary VA
R/W/C
R
R
R
R
R/C
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
3-173

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents