Download Print this page

GE C70 Instruction Manual

Capacitor bank protection and control system ur series.
Hide thumbs
   
1
2
Table of Contents
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556
557
558
559
560
561
562
563
564
565
566
567
568
569
570
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
631
632
633
634
635
636
637
638
639
640
641
642
643
644
645
646
647
648
649
650
651
652
653
654
655
656
657
658
659
660
661
662
663
664
665
666
667
668
669
670
671
672
673
674
675
676
677
678
679
680
681
682
683
684
685
686
687
688
689
690
691
692
693
694
695
696
697
698
699
700
701
702
703
704
705
706
707
708

Advertisement

GE
Grid Solutions
GE Grid Solutions
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet:
http://www.GEGridSolutions.com
*1601-9015-AA4*
C70 Capacitor Bank Protection
and Control System
UR Series Instruction Manual
Manual P/N: 1601-9015-AA4 (GEK-119555C)
C70 Revision: 7.2x
E83849
LISTED
IND.CONT. EQ.
52TL
834766A1.CDR
GE Multilin's Quality Management
System is registered to ISO
9001:2008
QMI # 005094
UL # A3775

Advertisement

   Also See for GE C70

   Related Manuals for GE C70

   Summary of Contents for GE C70

  • Page 1

    Grid Solutions C70 Capacitor Bank Protection and Control System UR Series Instruction Manual C70 Revision: 7.2x Manual P/N: 1601-9015-AA4 (GEK-119555C) 834766A1.CDR E83849 GE Grid Solutions LISTED 650 Markland Street IND.CONT. EQ. 52TL Markham, Ontario GE Multilin's Quality Management Canada L6C 0M1...

  • Page 2

    The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.

  • Page 3: Table Of Contents

    1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 SYSTEM REQUIREMENTS ................1-5 1.3.2 INSTALLATION....................1-5 1.3.3 CONFIGURING THE C70 FOR SOFTWARE ACCESS ........1-6 1.3.4 USING THE QUICK CONNECT FEATURE............1-9 1.3.5 CONNECTING TO THE C70 RELAY .............. 1-14 1.3.6 SETTING UP CYBERSENTRY AND CHANGING DEFAULT PASSWORD ... 1-15 1.4 UR HARDWARE...

  • Page 4: Table Of Contents

    USER-PROGRAMMABLE LEDS ..............5-74 5.2.11 USER-PROGRAMMABLE SELF TESTS ............5-77 5.2.12 CONTROL PUSHBUTTONS ................5-78 5.2.13 USER-PROGRAMMABLE PUSHBUTTONS............5-80 5.2.14 FLEX STATE PARAMETERS ................5-86 5.2.15 USER-DEFINABLE DISPLAYS ................5-86 5.2.16 DIRECT INPUTS AND OUTPUTS..............5-89 5.2.17 INSTALLATION ....................5-96 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 5: Table Of Contents

    DCMA INPUTS ....................5-261 5.9.2 RTD INPUTS....................5-262 5.9.3 DCMA OUTPUTS ..................5-264 5.10 TESTING 5.10.1 TEST MODE ....................5-267 5.10.2 FORCE CONTACT INPUTS ................5-268 5.10.3 FORCE CONTACT OUTPUTS ..............5-269 GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 6: Table Of Contents

    BANK PHASE OVERVOLTAGE (ANSI 59B) .............8-1 8.1.3 VOLTAGE DIFFERENTIAL (ANSI 87V) .............8-3 8.1.4 COMPENSATED BANK NEUTRAL VOLTAGE UNBALANCE (ANSI 59NU)..8-6 8.1.5 PHASE CURRENT UNBALANCE (ANSI 60P) ..........8-10 8.1.6 NEUTRAL CURRENT UNBALANCE (ANSI 60N) ..........8-12 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 7: Table Of Contents

    DISPOSAL ..................... 10-11 A. FLEXANALOG AND A.1 PARAMETER LISTS FLEXINTEGER A.1.1 FLEXANALOG ITEMS ..................A-1 A.1.2 FLEXINTEGER ITEMS ..................A-34 PARAMETERS B. MODBUS B.1 MODBUS RTU PROTOCOL COMMUNICATIONS B.1.1 INTRODUCTION....................B-1 B.1.2 PHYSICAL LAYER.....................B-1 GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 8: Table Of Contents

    C.6.1 ACSI BASIC CONFORMANCE STATEMENT ..........C-23 C.6.2 ACSI MODELS CONFORMANCE STATEMENT ..........C-23 C.6.3 ACSI SERVICES CONFORMANCE STATEMENT ......... C-24 C.7 LOGICAL NODES C.7.1 LOGICAL NODES TABLE ................C-27 viii C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 9: Table Of Contents

    RADIUS SERVER CONFIGURATION.............. G-1 H. MISCELLANEOUS H.1 CHANGE NOTES H.1.1 REVISION HISTORY ..................H-1 H.1.2 CHANGES TO THE C70 MANUAL..............H-1 H.2 ABBREVIATIONS H.2.1 STANDARD ABBREVIATIONS .................H-5 H.3 WARRANTY H.3.1 GE MULTILIN WARRANTY ................H-7 GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 10

    TABLE OF CONTENTS C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 11: Cautions And Warnings

    1.1 IMPORTANT PROCEDURES 1 GETTING STARTED 1.1IMPORTANT PROCEDURES Use this chapter for initial setup of your new C70 Capacitor Bank Protection and Control System. 1.1.1 CAUTIONS AND WARNINGS Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment damage, or downtime.

  • Page 12: Inspection Procedure

    • GE EnerVista™ DVD (includes the EnerVista UR Setup software and manuals in PDF format) • Mounting screws If there is any noticeable physical damage, or any of the contents listed are missing, contact GE Grid Solutions as fol- lows.

  • Page 13: Introduction To The Ur

    1.2UR OVERVIEW 1.2.1 INTRODUCTION TO THE UR The GE Universal Relay (UR) series is a new generation of digital, modular, and multifunction equipment that is easily incorporated into automation systems, at both the station and enterprise levels. 1.2.2 HARDWARE ARCHITECTURE...

  • Page 14: Software Architecture

    Employing OOD/OOP in the software architecture of the C70 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functional classes.

  • Page 15: System Requirements

    Ethernet port of the same type as one of the UR CPU ports or a LAN connection to the UR • Internet access or a DVD drive The following qualified modems have been tested to be compatible with the C70 and the EnerVista UR Setup software: • US Robotics external 56K FaxModem 5686 •...

  • Page 16: Configuring The C70 For Software Access

    To configure the C70 for remote access via the rear Ethernet port, see the Configuring Ethernet Communications sec- tion. • To configure the C70 for local access with a computer through either the front RS232 port or rear Ethernet port, see the Using the Quick Connect Feature section. C70 Capacitor Bank Protection and Control System...

  • Page 17

    CONFIGURING SERIAL COMMUNICATIONS A computer with an RS232 port and a serial cable is required. To use the RS485 port at the back of the relay, a GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.

  • Page 18

    MODBUS PROTOCOL 21. Click the Read Order Code button to connect to the C70 device and upload the order code. If an communications error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting values.

  • Page 19: Using The Quick Connect Feature

    USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the C70 from a computer through Ethernet, first assign an IP address to the relay from the front panel keyboard. Press the MENU key until the SETTINGS menu displays.

  • Page 20

    Right-click the Local Area Connection icon and select Properties. Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button. Click the “Use the following IP address” box. 1-10 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 21

    1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE Enter an IP address with the first three numbers the same as the IP address of the C70 relay and the last number dif- ferent (in this example, 1.1.1.2). Enter a subnet mask equal to the one set in the C70 (in this example, 255.0.0.0).

  • Page 22

    If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been discon- nected from the C70 relay. Start the Internet Explorer software. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup. 1-12 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 23

    Click the Quick Connect button to open the Quick Connect dialog box. Select the Ethernet interface and enter the IP address assigned to the C70, then click the Connect button. The EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick Connect”...

  • Page 24: Connecting To The C70 Relay

    The EnerVista UR Setup software has several quick action buttons to provide instant access to several functions that are often performed when using C70 relays. From the online window, users can select the relay to interrogate from a pull-down window, then click the button for the action they want to perform. The following quick action functions are available: •...

  • Page 25: Setting Up Cybersentry And Changing Default Password

    If using EnerVista, navigate to Settings > Product Setup > Security. Change the Local Administrator Password, for example. It is strongly recommended that the password for the Administrator be changed from the default. Changing the passwords for the other three roles is optional. GE Multilin C70 Capacitor Bank Protection and Control System 1-15...

  • Page 26: Mounting And Wiring

    This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the C70 rear communications port. The converter terminals (+, –, GND) are connected to the C70 communication module (+, –, COM) terminals. See the CPU Communica- tion Ports section in chapter 3 for details.

  • Page 27: Faceplate Keypad

    MESSAGE LEFT key from a setting value or actual value display returns to the header display. HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE)  SETTINGS  SECURITY ACCESS LEVEL:  PRODUCT SETUP  Restricted  SETTINGS  SYSTEM SETUP GE Multilin C70 Capacitor Bank Protection and Control System 1-17...

  • Page 28: Relay Activation

    For more information, see the CyberSentry content in the Security section of the next chapter. 1.5.6 FLEXLOGIC CUSTOMIZATION FlexLogic equation editing is required for setting user-defined logic for customizing the relay operations. See the FlexLogic section in Chapter 5. 1-18 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 29: Commissioning

    The C70 performs a number of continual self-tests and takes the necessary action in case of any major errors (see the Relay Self-tests section in chapter 7). However, it is recommended that C70 maintenance be scheduled with other system maintenance.

  • Page 30

    1.5 USING THE RELAY 1 GETTING STARTED 1-20 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 31: Overview

    Ethernet port supports IEC 61850, Modbus/TCP, and TFTP protocols, PTP (according to IEEE Std. 1588-2008 or IEC 61588), and allows access to the relay via any standard web browser (C70 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port. The Ethernet port also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when purchased as an option.

  • Page 32

    Contact inputs (up to 96) Frequency metering User-definable displays Contact outputs (up to 64) IEC 60870-5-103 communications User-programmable fault reports (optional) Control pushbuttons IEC 61850 communications (optional) User-programmable LEDs CyberSentry™ security Modbus communications User-programmable pushbuttons C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 33: Security

    Test mode operation The C70 supports password entry from a local or remote connection. Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear communications port.

  • Page 34

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the C70, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password applies.

  • Page 35

    Remote Output DNA |--------------- Bit Pair Remote Output user |--------------- Bit Pair |--------------- Resetting |--------------- Direct Inputs |--------------- Direct Outputs |--------------- Teleprotection |--------------- Direct Analogs |--------------- Direct Integers IEC61850 GOOSE |--------------- Analogs GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 36

    When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication database to authenticate the user. No password or security information are displayed in plain text by the EnerVista software or UR device, nor are they ever transmitted without cryptographic protection. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 37: Iec 870-5-103 Protocol

    The UR implementation of IEC 60870-5-103 consists of the following functions: • Report binary inputs • Report analog values (measurands) • Commands • Time synchronization The RS485 port supports IEC 60870-5-103. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 38

    2.2ORDER CODES 2.2.1 OVERVIEW The C70 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod- ules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications.

  • Page 39

    G.703, 2 Channels RS422, 2 Channels The order codes for the reduced size vertical mount units are shown below. Table 2–5: C70 ORDER CODES (REDUCED SIZE VERTICAL UNITS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below)

  • Page 40: Order Codes With Process Bus Modules

    RS422, 2 Channels 2.2.3 ORDER CODES WITH PROCESS BUS MODULES The order codes for the horizontal mount units with the process bus module are shown below. Table 2–6: C70 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS MODULE) * - F - W/X...

  • Page 41

    RS422, 2 Channels The order codes for the reduced size vertical mount units with the process bus module are shown below. Table 2–7: C70 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS MODULE) * - F Reduced Size Vertical Mount (see note regarding P/R slot below)

  • Page 42

    2.2 ORDER CODES 2 PRODUCT DESCRIPTION Table 2–7: C70 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS MODULE) * - F Reduced Size Vertical Mount (see note regarding P/R slot below) POWER SUPPLY 125 / 250 V AC/DC power supply...

  • Page 43: Replacement Modules

    Replacement modules can be ordered separately. When ordering a replacement CPU module or faceplate, provide the serial number of your existing unit. Not all replacement modules may be applicable to the C70 relay. Only the modules specified in the order codes are available as replacement modules.

  • Page 44

    Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels 2-14 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 45: Ur Signal Processing

    The sampling rate is dynamically adjusted to the actual system frequency by an accurate and fast frequency tracking system. The A/D converter has the following ranges of AC signals: Voltages: ± ⋅ 260 V (EQ 2.1) Currents: GE Multilin C70 Capacitor Bank Protection and Control System 2-15...

  • Page 46

    61850 services, ICD/CID/IID files, and so on), IEEE 1588 (IEEE C37.238 power profile) based time synchronization, Cyber- Sentry (advanced cyber security), the Parallel Redundancy Protocol (PRP), IEC 60870-5-103, and so on. 2-16 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 47: Protection Elements

    Open delay: 0 to 65.353 s in steps of 0.001 Timer accuracy: ±3% of operate time or ±20 ms, which- ever is greater Operate time: <80 ms at 60 Hz GE Multilin C70 Capacitor Bank Protection and Control System 2-17...

  • Page 48

    Pickup delay: 0 to 600.00 s in steps of 0.01 Timer accuracy: ±3% of operate time or ±35 ms, which- ever is greater Operate time: <35 ms at 60 Hz 2-18 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 49

    0 to 600.00 s in steps of 0.01 Timer accuracy: ±3% of operate time or ±20 ms, which- ever is greater <30 ms at 1.10 × pickup at 60 Hz Operate time: GE Multilin C70 Capacitor Bank Protection and Control System 2-19...

  • Page 50: User-programmable Elements

    Number: up to 256 logical variables grouped tual input under 16 Modbus addresses Reset mode: self-reset or latched Programmability: any logical variable, contact, or virtual input 2-20 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 51: Monitoring

    ±0.5% of reading from 10 to 208 V 0.1 to 2.0 × CT rating: ±0.25% of reading or ±0.1% of rated (whichever is greater) > 2.0 × CT rating: ±1.0% of reading GE Multilin C70 Capacitor Bank Protection and Control System 2-21...

  • Page 52: Inputs

    Debounce time: 0.0 to 16.0 ms in steps of 0.5 Continuous current draw:4 mA (when energized) Auto-burnish impulse current: 50 to 70 mA Duration of auto-burnish impulse: 25 to 50 ms 2-22 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 53: Power Supply

    0.2 A Operate time: < 4 ms Operate time: < 4 ms Contact material: silver alloy Contact material: silver alloy Control: separate operate and reset inputs Control mode: operate-dominant or reset-dominant GE Multilin C70 Capacitor Bank Protection and Control System 2-23...

  • Page 54

    99% Settling time to a step change: 100 ms Isolation: 1.5 kV Driving signal: any FlexAnalog quantity Upper and lower limit for the driving signal: –90 to 90 pu in steps of 0.001 2-24 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 55: Communication Protocols

    29 dB Single mode 1550 nm Laser, +5 dBm –30 dBm 35 dB Single mode These power budgets are calculated from the manu- facturer’s worst-case transmitter power and worst NOTE GE Multilin C70 Capacitor Bank Protection and Control System 2-25...

  • Page 56: Environmental

    – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Noise: 0 dB Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days). 2-26 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 57: Type Tests

    IEC 60255-27 Insulation: class 1, Pollution degree: 2, Over voltage cat II 2.4.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. GE Multilin C70 Capacitor Bank Protection and Control System 2-27...

  • Page 58: Approvals

    To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. 2-28 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 59: Panel Cutout

    HORIZONTAL UNITS The C70 Capacitor Bank Protection and Control System is available as a 19-inch rack horizontal mount unit with a remov- able faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced face- plate contains additional user-programmable pushbuttons and LED indicators.

  • Page 60

    VERTICAL UNITS The C70 Capacitor Bank Protection and Control System is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.

  • Page 61

    3 HARDWARE 3.1 DESCRIPTION Figure 3–4: C70 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 62

    3.1 DESCRIPTION 3 HARDWARE Figure 3–5: C70 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For side mounting C70 devices with the enhanced front panel, see the following documents available on the UR DVD and the GE Grid Solutions website: • GEK-113180: UR-Series UR-V Side-Mounting Front Panel Assembly Instructions •...

  • Page 63

    3 HARDWARE 3.1 DESCRIPTION Figure 3–6: C70 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL) GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 64

    3.1 DESCRIPTION 3 HARDWARE Figure 3–7: C70 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL) C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 65: Rear Terminal Layout

    (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following figure for an example of rear terminal assignments. Figure 3–9: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 66: Typical Wiring

    3.2 WIRING 3 HARDWARE 3.2WIRING 3.2.1 TYPICAL WIRING Figure 3–10: TYPICAL WIRING DIAGRAM (T MODULE SHOWN FOR CPU) C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 67: Dielectric Strength

    (see the Self-test Errors section in chapter 7) or control power is lost, the relay is de-energize. For high reliability systems, the C70 has a redundant option in which two C70 power supplies are placed in parallel on the bus.

  • Page 68: Ct/vt Modules

    CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram. The exact placement of a zero-sequence core balance CT to detect ground fault current is shown as follows. Twisted-pair cabling on the zero-sequence CT is recommended. 3-10 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 69

    8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs) Current inputs 8H, 8J, 8N, and 8R modules (8 CTs) Voltage inputs 8V modules (8 VTs) 842809A1.CDR Figure 3–13: CT/VT MODULE WIRING GE Multilin C70 Capacitor Bank Protection and Control System 3-11...

  • Page 70: Process Bus Modules

    3.2.5 PROCESS BUS MODULES The C70 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bidirectional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.

  • Page 71

    Logic operand driving the contact output should be given a reset delay of 10 ms to prevent damage of the output contact (in situations when the element initiating the contact output is bouncing, at val- ues in the region of the pickup value). GE Multilin C70 Capacitor Bank Protection and Control System 3-13...

  • Page 72

    2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs 3-14 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 73

    2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used GE Multilin C70 Capacitor Bank Protection and Control System 3-15...

  • Page 74

    3.2 WIRING 3 HARDWARE Figure 3–15: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) 3-16 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 75

    3.2 WIRING Figure 3–16: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output con- nections. GE Multilin C70 Capacitor Bank Protection and Control System 3-17...

  • Page 76

    Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. 3-18 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 77

    CONTACT INPUT 1 AUTO-BURNISH = OFF CONTACT INPUT 2 AUTO-BURNISH = ON CONTACT INPUT 1 AUTO-BURNISH = ON CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–19: AUTO-BURNISH DIP SWITCHES GE Multilin C70 Capacitor Bank Protection and Control System 3-19...

  • Page 78: Transducer Inputs/outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE Figure 3–20: TRANSDUCER INPUT/OUTPUT MODULE WIRING The following figure show how to connect RTDs. 3-20 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 79

    3 HARDWARE 3.2 WIRING Figure 3–21: RTD CONNECTION GE Multilin C70 Capacitor Bank Protection and Control System 3-21...

  • Page 80: Rs232 Faceplate Port

    3.2.8 RS232 FACEPLATE PORT A 9-pin RS232C serial port is located on the C70 faceplate for programming with a computer. All that is required to use this interface is a computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.

  • Page 81

    This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the C70 COM terminal (#3); others function cor- rectly only if the common wire is connected to the C70 COM terminal, but insulated from the shield.

  • Page 82

    The fiber optic communication ports allow for fast and efficient communications between relays at 100 Mbps. Optical fiber can be connected to the relay supporting a wavelength of 1310 nm in multi-mode. 3-24 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 83: Irig-b

    IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The IRIG-B code allows time accuracies of up to 100 ns. Using the IRIG-B input, the C70 operates an internal oscillator with 1 µs resolution and accuracy.

  • Page 84: Description

    1 to channel 2 on UR2, the setting should be “Enabled” on UR2. This DIRECT I/O CHANNEL CROSSOVER forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1. 3-26 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 85: Fiber: Led And Eled Transmitters

    3.3.2 FIBER: LED AND ELED TRANSMITTERS The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules. Figure 3–29: LED AND ELED FIBER MODULES GE Multilin C70 Capacitor Bank Protection and Control System 3-27...

  • Page 86: G.703 Interface

    Remove the module cover screw. Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. 3-28 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 87

    Loop Timing Mode: The system clock is derived from the received line signal. Therefore, the G.703 timing selection should be in loop timing mode for connections to higher order systems. For connection to a higher order system (UR- GE Multilin C70 Capacitor Bank Protection and Control System 3-29...

  • Page 88

    G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–34: G.703 DUAL LOOPBACK MODE 3-30 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 89: Rs422 Interface

    If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. GE Multilin C70 Capacitor Bank Protection and Control System 3-31...

  • Page 90

    Figure 3–37: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, THREE-TERMINAL APPLICATION Data module 1 provides timing to the C70 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they vary by manufacturer.

  • Page 91: Ieee C37.94 Interface

    5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of C70 communica- tion for two and three terminal applications.

  • Page 92

    Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is fully inserted. 3-34 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 93

    Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the follow- ing figure. Figure 3–40: STATUS LEDS The clock configuration LED status is as follows: • Flashing green — loop timing mode while receiving a valid data packet GE Multilin C70 Capacitor Bank Protection and Control System 3-35...

  • Page 94

    Solid yellow — FPGA is receiving a "yellow bit" and remains yellow for each "yellow bit" • Solid red — FPGA is not receiving a valid packet or the packet received is invalid 3-36 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 95: Introduction

    In online mode, you can communicate with the device in real-time. The EnerVista UR Setup software is provided with every C70 relay and runs on Microsoft Windows XP, 7, and Server 2008. This chapter provides a summary of the basic EnerVista UR Setup software interface features. The EnerVista UR Setup Help File provides details for getting started and using the EnerVista UR Setup software interface.

  • Page 96

    Site List window are automatically sent to the online communicating device. g) FIRMWARE UPGRADES The firmware of a C70 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.

  • Page 97: Enervista Ur Setup Main Window

    Settings list control bar window Device data view windows, with common tool bar Settings file data view windows, with common tool bar Workspace area with data view tabs Status bar 10. Quick action hot links GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 98

    4.1 ENERVISTA UR SETUP INTERFACE 4 HUMAN INTERFACES 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 99: Settings Templates

    Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 100

    The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 101

    The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 102

    Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 103: Securing And Locking Flexlogic Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic equation. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 104

    FlexLogic entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. 4-10 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 105: Settings File Traceability

    When a settings file is transferred to a C70 device, the date, time, and serial number of the C70 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the C70 actual values at any later date to determine if security has been compromised.

  • Page 106

    4 HUMAN INTERFACES The transfer date of a setting file written to a C70 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.

  • Page 107

    ONLINE DEVICE TRACEABILITY INFORMATION The C70 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.

  • Page 108: Faceplate

    The following figure shows the horizontal arrange- ment of the faceplate panels. Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS 4-14 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 109: Led Indicators

    The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. GE Multilin C70 Capacitor Bank Protection and Control System 4-15...

  • Page 110

    Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack- age of every C70, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.

  • Page 111

    User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program the operation of the LEDs on these panels. GE Multilin C70 Capacitor Bank Protection and Control System 4-17...

  • Page 112: Custom Labeling Of Leds

    EnerVista UR Setup software is installed and operational • The C70 settings have been saved to a settings file • The C70 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://www.gegridsolutions.com/products/support/ur/URLEDenhanced.doc and printed •...

  • Page 113

    Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the C70 front panel label cutout sheet into a printer and press the Print button in the front panel report window.

  • Page 114

    4 HUMAN INTERFACES Bend the tab at the center of the tool tail as shown below. The following procedure describes how to remove the LED labels from the C70 enhanced front panel and insert the custom labels. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay.

  • Page 115

    Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below. The following procedure describes how to remove the user-programmable pushbutton labels from the C70 enhanced front panel and insert the custom labels.

  • Page 116

    Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This attaches the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. 4-22 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 117: Display

    INTRODUCTION The C70 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, that can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from faceplate keypad or automatically initiated from a FlexLogic operand.

  • Page 118: Menus

    Press the MENU key to select a header display page (top-level menu). The header title appears momentarily followed by a header display page menu item. Each press of the MENU key advances through the following main heading pages: • Actual values • Settings 4-24 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 119

    4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE • Commands • Targets • User displays (when enabled) GE Multilin C70 Capacitor Bank Protection and Control System 4-25...

  • Page 120

    Pressing the MESSAGE DOWN key displays the second setting sub-header associ-  PROPERTIES ated with the Product Setup header.  Press the MESSAGE RIGHT key once more to display the first setting for Display FLASH MESSAGE Properties. TIME: 1.0 s 4-26 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 121: Changing Settings

    Text settings have data values which are fixed in length, but user-defined in character. They can be upper case letters, lower case letters, numerals, and a selection of special characters. GE Multilin C70 Capacitor Bank Protection and Control System 4-27...

  • Page 122

    The information in this section refers to password security. For information on how to set or change CyberSentry pass- words, see the Settings > Product Setup > Security > CyberSentry section in the next chapter. 4-28 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 123

    By default, when an incorrect Command or Setting password has been entered via the faceplate interface three times within three minutes, the FlexLogic operand is set to “On” and the C70 does not allow settings or LOCAL ACCESS DENIED command level access via the faceplate interface for the next five minutes.

  • Page 124

    FlexLogic operand is set to “Off” after five minutes for a Command password or 30 minutes for a Settings password. These default settings can be changed in EnerVista under Settings > Product Setup > Security. 4-30 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 125: Settings Menu

     SETTINGS  AC INPUTS See page 5-98.  SYSTEM SETUP   POWER SYSTEM See page 5-99.   SIGNAL SOURCES See page 5-101.   BREAKERS See page 5-104.  GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 126

    See page 5-230.   MONITORING See page 5-232.  ELEMENTS  SETTINGS  CONTACT INPUTS See page 5-245.  INPUTS / OUTPUTS   VIRTUAL INPUTS See page 5-247.  C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 127

    TEST MODE See page 5-267.  TESTING FUNCTION: Disabled TEST MODE FORCING: See page 5-267.  FORCE CONTACT See page 5-268.  INPUTS  FORCE CONTACT See page 5-269.  OUTPUTS GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 128: Introduction To Elements

    In more complex elements, a set of settings may be provided to define the range of the measured parameters which will cause the element to pickup. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 129: Introduction To Ac Sources

    The same considerations apply to transformer winding 2. The protection elements require access to the net current for transformer protection, but some elements may need access to the individual currents from CT1 and CT2. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 130

    CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3 < bank 1 > < bank 3 > < bank 5 > < bank 2 > < bank 4 > < bank 6 > C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 131

    Upon startup, the CPU configures the settings required to characterize the current and voltage inputs, and will display them in the appropriate section in the sequence of the banks (as described above) as follows for a maximum configuration: F1, F5, M1, M5, U1, and U5. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 132

    To reset the unit after a lost password: Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email account. Customer service provides a code to reset the relay to the factory defaults.

  • Page 133

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the C70, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.

  • Page 134

    When lockout occurs, the LOCAL ACCESS DENIED FlexLogic operands are set to “On”. These operands are returned to the “Off” state upon REMOTE ACCESS DENIED expiration of the lockout. 5-10 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 135

    INVALID ATTEMPTS BEFORE LOCKOUT The C70 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is UNAUTHORIZED ACCESS asserted.

  • Page 136

    It is disabled by default to allow the administrator direct access to the EnerVista software immediately after installation. When security is disabled, all users have administrator access. GE recommends enabling the EnerVista security before placing the device in service.

  • Page 137

    Enter a username in the User field. The username must be 4 to 20 characters in length. Select the user access rights by enabling the check box of one or more of the fields. GE Multilin C70 Capacitor Bank Protection and Control System 5-13...

  • Page 138

    Deletes the user account when exiting the user management window Actual Values Allows the user to read actual values Settings Allows the user to read setting values Commands Allows the user to execute commands 5-14 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 139

    Note that other protocols (DNP, 101, 103, 104, EGD) are not encrypted, and they are good communications options for SCADA systems when CyberSentry is enabled. CYBERSENTRY SETTINGS THROUGH ENERVISTA CyberSentry security settings are configured under Device > Settings > Product Setup > Security. GE Multilin C70 Capacitor Bank Protection and Control System 5-15...

  • Page 140

    Number of retries before giving up 9999 Administrator Confirm RADIUS Confirmation of the shared secret. The See the 245 characters Administrator Authentication entry displays as asterisks. Password (Shared) Secret Requirement s section 5-16 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 141

    If Yes and a (Administrator if settings change attempt is made, the device Supervisor has alarm activates. If No, the device alarm does not been disabled) activate. GE Multilin C70 Capacitor Bank Protection and Control System 5-17...

  • Page 142

    PRODUCT SETUP SECURITY CHANGE LOCAL PASSWORDS Range: 20 Alphanumeric Characters  CHANGE LOCAL LOGIN:  PASSWORDS None Range: 20 Alphanumeric Characters NEW PASSWORD: MESSAGE Range: 20 Alphanumeric Characters CONFIRM PASSWORD: MESSAGE 5-18 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 143

    LOAD FACTORY DEFAULTS: This setting is used to reset all the settings, communication and security passwords. An Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it. GE Multilin C70 Capacitor Bank Protection and Control System 5-19...

  • Page 144

    Administrator if the Supervisor role is disabled. The Supervisor role enables this setting for the relay to start accepting setting changes or command changes or firmware upgrade. After all the setting changes are applied or com- mands executed, the Supervisor disables to lock setting changes. 5-20 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 145

    Observer). When using a serial connection, only device authentication is supported. When server authentication is required, characteristics for communication with a RADIUS server must be configured. This is possible only in the EnerV- GE Multilin C70 Capacitor Bank Protection and Control System 5-21...

  • Page 146

    Date & Timestamp — UTC date and time Username — 255 chars maximum, but in the security log it is truncated to 20 characters IP address — Device IP address 5-22 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 147

    Clear energy command was issued RESET_UNAUTH_ACCESS Warning (4) Reset Unauthorized access command was issued CLEAR_TELEPROTECTION_CNT Notice (5) Clear teleprotection counters command was issued CLEAR_ALL_RECS Warning (4) Clear all records command was issued GE Multilin C70 Capacitor Bank Protection and Control System 5-23...

  • Page 148: Display Properties

    Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The C70 applies a cut- off value to the magnitudes and angles of the measured currents.

  • Page 149: Clear Relay Records

    Range: FlexLogic operand CLEAR DATA LOGGER: MESSAGE Range: FlexLogic operand RESET UNAUTH ACCESS: MESSAGE Range: FlexLogic operand. CLEAR DIR I/O STATS: MESSAGE Valid only for units with Direct I/O module. GE Multilin C70 Capacitor Bank Protection and Control System 5-25...

  • Page 150: Communications

    Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-programma- ble pushbuttons to clear specific records are typical applications for these commands. Since the C70 responds to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.

  • Page 151

    ETHERNET NETWORK TOPOLOGY The C70 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND oper- ation performed between their respective IP address and mask produces a different result.

  • Page 152

    In this configuration, P3 uses the IP and MAC address of P2. Figure 5–5: MULTIPLE LANS, WITH REDUNDANCY Public Network SCADA EnerVista Software LAN1 LAN2 LAN2 ML3000 ML3000 ML3000 IP1/ IP2/ IP2/ MAC2 MAC2 MAC1 Redundancy mode 859709A4.vsd 5-28 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 153

    IP addresses and mask. Configure the network IP and subnet settings before configuring the rout- ing settings. To obtain a list of all port numbers used, for example for audit purposes, contact GE technical support with substantiating information, such as the serial number and order code of your device.

  • Page 154

    2 is performed. The delay in switching back ensures that rebooted switching devices connected to the C70, which signal their ports as active prior to being completely functional, have time to completely initialize themselves and become active. Once port 2 is active again, port 3 returns to standby mode.

  • Page 155

    There is a second type of specialized device used in PRP networks, called RedBox, with the role of connecting Single Attached Nodes (SANs) to a redundant network. GE Multilin C70 Capacitor Bank Protection and Control System 5-31...

  • Page 156

    When the destination address is 127.0.0.1, the mask and gateway must be also kept on default values. By default, the value of the route gateway address is 127.0.0.1. This means the default route is not configured. To add a route: 5-32 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 157

    Starting with UR 7.10, up to six static network routes can be configured in addition to a default route. The default route con- figuration was also moved from the network settings into the routing section. GE Multilin C70 Capacitor Bank Protection and Control System 5-33...

  • Page 158

    SHOW ROUTES AND ARP TABLES This feature is available on the Web interface, where the main menu contains an additional Communications menu and two submenus: • Routing Table • ARP Table 5-34 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 159

    This allows the EnerVista UR Setup software to be used on the port. The UR operates as a Modbus slave device only. When using Modbus protocol on the RS232 port, the C70 responds regardless of the pro- MODBUS SLAVE ADDRESS grammed.

  • Page 160

    Range: 1 to 255 in steps of 1 DNP UNSOL RESPONSE MESSAGE MAX RETRIES: 10 Range: 0 to 65519 in steps of 1 DNP UNSOL RESPONSE MESSAGE DEST ADDRESS: 1 5-36 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 161

    DEFAULT VARIATION: 2 Range: 1, 2, 3, 4, 5 DNP OBJECT 30 MESSAGE DEFAULT VARIATION: 1 Range: 1, 2, 3, 4, 5, 7 DNP OBJECT 32 MESSAGE DEFAULT VARIATION: 1 GE Multilin C70 Capacitor Bank Protection and Control System 5-37...

  • Page 162

    DNP slave should be assigned a unique address. The C70 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which the C70 can connect. The settings in this sub-menu are shown below.

  • Page 163

    DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the C70 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer- tain ranges in DNP masters.

  • Page 164

    60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored. NOTE Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the C70 is restarted. NOTE 5-40...

  • Page 165

    The C70 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported over two protocol stacks: TCP/IP over Ethernet. The C70 operates as an IEC 61850 server. The Remote Inputs and Out- puts section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.

  • Page 166

    IEC 61850 GSSE application ID name string sent as part of each GSSE message. This GSSE ID string identifies the GSSE message to the receiving device. In C70 releases previous to 5.0x, this name string was repre- sented by the setting.

  • Page 167

    DESTINATION MAC address; the least significant bit of the first byte must be set. In C70 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the C70) and setting the multicast bit.

  • Page 168

    The C70 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.

  • Page 169

    Configure the transmission dataset. Configure the GOOSE service settings. Configure the data. The general steps required for reception configuration are: Configure the reception dataset. Configure the GOOSE service settings. Configure the data. GE Multilin C70 Capacitor Bank Protection and Control System 5-45...

  • Page 170

    MMXU1 HZ DEADBAND change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency. The C70 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. Configure the reception dataset by making the following changes in the ...

  • Page 171

    IEC61850 GOOSE ANALOG INPUT 1 UNITS The GOOSE analog input 1 can now be used as a FlexAnalog value in a FlexElement or in other settings. The C70 must be rebooted (control power removed and re-applied) before these settings take effect.

  • Page 172

    DNA and UserSt bit pairs that are included in GSSE messages. To set up a C70 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and “GGIO3.ST.Ind2.stVal”.

  • Page 173

    CPU resources. When server scanning is disabled, there is no updating of the IEC 61850 logical node status values in the C70. Clients are still able to connect to the server (C70 relay), but most data values are not updated. This set- ting does not affect GOOSE/GSSE operation.

  • Page 174

    (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard. Changes to the logical node prefixes will not take effect until the C70 is restarted. The main menu for the IEC 61850 MMXU deadbands is shown below.

  • Page 175

    The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the C70 virtual inputs.

  • Page 176

    GGIO1 (binary status values). The settings allow the selection of FlexInteger values for each GGIO5 integer value point. It is intended that clients use GGIO5 to access generic integer values from the C70. Additional settings are provided to allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger values to the GGIO5 integer inputs.

  • Page 177

    ITEM 64 attributes supported by the C70. Changes to the dataset will only take effect when the C70 is restarted. It is recommended to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1, GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.

  • Page 178

    XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation can result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1. 5-54 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 179

    Since GSSE/GOOSE messages are multicast Ethernet by specification, they are not usually be forwarded by net- work routers. However, GOOSE messages may be forwarded by routers if the router has been configured for VLAN functionality. NOTE GE Multilin C70 Capacitor Bank Protection and Control System 5-55...

  • Page 180

    Menu”. Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the UR and a computer to an Ethernet network, then enter the IP address of the C70 Ethernet port employed into the “Address”...

  • Page 181

    PROTOCOL connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the C70 maintains two sets of IEC 60870-5-104 data change buffers, no more than two masters should actively communicate with the C70 at one time.

  • Page 182

    MESSAGE 0.0.0.0 The C70 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to which the C70 can connect. A maximum of two simultaneous connections are supported at any given time.

  • Page 183

    Spontaneous transmission occurs as a response to cyclic Class 2 requests. If the C70 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the con- trol field of the response).

  • Page 184

      MEASURANDS Range: see sub-menu below  ASDU 2 MESSAGE  Range: see sub-menu below  ASDU 3 MESSAGE  Range: see sub-menu below  ASDU 4 MESSAGE  5-60 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 185

    Range: 0.000 to 65.535 in steps of 0.001 ASDU 4 ANALOG 9 MESSAGE FACTOR: 1.000 Range: -32768 to 32767 in steps of 1 ASDU 4 ANALOG 9 MESSAGE OFFSET: 0 GE Multilin C70 Capacitor Bank Protection and Control System 5-61...

  • Page 186

    FlexAnalog operands. The measurands sent are voltage, current, power, power fac- tor, and frequency. If any other FlexAnalog is chosen, the C70 sends 0 instead of its value. Note that the power is transmit- ted in KW, not W.

  • Page 187

    ASDU command comes. A list of available mappings is provided on the C70. This includes 64 virtual inputs (see the following table). The ON and OFF for the same ASDU command can be mapped to different virtual inputs.

  • Page 188: Modbus User Map

    A setting of None causes the RTC and the synchrophasor clock to free-run until the clock is 5-64 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 189

    Range: 0 to 60 000 ns in steps of 1 PORT 1 PATH DELAY MESSAGE ADDER: 00000 ns Range: –1 000 to +1 000 ns in steps of 1 PORT 1 PATH DELAY MESSAGE ASYMMETRY: 0000 ns GE Multilin C70 Capacitor Bank Protection and Control System 5-65...

  • Page 190

    This setting selects the value of the priority field in the 802.1Q VLAN tag in request messages issued by the relay’s peer delay mechanism. In compliance with PP the default VLAN priority is 4, but it is recommended that in accordance with PTP it be set to 7. 5-66 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 191

    The C70 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the C70 can obtain clock time over an Ethernet network. The C70 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a ded- icated product using a GPS receiver to provide an accurate time.

  • Page 192

    C70 clock is closely synchronized with the SNTP/NTP server. It takes up to two minutes for the C70 to signal an SNTP self-test error if the server is offline.

  • Page 193: User-programmable Fault Reports

    The user programmable record contains the following information: the user-programmed relay name, detailed firmware revision (7.2x, for example) and relay model (C70), the date and time of trigger, the name of pre-fault trigger (a specific FlexLogic operand), the name of fault trigger (a specific FlexLogic operand), the active setting group at pre-fault trigger, the active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault trigger), and fault values of all programmed analog channels (at the fault trigger).

  • Page 194: Oscillography

    64 samples per cycle; that is, it has no effect on the fundamental calculations of the device. When changes are made to the oscillography settings, all existing oscillography records will be CLEARED. NOTE 5-70 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 195

    IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear. GE Multilin C70 Capacitor Bank Protection and Control System 5-71...

  • Page 196: Data Logger

    The relay automatically partitions the available memory between the channels in use. Exam- ple storage capacities for a system frequency of 60 Hz are shown in the following table. 5-72 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 197

    • DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not selected to “Off” without over-writing old data. GE Multilin C70 Capacitor Bank Protection and Control System 5-73...

  • Page 198: User-programmable Leds

    The test responds to the position and rising edges of the control input defined by the set- LED TEST CONTROL ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed. 5-74 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 199

    2. Once stage 2 has started, the pushbutton can be released. When stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton. GE Multilin C70 Capacitor Bank Protection and Control System 5-75...

  • Page 200

    LED 8 operand LED 20 operand LED 9 operand LED 21 operand LED 10 operand LED 22 operand LED 11 operand LED 23 operand LED 12 operand LED 24 operand 5-76 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 201: User-programmable Self Tests

    ANY SELF-TEST minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7 for information on major and minor self-test alarms. GE Multilin C70 Capacitor Bank Protection and Control System 5-77...

  • Page 202: Control Pushbuttons

    The location of the control pushbuttons are shown in the following figures. Control pushbuttons 842813A1.CDR Figure 5–10: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the C70 is ordered with the 12 user- programmable pushbutton option. STATUS EVENT CAUSE...

  • Page 203

    BREAKERS/BREAKER 1/ BREAKER 1 PUSHBUTTON CONTROL Enabled=1 TIMER FLEXLOGIC OPERAND SYSTEM SETUP/ BREAKERS/BREAKER 2/ CONTROL PUSHBTN 1 ON 100 msec BREAKER 2 PUSHBUTTON CONTROL 842010A2.CDR Enabled=1 Figure 5–12: CONTROL PUSHBUTTON LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-79...

  • Page 204: User-programmable Pushbuttons

    FlexLogic equations, protection elements, and control elements. Typical applications include breaker control, autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of password protection. The user-configurable pushbuttons for the enhanced faceplate are shown below. 5-80 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 205

    The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the push- button. This allows the user-programmable pushbuttons to properly operate during power cycling events and vari- ous system disturbances that may cause transient assertion of the operating signals. NOTE GE Multilin C70 Capacitor Bank Protection and Control System 5-81...

  • Page 206

    PUSHBTN 1 RESET • PUSHBTN 1 LOCAL: This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the front panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset. 5-82 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 207

    “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. GE Multilin C70 Capacitor Bank Protection and Control System 5-83...

  • Page 208

    SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–15: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) 5-84 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 209

    This can be done via EnerVista UR Setup with the Maintenance > Enable Pushbutton command. NOTE GE Multilin C70 Capacitor Bank Protection and Control System 5-85...

  • Page 210: Flex State Parameters

    USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL setting. Any FlexLogic operand (in particular, the user-programmable pushbutton operands), can be used to navigate the programmed displays. 5-86 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 211

    (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this conversion). GE Multilin C70 Capacitor Bank Protection and Control System 5-87...

  • Page 212

    If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items are different. NOTE 5-88 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 213: Direct Inputs And Outputs

    “Yes”), all direct output messages should be received back. If not, the direct input/output ring CH2 RING CONFIGURATION break self-test is triggered. The self-test error is signaled by the FlexLogic operand. DIRECT RING BREAK GE Multilin C70 Capacitor Bank Protection and Control System 5-89...

  • Page 214

    64 kbps Channel 1 64 kbps Channel 2 64 kbps The G.703 modules are fixed at 64 kbps. The setting is not applicable to these modules. DIRECT I/O DATA RATE NOTE 5-90 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 215

    UR IED 4 UR IED 2 UR IED 3 842712A1.CDR Figure 5–18: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME For increased reliability, a dual-ring configuration (shown below) is recommended for this application. GE Multilin C70 Capacitor Bank Protection and Control System 5-91...

  • Page 216

    The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns. 5-92 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 217

    Inputs and Outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This is accomplished using a dual-ring configuration as shown here. GE Multilin C70 Capacitor Bank Protection and Control System 5-93...

  • Page 218

    EVENTS: Disabled The C70 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.

  • Page 219

    MESSAGE EVENTS: Disabled The C70 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unre- turned messages.

  • Page 220: Installation

    "Programmed" state. UNIT NOT PROGRAMMED setting allows the user to uniquely identify a relay. This name will appear on generated reports. RELAY NAME 5-96 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 221: Remote Resources Configuration

    Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the C70 process card and specific Brick. The relay is then configured to measure spe- cific currents, voltages and contact inputs from those Bricks, and to control specific outputs.

  • Page 222: Ac Inputs

    1 pu will operate on 1000 A primary. The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). 5-98 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 223: Power System

    GE Multilin C70 Capacitor Bank Protection and Control System 5-99...

  • Page 224

    “Disabled” only in unusual circumstances; consult the factory for special variable- FREQUENCY TRACKING frequency applications. NOTE The frequency tracking feature functions only when the C70 is in the “Programmed” mode. If the C70 is “Not Pro- grammed”, then metering values are available but can exhibit significant errors. NOTE 5-100...

  • Page 225: Signal Sources

    CT wiring problem. A disturbance detector is provided for each source. The 50DD function responds to the changes in magnitude of the sequence currents. The disturbance detector scheme logic is as follows: GE Multilin C70 Capacitor Bank Protection and Control System 5-101...

  • Page 226

    This configuration could be used on a two-winding transformer, with one winding connected into a breaker-and-a-half sys- tem. The following figure shows the arrangement of sources used to provide the functions required in this application, and the CT/VT inputs that are used to provide the data. 5-102 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 227

    Figure 5–25: EXAMPLE USE OF SOURCES Y LV D HV SRC 1 SRC 2 SRC 3 Phase CT F1+F5 None Ground CT None None Phase VT None None Aux VT None None GE Multilin C70 Capacitor Bank Protection and Control System 5-103...

  • Page 228: Breakers

    Range: 0.000 to 65.535 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled 5-104 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 229

    1. The number of breaker control elements is dependent on the number of CT/VT modules specified with the C70. The follow- ing settings are available for each breaker control element.

  • Page 230

    5.4 SYSTEM SETUP 5 SETTINGS Figure 5–26: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the C70 is in “Programmed” mode and not in the local control mode. NOTE 5-106 C70 Capacitor Bank Protection and Control System...

  • Page 231

    Note that IEC 61850 commands are event-driven and dwell time for these is one protection pass only. If you want to main- tain the close/open command for a certain time, do so either on the contact outputs using the "Seal-in" setting or in Flex- Logic. GE Multilin C70 Capacitor Bank Protection and Control System 5-107...

  • Page 232: Disconnect Switches

    SWITCH 1 MODE: This setting selects “3-Pole” mode, where disconnect switch poles have a single common auxiliary switch, or “1-Pole” mode where each disconnect switch pole has its own auxiliary switch. 5-108 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 233

    This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the C70 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin...

  • Page 234

    5.4 SYSTEM SETUP 5 SETTINGS Figure 5–28: DISCONNECT SWITCH SCHEME LOGIC 5-110 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 235: Flexcurves

    0.88 15.5 0.50 0.90 16.0 0.52 0.91 16.5 0.54 0.92 17.0 0.56 0.93 17.5 0.58 0.94 18.0 0.60 0.95 18.5 0.62 0.96 19.0 0.64 0.97 19.5 0.66 0.98 10.0 20.0 GE Multilin C70 Capacitor Bank Protection and Control System 5-111...

  • Page 236

    The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE 5-112 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 237

    EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the C70 are displayed in the following graphs. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 238

    Figure 5–32: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–33: RECLOSER CURVES GE113, GE120, GE138 AND GE142 5-114 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 239

    Figure 5–34: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–35: RECLOSER CURVES GE131, GE141, GE152, AND GE200 GE Multilin C70 Capacitor Bank Protection and Control System 5-115...

  • Page 240

    GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–37: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 5-116 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 241

    Figure 5–38: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–39: RECLOSER CURVES GE119, GE135, AND GE202 GE Multilin C70 Capacitor Bank Protection and Control System 5-117...

  • Page 242: Introduction To Flexlogic

    Figure 5–40: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the C70 are represented by flags (or FlexLogic operands, which are described later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an ele- ment from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output.

  • Page 243

    The virtual input is presently in the ON state Virtual Output Virt Op 1 On The virtual output is presently in the set state (i.e. evaluation of the equation which produces this virtual output results in a "1") GE Multilin C70 Capacitor Bank Protection and Control System 5-119...

  • Page 244

    5.5 FLEXLOGIC 5 SETTINGS The operands available for this relay are listed alphabetically by types in the following table. Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 1 of 10) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed...

  • Page 245

    5 SETTINGS 5.5 FLEXLOGIC Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 2 of 10) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: BANK OV 1 STG 1A PKP Bank overvoltage element 1 picked up in phase A of stage 1 Bank phase...

  • Page 246

    5.5 FLEXLOGIC 5 SETTINGS Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 3 of 10) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: BREAKER 1 OFF CMD Breaker 1 open command initiated Breaker control BREAKER 1 ON CMD Breaker 1 close command initiated BREAKER 1 ΦA BAD ST...

  • Page 247

    5 SETTINGS 5.5 FLEXLOGIC Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 4 of 10) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: CUR BAL 1 STG1A PKP Phase current unbalance element 1 picked up in phase A of stage 1 Phase current...

  • Page 248

    5.5 FLEXLOGIC 5 SETTINGS Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 5 of 10) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: MONTH JANUARY Current month is January Time of day timer MONTH FEBRUARY Current month is February month MONTH MARCH Current month is March...

  • Page 249

    5 SETTINGS 5.5 FLEXLOGIC Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 6 of 10) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: NTRL VOLT 1 STG1 PKP Neutral voltage unbalance element 1 picked up in stage 1 Neutral voltage NTRL VOLT 1 STG2 PKP...

  • Page 250

    5.5 FLEXLOGIC 5 SETTINGS Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 7 of 10) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: SELECTOR 1 POS Y Selector switch 1 is in Position Y (mutually exclusive operands) Selector switch SELECTOR 1 BIT 0...

  • Page 251

    5 SETTINGS 5.5 FLEXLOGIC Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 8 of 10) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT TRIP BUS 1 PKP Asserted when the trip bus 1 element picks up Trip bus TRIP BUS 1 OP Asserted when the trip bus 1 element operates...

  • Page 252

    5.5 FLEXLOGIC 5 SETTINGS Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 9 of 10) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION INPUTS/OUTPUTS: Virt Ip 1 Flag is set, logic=1 Virtual inputs Virt Ip 2 Flag is set, logic=1 Virt Ip 3 Flag is set, logic=1 ↓...

  • Page 253

    5 SETTINGS 5.5 FLEXLOGIC Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 10 of 10) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION SELF- ANY MAJOR ERROR Any of the major self-test errors generated (major error) DIAGNOSTICS ANY MINOR ERROR Any of the minor self-test errors generated (minor error)

  • Page 254: Flexlogic Rules

    When making changes to FlexLogic entries in the settings, all FlexLogic equations are re-compiled whenever any new FlexLogic entry value is entered, and as a result of the re-compile all latches are reset automatically. 5-130 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 255: Flexlogic Example

    State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–42: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS GE Multilin C70 Capacitor Bank Protection and Control System 5-131...

  • Page 256

    Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." 5-132 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 257

    86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". GE Multilin C70 Capacitor Bank Protection and Control System 5-133...

  • Page 258

    In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) 5-134 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 259: Flexlogic Equation Editor

    TIMER 1 TYPE: This setting is used to select the time measuring unit. • TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". GE Multilin C70 Capacitor Bank Protection and Control System 5-135...

  • Page 260: Flexelements

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. 5-136 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 261

    The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS GE Multilin C70 Capacitor Bank Protection and Control System 5-137...

  • Page 262

    Figure 5–49: FLEXELEMENT DIRECTION, PICKUP, AND HYSTERESIS In conjunction with the setting the element could be programmed to provide two extra charac- FLEXELEMENT 1 INPUT MODE teristics as shown in the figure below. 5-138 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 263

    = maximum nominal primary RMS value of the +IN and –IN inputs BASE SOURCE POWER = maximum value of V × I for the +IN and –IN inputs BASE BASE BASE GE Multilin C70 Capacitor Bank Protection and Control System 5-139...

  • Page 264

    FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. 5-140 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 265: Non-volatile Latches

    LATCH N LATCH N TYPE RESET Reset Dominant Previous Previous State State Dominant Previous Previous State State Figure 5–51: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-141...

  • Page 266

    (see the Control elements section for additional details). If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.25, 7.31, or later to cor- rect this issue. 5-142 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 267: Breaker Failure (ansi 50bf)

    Range: 0.001 to 30.000 pu in steps of 0.001 BF1 N AMP HISET MESSAGE PICKUP: 1.050 pu Range: 0.001 to 30.000 pu in steps of 0.001 BF1 PH AMP LOSET MESSAGE PICKUP: 1.050 pu GE Multilin C70 Capacitor Bank Protection and Control System 5-143...

  • Page 268

    5-144 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 269

    BREAKER FAILURE TIMER No. 2 (±1/8 cycle) INITIATE (1/8 cycle) BREAKER FAILURE CURRENT DETECTOR PICKUP (1/8 cycle) BREAKER FAILURE OUTPUT RELAY PICKUP (1/4 cycle) FAULT cycles OCCURS 827083A6.CDR Figure 5–52: BREAKER FAILURE MAIN PATH SEQUENCE GE Multilin C70 Capacitor Bank Protection and Control System 5-145...

  • Page 270

    In microprocessor relays this time is not significant. In C70 relays, which use a Fourier transform, the calculated current magnitude will ramp-down to zero one power frequency cycle after the current is interrupted, and this lag should be included in the overall margin duration, as it occurs after current interruption.

  • Page 271

    Upon operation of the breaker failure element for a single pole trip command, a three-pole trip command should be given via output operand BKR FAIL 1 TRIP OP GE Multilin C70 Capacitor Bank Protection and Control System 5-147...

  • Page 272

    5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–54: SINGLE-POLE BREAKER FAILURE, INITIATE 5-148 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 273

    5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–55: SINGLE-POLE BREAKER FAILURE, TIMERS GE Multilin C70 Capacitor Bank Protection and Control System 5-149...

  • Page 274

    5.6 GROUPED ELEMENTS 5 SETTINGS Figure 5–56: THREE-POLE BREAKER FAILURE, INITIATE 5-150 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 275

    5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–57: THREE-POLE BREAKER FAILURE, TIMERS GE Multilin C70 Capacitor Bank Protection and Control System 5-151...

  • Page 276: Phase Current

     UNBALANCE 3 b) INVERSE TOC CURVE CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.

  • Page 277

    22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 GE Multilin C70 Capacitor Bank Protection and Control System 5-153...

  • Page 278

    0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 5-154 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 279

    = characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–24: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...

  • Page 280

    = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET RECLOSER CURVES: The C70 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurve section in this chapter for details. 5-156 C70 Capacitor Bank Protection and Control System...

  • Page 281

    (see the figure below); the pickup level is calculated as ‘Mvr’ times the setting. If the voltage restraint PHASE TOC1 PICKUP feature is disabled, the pickup level always remains at the setting value. GE Multilin C70 Capacitor Bank Protection and Control System 5-157...

  • Page 282

    5.6 GROUPED ELEMENTS 5 SETTINGS Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage 818784A4.CDR Figure 5–58: PHASE TIME OVERCURRENT VOLTAGE RESTRAINT CHARACTERISTIC Figure 5–59: PHASE TIME OVERCURRENT 1 SCHEME LOGIC 5-158 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 283

    The input current is the fundamental phasor magnitude. For timing curves, see the publication Instan- taneous Overcurrent Element Response to Saturated Waveforms in UR-Series Relays (GET-8400A). Figure 5–60: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-159...

  • Page 284

    Phasors for Phase A Polarization: × VPol = VBC (1/_ECA) = polarizing voltage IA = operating current ECA = Element Characteristic Angle at 30° 827800A2.CDR Figure 5–61: PHASE A DIRECTIONAL POLARIZATION 5-160 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 285

    When set to "Yes", the directional element blocks the operation of any phase overcurrent element under directional control, when voltage memory expires; when set to "No", the directional element allows tripping of phase overcurrent elements under directional control. GE Multilin C70 Capacitor Bank Protection and Control System 5-161...

  • Page 286

    If current reversal is of a concern, a longer delay – in the order of 20 ms – may be needed. Figure 5–62: PHASE DIRECTIONAL SCHEME LOGIC 5-162 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 287

    Range: 0.00 to 600.00 s in steps of 0.01 CUR UNBALCE 1 STG 2 MESSAGE PKP DELAY: 10.00 s Range: 0.00 to 600.00 s in steps of 0.01 CUR UNBALCE 1 STG 3 MESSAGE PKP DELAY: 1.00 s GE Multilin C70 Capacitor Bank Protection and Control System 5-163...

  • Page 288

    SOURCE CT bank Grounding method not relevant, neutral points must be connected together 8347516A1.CDR Figure 5–63: PHASE CURRENT UNBALANCE BASIC CONNECTIONS The following settings are available for all three elements. 5-164 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 289

    At minimum this function shall be blocked when the two banks are not paralleled. Note that when unblocked, the function becomes operational after five cycles of intentional delay. High-set instantaneous protection on energization can be provided by a separate instantaneous overcurrent function. GE Multilin C70 Capacitor Bank Protection and Control System 5-165...

  • Page 290: Neutral Current

    See page 5–168.   NEUTRAL IOC2 MESSAGE See page 5–168.  ↓  NEUTRAL IOC12 MESSAGE See page 5–168.   NEUTRAL MESSAGE See page 5–169.  DIRECTIONAL OC1 5-166 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 291

    See page 5–173.  UNBALANCE 3 The C70 contains protection elements for neutral time overcurrent (ANSI device 51G), neutral instantaneous overcurrent (ANSI device 50G), and neutral current unbalance (ANSI device 60N). A maximum of six ground time overcurrent and twelve ground instantaneous overcurrent elements are available, dependent on the CT/VT modules ordered with the relay.

  • Page 292

    × Kx I_1 where K 1 16 ⁄ (EQ 5.15) – The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents resulting from 5-168 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 293

    Range: 40 to 90° in steps of 1 NEUTRAL DIR OC1 REV MESSAGE LIMIT ANGLE: 90° Range: 0.006 to 30.000 pu in steps of 0.001 NEUTRAL DIR OC1 REV MESSAGE PICKUP: 0.050 pu GE Multilin C70 Capacitor Bank Protection and Control System 5-169...

  • Page 294

    –V_0 + Z_offset × I_0 I_0 × 1∠ECA = 3 × (|I_0|) if |I | ≤ 0.8 pu Forward Dual, Dual-V, Dual-I –V_0 + Z_offset × I_0 –I_0 × 1∠ECA Reverse –I_0 5-170 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 295

    V_0 calculated from the phase voltages, or the zero-sequence voltage supplied externally as the auxiliary voltage V_X, both from the NEUTRAL DIR OC1 SOURCE GE Multilin C70 Capacitor Bank Protection and Control System 5-171...

  • Page 296

    180°. • NEUTRAL DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit angle for the forward direction. 5-172 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 297

    NTRL CUR UNBALCE 1  UNBALANCE 1 FUNCTION: Disabled Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6 NTRL CUR UNBALCE 1 MESSAGE BANK SOURCE: SRC 1 GE Multilin C70 Capacitor Bank Protection and Control System 5-173...

  • Page 298

    NTRL CUR UNBALCE 1 MESSAGE TARGET: Self-Reset Range: Disabled, Enabled NTRL CUR UNBALCE 1 MESSAGE EVENTS: Disabled Up to three identical neutral current unbalance elements, one per each installed CT/VT module. 5-174 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 299

    Without the phase currents configured under this source, the function would run only if the magnitude of the inherent unbalance factor is set to zero. GE Multilin C70 Capacitor Bank Protection and Control System 5-175...

  • Page 300

    At minimum this function shall be blocked when the two banks are not paralleled. Note that when unblocked, the function becomes operational after five cycles of intentional delay. High-set instantaneous protection on energization can be provided by a separate instantaneous overcurrent function. 5-176 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 301

    5 SETTINGS 5.6 GROUPED ELEMENTS Figure 5–70: NEUTRAL CURRENT UNBALANCE SCHEME LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-177...

  • Page 302: Ground Current

    The ground current input value is the quantity measured by the ground input CT and is the funda- mental phasor or RMS magnitude. Two methods of resetting operation are available: “Timed” and “Instantaneous” (see the 5-178 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 303

    The ground instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental phasor magnitude. GE Multilin C70 Capacitor Bank Protection and Control System 5-179...

  • Page 304: Negative Sequence Current

      NEG SEQ IOC2 MESSAGE See page 5–182.   NEG SEQ DIR OC1 MESSAGE See page 5–183.   NEG SEQ DIR OC2 MESSAGE See page 5–183.  5-180 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 305

    For example, if the element reset characteristic is set to “Instanta- neous” and the element is blocked, the time accumulator is cleared immediately. Figure 5–73: NEGATIVE SEQUENCE TOC1 SCHEME LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-181...

  • Page 306

    The operating quantity depends on the way the test currents are injected into the relay (single-phase injection: ⋅ 0.2917 I ; three-phase injection, opposite rotation: injected injected Figure 5–74: NEGATIVE SEQUENCE IOC1 SCHEME LOGIC 5-182 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 307

    The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence and zero-sequence currents resulting from: • System unbalances under heavy load conditions. • Transformation errors of current transformers (CTs). • Fault inception and switch-off transients. GE Multilin C70 Capacitor Bank Protection and Control System 5-183...

  • Page 308

    CT errors, since the current is low. The operating quantity depends on the way the test currents are injected into the C70. For single phase injection: = ⅓ × (1 – K) × I •...

  • Page 309

    The element characteristic angle in the reverse direction is the angle set for the forward direction shifted by 180°. • NEG SEQ DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit angle for the forward direction. GE Multilin C70 Capacitor Bank Protection and Control System 5-185...

  • Page 310

    NEG SEQ DIR OC1 TYPE selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique. Figure 5–76: NEGATIVE SEQUENCE DIRECTIONAL OC1 SCHEME LOGIC 5-186 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 311: Voltage Elements

     DIFFERENTIAL 2  VOLTAGE MESSAGE See page 5–194.  DIFFERENTIAL 3  BANK MESSAGE See page 5–197.  OVERVOLTAGE  NEUTRAL VOLTAGE MESSAGE See page 5–201.  UNBALANCE 1 GE Multilin C70 Capacitor Bank Protection and Control System 5-187...

  • Page 312

    V = secondary voltage applied to the relay = pickup level pickup % of voltage pickup 842788A1.CDR Figure 5–77: INVERSE TIME UNDERVOLTAGE CURVES At 0% of pickup, the operating time equals the UNDERVOLTAGE DELAY setting. NOTE 5-188 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 313

    The minimum voltage setting selects the operating voltage below which the element is blocked (a setting of “0” will allow a dead source to be considered a fault condition). Figure 5–78: PHASE UNDERVOLTAGE1 SCHEME LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-189...

  • Page 314

    PHASE OV1 PKP 827066A7.CDR Figure 5–79: PHASE OVERVOLTAGE SCHEME LOGIC > × If the source VT is wye-connected, then the phase overvoltage pickup condition is Pickup for V and V NOTE 5-190 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 315

    NEUTRAL OV1 CURVE VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to be wye-connected. Figure 5–80: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-191...

  • Page 316

    The negative-sequence overvoltage element may be used to detect loss of one or two phases of the source, a reversed phase sequence of voltage, or a non-symmetrical system voltage condition. Figure 5–81: NEGATIVE-SEQUENCE OVERVOLTAGE SCHEME LOGIC 5-192 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 317

    AUX OV1 EVENTS: MESSAGE Disabled The C70 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM ...

  • Page 318

    Range: 0.00 to 600.00 s in steps of 0.01 VOLTAGE DIF 1 STG 1 MESSAGE PKP DELAY: 30.00 s Range: 0.00 to 600.00 s in steps of 0.01 VOLTAGE DIF 1 STG 2 MESSAGE PKP DELAY: 10.00 s 5-194 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 319

    The function works with grounded and ungrounded banks. In the latter case, the neutral point voltage must be measured by the relay. For additional information, refer to the Theory of Operation and Application of Settings chapters. The following settings are available for each voltage differential element. GE Multilin C70 Capacitor Bank Protection and Control System 5-195...

  • Page 320

    The VT fuse fail condition from both the bus and tap VT should also be considered. Note that when unblocked, the function becomes operational after five cycles of intentional delay. 5-196 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 321

    Range: 1.00 to 10.00 in steps of 0.01 BANK OV 1 CURVE TIME MESSAGE MULTIPLIER: 1.00 Range: 0.800 to 2.000 pu in steps of 0.001 BANK OV 1 STG 1A MESSAGE PICKUP: 1.050 pu GE Multilin C70 Capacitor Bank Protection and Control System 5-197...

  • Page 322

    5-198 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 323

    Vop_C = VC – VX Vop_C = (VBC – VCA) / 3 Delta Vop_A = (VCA – VAB) / 3 Vop_B = (VAB – VBC) / 3 Vop_C = (VBC – VCA) / 3 GE Multilin C70 Capacitor Bank Protection and Control System 5-199...

  • Page 324

    • BANK OV 1 BLK: This input is used to block the function when required; in particular, when the bank is offline. 5-200 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 325

    Range: 0.0 to 10.0% in steps of 0.1 NTRL VOL UNBAL 1 MESSAGE STG 1 SLOPE: 0.0% Range: 0.001 to 1.000 pu in steps of 0.001 NTRL VOL UNBAL 1 MESSAGE STG 2 PKP: 0.020 pu GE Multilin C70 Capacitor Bank Protection and Control System 5-201...

  • Page 326

    The slope of the operating characteristic is user adjustable, and if desired, it can be effectively removed yielding a straight compensated overvoltage function. For additional information, see the Theory of operation and Application of settings chapters. 5-202 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 327

    The value of resistor R should be chosen so the voltage measured by the auxiliary input of the relay matches bus V0 during system faults (for example, an SLG fault at the bus). This is accomplished by the following condition: GE Multilin C70 Capacitor Bank Protection and Control System 5-203...

  • Page 328

    The function becomes blocked if all four blocking inputs are asserted. The individual blocking inputs inhibit the associated stages of the func- tion. 5-204 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 329

    NTRL VOLT 1 STG4 OP t DPO FLEXLOGIC OPERANDS FLEXLOGIC OPERANDS NTRL VOLT 1 PKP NTRL VOLT 1 OP NTRL VOLT 1 DPO 834741A1.DWG Figure 5–88: NEUTRAL VOLTAGE UNBALANCE LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-205...

  • Page 330

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. 5-206 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 331

    As such, a reset command the front panel interface or via RESET OP communications will reset the trip bus output. GE Multilin C70 Capacitor Bank Protection and Control System 5-207...

  • Page 332: Setting Groups

    MESSAGE Range: up to 16 alphanumeric characters GROUP 2 NAME: MESSAGE ↓ Range: up to 16 alphanumeric characters GROUP 6 NAME: MESSAGE Range: Disabled, Enabled SETTING GROUP MESSAGE EVENTS: Disabled 5-208 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 333

    The assigned operand is used to control the “On” state of a particular settings group. VIRTUAL OUTPUT 1 GE Multilin C70 Capacitor Bank Protection and Control System 5-209...

  • Page 334: Selector Switch

    SELECTOR 1 3BIT ACK: MESSAGE Range: Restore, Synchronize, Sync/Restore SELECTOR 1 POWER-UP MESSAGE MODE: Restore Range: Self-reset, Latched, Disabled SELECTOR 1 TARGETS: MESSAGE Self-reset Range: Disabled, Enabled SELECTOR 1 EVENTS: MESSAGE Disabled 5-210 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 335

    SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con- trol word pre-selects the position using the following encoding convention: POSITION rest GE Multilin C70 Capacitor Bank Protection and Control System 5-211...

  • Page 336

    The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. 5-212 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 337

    POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–92: TIME-OUT MODE GE Multilin C70 Capacitor Bank Protection and Control System 5-213...

  • Page 338

    Make the following changes to selector switch element in the    SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 5-214 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 339

    SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–94: SELECTOR SWITCH LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-215...

  • Page 340: Time Of Day Timers

    The time of day timer function provides the ability to program control actions based on real time. There are five identical time of day timers, each with an independent start and stop time setting. Each timer is on when the C70 real-time clock/cal- endar value is later than its programmed start time, and earlier than its programmed stop time.

  • Page 341: Capacitor Control

    CAP 1 LCL SET MAN: MESSAGE Range: FlexLogic operand CAP 1 TRIP 1: MESSAGE Range: FlexLogic operand CAP 1 TRIP 2: MESSAGE Range: FlexLogic operand CAP 1 TRIP 3: MESSAGE GE Multilin C70 Capacitor Bank Protection and Control System 5-217...

  • Page 342

    CAP 1 BKR CLOSE BLK: MESSAGE Range: FlexLogic operand CAP 1 CLS OVERRIDE: MESSAGE Range: Self-reset, Latched, Disabled CAP 1 TARGETS: MESSAGE Disabled Range: Disabled, Enabled CAP 1 EVENTS: MESSAGE Disabled 5-218 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 343

    CAP 1 BKR OPEN 52b: Selects a FlexLogic operand that cancels the trip seal-in. Expected to be set to the contact input to which a contact is wired that is closed when the capacitor breaker is open. When both 52a and 52b contacts GE Multilin C70 Capacitor Bank Protection and Control System 5-219...

  • Page 344

    CAP 1 CLS OVERRIDE: Selects a FlexLogic operand that overrides all inhibits for the breaker close command and allows the command to be issued from any source as per the logic diagram. CLOSE 5-220 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 345

    Off = 0 CAP 1 AUTO CLOSE OFF = 0 SETTINGS CAP 1 CLOSE SEAL-IN DELAY FLEXLOGIC OPERAND CAP 1 BKR CLOSE 834740A1.DWG Figure 5–98: CAPACITOR BANK CONTROL SCHEME LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-221...

  • Page 346: Automatic Voltage Regulator

    The automatic voltage regulator element (AVR) is intended to switch a static capacitor bank breaker close and open to reg- ulate either system voltage, load voltage, power factor, or reactive power. The following figure illustrates some possible applications. 5-222 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 347

    For the latter preference, set the var open mode to “Minimize No. of Ops” (minimize number of operations) and set the var open level to the negative of the close level. GE Multilin C70 Capacitor Bank Protection and Control System 5-223...

  • Page 348

    AVRs facilitates coordination with those AVRs. • AVR 1 VOLT LEVEL TO CLOSE: In the voltage mode, this setting specifies the voltage level at or below which to issue the close command. 5-224 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 349

    • AVR 1 BLOCK: This setting specifies a dynamic blocking condition. When blocked the element resets its output flags and internal timers. VT fuse fail is a typical application. GE Multilin C70 Capacitor Bank Protection and Control System 5-225...

  • Page 350

    AVR 1 OPEN DPO SETTING see note at right VAR Open Mode Minimize No. of Ops. = 0 Minimize Uptime = 1 834739A2.CDR Figure 5–102: AUTOMATIC VOLTAGE REGULATOR SCHEME LOGIC 5-226 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 351: Digital Elements

    DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”. • DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to “Disabled”, the operation of the pickup LED is blocked. GE Multilin C70 Capacitor Bank Protection and Control System 5-227...

  • Page 352

    In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. Figure 5–104: TRIP CIRCUIT EXAMPLE 1 5-228 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 353

    In this case, it is not required to supervise the monitoring circuit with the breaker position – the setting is BLOCK selected to “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). Figure 5–105: TRIP CIRCUIT EXAMPLE 2 GE Multilin C70 Capacitor Bank Protection and Control System 5-229...

  • Page 354: Digital Counters

    –2,147,483,648 counts, the counter will rollover to +2,147,483,647. • COUNTER 1 BLOCK: Selects the FlexLogic operand for blocking the counting operation. All counter operands are blocked. 5-230 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 355

    COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A2.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–106: DIGITAL COUNTER SCHEME LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-231...

  • Page 356: Monitoring Elements

      VT FUSE FAILURE 5 MESSAGE See page 5–240.   VT FUSE FAILURE 6 MESSAGE See page 5–240.   THERMAL OVERLOAD MESSAGE See page 5–242.  PROTECTION 5-232 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 357

    Voltage difference drop, and Measured flashover current through the breaker. Furthermore, the scheme is applicable for cases where either one or two sets of three-phase voltages are available across the breaker. GE Multilin C70 Capacitor Bank Protection and Control System 5-233...

  • Page 358

    This application does not require detection of breaker status via a 52a contact, as it uses a voltage difference larger than setting. However, monitoring the breaker contact will ensure scheme stability. BRK 1 FLSHOVR DIFF V PKP 5-234 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 359

    Depending on the flashover protection application, the flashover current can vary from levels of the charging current when the line is de-energized (all line breakers open), to well above the maximum line (feeder) load (line/feeder con- nected to load). GE Multilin C70 Capacitor Bank Protection and Control System 5-235...

  • Page 360

    A six-cycle time delay applies after the selected FlexLogic operand resets. • BRK FLSHOVR PKP DELAY: This setting specifies the time delay to operate after a pickup condition is detected. 5-236 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 361

    5 SETTINGS 5.7 CONTROL ELEMENTS Figure 5–107: BREAKER FLASHOVER SCHEME LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-237...

  • Page 362

    MESSAGE EVENTS: Disabled One breaker restrike element is provided for each CT bank in the C70. According to IEEE standard C37.100: IEEE Standard Definitions for Power Switchgear, restrike is defined as “a resumption of current between the contacts of a switching device during an opening operation after an interval of zero current of ¼...

  • Page 363

    BREAKER RESTRIKE 1 RESET DELAY: This setting specifies the reset delay for this element. When set to “0 ms”, then FlexLogic operand will be picked up for only 1/8th of the power cycle. GE Multilin C70 Capacitor Bank Protection and Control System 5-239...

  • Page 364

    B failures is when positive sequence current is present and there is an insignificant amount of positive sequence voltage. Also rapid decrease in the phase voltages magnitude from a healthy 5-240 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 365

    Figure 5–111: VT FUSE FAIL SCHEME LOGIC Base voltage for this element is PHASE VT SECONDARY setting in the case of WYE VTs and (PHASE VT SECONDARY)/ in case of DELTA VTs. GE Multilin C70 Capacitor Bank Protection and Control System 5-241...

  • Page 366

    = measured load RMS current before overload occurs • k= IEC 255-8 k-factor applied to I , defining maximum permissible current above nominal current • = protected element base (nominal) current 5-242 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 367

    When current is greater than the pickup level, I > k × I , element starts increasing the thermal energy: t Δ -------------- - (EQ 5.24) – op In GE Multilin C70 Capacitor Bank Protection and Control System 5-243...

  • Page 368

    60 minutes 20 minutes Underground cable 20 to 60 minutes 60 minutes The logic for the thermal overload protection element is shown below. Figure 5–113: THERMAL OVERLOAD PROTECTION SCHEME LOGIC 5-244 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 369: Contact Inputs

    The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the C70 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...

  • Page 370

    "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. 5-246 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 371: Virtual Inputs

    FlexLogic equation, it will likely have to be lengthened NOTE in time. A FlexLogic timer with a delayed reset can perform this function. Figure 5–115: VIRTUAL INPUTS SCHEME LOGIC GE Multilin C70 Capacitor Bank Protection and Control System 5-247...

  • Page 372: Contact Outputs

    INPUTS/OUTPUTS CONTACT OUTPUTS CONTACT OUTPUT H1a Range: Up to 12 alphanumeric characters  CONTACT OUTPUT H1a OUTPUT H1a ID  L-Cont Op 1 Range: FlexLogic operand OUTPUT H1a OPERATE: MESSAGE 5-248 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 373

    USER-PROGRAMMABLE PUSHBUT-  menus: TONS USER PUSHBUTTON 1 USER PUSHBUTTON 2 “Self-reset” “Self-reset” PUSHBUTTON 1 FUNCTION: PUSHBUTTON 2 FUNCTION: “0.00 s” “0.00 s” PUSHBTN 1 DROP-OUT TIME: PUSHBTN 2 DROP-OUT TIME: GE Multilin C70 Capacitor Bank Protection and Control System 5-249...

  • Page 374

    Write the following FlexLogic equation (EnerVista UR Setup example shown): Program the Latching Outputs by making the following changes in the   SETTINGS INPUTS/OUTPUTS CONTACT OUT-  menu (assuming an H4L module): PUTS CONTACT OUTPUT H1a 5-250 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 375: Virtual Outputs

    32 “DNA” bit pairs that represent the state of two pre-defined events and 30 user-defined events. All remaining bit pairs are “UserSt” bit pairs, which are status bits representing user-definable events. The C70 implementation provides 32 of the 96 available UserSt bit pairs.

  • Page 376

    5 SETTINGS b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES In a C70 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message is programmed in the ...

  • Page 377: Remote Inputs

    This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre- sponding settings on the sending device. setting provides for the choice of the C70 fixed (DNA/UserSt) dataset (that is, containing REMOTE DEVICE 1 DATASET DNA and UserSt bit pairs), or one of the configurable datasets.

  • Page 378: Remote Double-point Status Inputs

    REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUTPUTS DNA- 1(32) BIT PAIR Range: FlexLogic operand  REMOTE OUTPUTS DNA- 1 OPERAND:  DNA- 1 BIT PAIR Range: Disabled, Enabled DNA- 1 EVENTS: MESSAGE Disabled 5-254 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 379: Resetting

    Each of these three operands generates an event in the event record when AND) activated. The setting shown above selects the operand that activates the operand. RESET OP (OPERAND) GE Multilin C70 Capacitor Bank Protection and Control System 5-255...

  • Page 380

    APPLICATION EXAMPLES The examples introduced in the earlier Direct Inputs and Outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs. 5-256 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 381

    5 SETTINGS 5.8 INPUTS AND OUTPUTS Example 1: Extending input/output capabilities of a C70 relay Consider an application that requires additional quantities of contact inputs or output contacts or lines of programmable logic that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements.

  • Page 382

    DIRECT INPUT 6 BIT NUMBER: UR IED 2: "1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "3" DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: 5-258 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 383: Iec 61850 Goose Analogs

    The following text must be used in the UNITS setting, to represent these types of analogs: A, V, W, var, VA, Hz, deg, and no text (blank setting) for power factor. GE Multilin C70 Capacitor Bank Protection and Control System 5-259...

  • Page 384: Iec 61850 Goose Integers

    GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna- log values in other C70 features, such as FlexElements. The base factor is applied to the GOOSE analog input Flex- Analog quantity to normalize it to a per-unit quantity. The base units are described in the following table.

  • Page 385: Dcma Inputs

    –20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT F1 MIN VALUE DCMA INPUT F1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE GE Multilin C70 Capacitor Bank Protection and Control System 5-261...

  • Page 386: Rtd Inputs

    1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. 5-262 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 387

    233.97 16.00 172.46 291.96 243.30 16.39 175.84 303.46 252.88 16.78 179.51 315.31 262.76 17.17 183.17 327.54 272.94 17.56 186.82 340.14 283.45 17.95 190.45 353.14 294.28 18.34 194.08 366.53 305.44 18.73 GE Multilin C70 Capacitor Bank Protection and Control System 5-263...

  • Page 388: Dcma Outputs

    MAX VAL MIN VAL MAX VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure. DRIVING SIGNAL MIN VAL MAX VAL 842739A1.CDR Figure 5–123: DCMA OUTPUT CHARACTERISTIC 5-264 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 389

    The CT ratio is 5000:5 and the maximum load current is 4200 A. The current should be monitored from 0 A upwards, allow- ing for 50% overload. The phase current with the 50% overload margin is: GE Multilin C70 Capacitor Bank Protection and Control System 5-265...

  • Page 390

    – • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 x 230.94 kV + 1.27 kV = 2.42 kV. 5-266 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 391: Test Mode

    TEST MODE FORCING: MESSAGE The C70 provides a test facility to verify the functionality of contact inputs and outputs, some communication functions and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face- plate by a Test Mode LED indicator.

  • Page 392: Force Contact Inputs

    Following a restart, power up, settings TEST MODE FUNCTION upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a C70 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states.

  • Page 393: Force Contact Outputs

    1 to initiate the Test mode, make the following changes in the menu:   SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin C70 Capacitor Bank Protection and Control System 5-269...

  • Page 394

    5.10 TESTING 5 SETTINGS 5-270 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 395: Actual Values Menu

     GOOSE UINTEGERS  COMM STATUS See page 6-9.  REMAINING CONNECT  PRP See page 6–10.   ACTUAL VALUES  SOURCE SRC 1 See page 6-14.  METERING  GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 396

    See page 6-22.   DATA LOGGER See page 6-23.   ACTUAL VALUES  MODEL INFORMATION See page 6-24.  PRODUCT INFO   FIRMWARE REVISIONS See page 6-24.  C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 397

    The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 398

    For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 399: Remote Devices

    (the count units label will also appear). Also included, is the date and time stamp for the frozen count. The value refers to the microsecond portion of the time stamp. COUNTER 1 MICROS GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 400: Selector Switches

    STATUS ETHERNET Range: Fail, OK  ETHERNET ETHERNET PRI LINK  STATUS: Fail Range: Fail, OK ETHERNET SEC LINK MESSAGE STATUS: Fail Range: Fail, OK ETHERNET TRD LINK MESSAGE STATUS: Fail C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 401: Real Time Clock Synchronizing

    PTP-— IRIG-B DELTA being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG-B time. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 402: Direct Inputs

    Range: Offline, Online DIRECT DEVICE 2 MESSAGE STATUS: Offline ↓ Range: Offline, Online DIRECT DEVICE 16 MESSAGE STATUS: Offline These actual values represent the state of direct devices 1 through 16. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 403

    UINT INPUT 16 MESSAGE The C70 Capacitor Bank Protection and Control System is provided with optional IEC 61850 communica- tions capability. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.

  • Page 404: Parallel Redundancy Protocol (prp)

    Mismatches Port B: MESSAGE The C70 Capacitor Bank Protection and Control System is provided with optional PRP capability. This fea- ture is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.

  • Page 405: Metering Conventions

    WATTS = Negative VARS = Positive PF = Lead PF = Lag PF = Lead Current UR RELAY 827239AC.CDR S=VI Generator Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS GE Multilin C70 Capacitor Bank Protection and Control System 6-11...

  • Page 406

    • ACB phase rotation: -- - V -- - V -- - V -- - V -- - V -- - V The above equations apply to currents as well. 6-12 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 407

    The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a relative matter. It is important to remember that the C70 displays are always referenced as specified under SETTINGS ...

  • Page 408: Sources

    MESSAGE 0.000 SRC 1 PHASOR Ia: MESSAGE 0.000 0.0° SRC 1 PHASOR Ib: MESSAGE 0.000 0.0° SRC 1 PHASOR Ic: MESSAGE 0.000 0.0° SRC 1 PHASOR In: MESSAGE 0.000 0.0° 6-14 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 409

    RMS Vab: MESSAGE 0.00 SRC 1 RMS Vbc: MESSAGE 0.00 SRC 1 RMS Vca: MESSAGE 0.00 SRC 1 PHASOR Vab: MESSAGE 0.000 0.0° SRC 1 PHASOR Vbc: MESSAGE 0.000 0.0° GE Multilin C70 Capacitor Bank Protection and Control System 6-15...

  • Page 410

    φb: 0.000 SRC 1 REACTIVE PWR MESSAGE φc: 0.000 SRC 1 APPARENT PWR MESSAGE 3φ: 0.000 SRC 1 APPARENT PWR MESSAGE φa: 0.000 SRC 1 APPARENT PWR MESSAGE φb: 0.000 6-16 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 411

    S = V x Î x Î x Î (EQ 6.1) When VTs are configured in delta, the C70 does not calculate power in each phase and three-phase power is measured as S = V x Î x Î (EQ 6.2)

  • Page 412

    The harmonics are a percentage of the fundamental signal obtained as a ratio of harmonic amplitude to fundamental ampli- tude multiplied by 100%. The total harmonic distortion (THD) is the ratio of the total harmonic content to the fundamental: … (EQ 6.4) 6-18 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 413

    NEUTRAL VOLTAGE UNBALANCE     PATH: ACTUAL VALUES METERING CAPACITOR BANK NEUTRAL VOLTAGE... NEUTRAL VOLTAGE UNBALANCE 1(3)  NEUTRAL VOLTAGE NEUTRAL-POINT Vx:  UNBALANCE 1 0.0000 pu / 0.0° GE Multilin C70 Capacitor Bank Protection and Control System 6-19...

  • Page 414: Tracking Frequency

    DCMA INPUT MAX under the +IN and –IN inputs. FREQUENCY = 1 Hz BASE ϕ PHASE ANGLE = 360 degrees (see the UR angle referencing convention) BASE 6-20 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 415: Iec 61580 Goose Analog Values

    MESSAGE 0.000 The C70 Capacitor Bank Protection and Control System is provided with optional IEC 61850 communica- tions capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details.

  • Page 416

    This menu allows the user to view the number of triggers involved and number of oscillography traces available. The value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog- CYCLES PER RECORD raphy section of chapter 5 for additional details. 6-22 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 417

    It counts up at the defined sampling rate. If the data logger channels are defined, then both values are static. Refer to the  menu for clearing data logger records. COMMANDS CLEAR RECORDS GE Multilin C70 Capacitor Bank Protection and Control System 6-23...

  • Page 418: Model Information

    Date and time when the boot program was built. 2012/09/15 16:41:32 The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been installed. 6-24 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 419: Capacitor Bank Automatic Settings

    If applied from this command level, a given value is placed into the setting file and applied instanta- neously in all setting groups of the relay with the same source as the active group during the auto-setting procedure. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 420

    “Auto” to “Disabled” and 87V becomes operational. In essence, when in the “Auto” mode, the user confirmation is processed immediately after the balancing values become available. The C70 does not display the applied coefficients in “Auto” mode; rather, they are be viewed under in the menu.

  • Page 421

    After the process if finished, it is recommended to disable the auto-setting feature. If not manually disabled, the feature automatically disables itself when user-initiated front panel interface activity ceases and the C70 display is dimmed. Certain security conditions are checked during the auto-setting process, such as the frequency deviation from the nominal frequency and the magnitude of the positive-sequence current above 0.1 pu.

  • Page 422

    “Auto” to “Disabled” and the 60P element becomes operational. When in the “Auto” mode, the automatic confirmation command is executed immediately after the balancing values are available. The C70 does not display the applied coefficients in “Auto” mode; rather, they can be viewed in the menu.

  • Page 423

    “Auto” to “Disabled”, and the 60N element becomes operational. In essence, the when in the “Auto” mode, the confirmation command is automatically executed immediately after the balancing values become available. The C70 does not display the applied coefficients in the “Auto” mode; instead, they may be viewed in the menu.

  • Page 424

    When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time is over-written. The timescale of the entered time is local time, including daylight savings time where and when applicable. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 425: Relay Maintenance

    Various self-checking diagnostics are performed in the background while the C70 is running, and diagnostic information is stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the C70 is shipped from the factory, the user may want to clear the diagnostic information for themselves under certain circumstances.

  • Page 426

     MESSAGE Each C70 element with a TARGET setting has a target message that when activated by its element is displayed in sequence with any other currently active target messages in the menu. In the example shown, the Phase TOC4 TARGETS and Digital Element 48 target settings are active and so have their targets displayed.

  • Page 427: Relay Self-tests

    Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the C70 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod- ule (for example, F8L).

  • Page 428

    Check Settings • Latched target message: No. • Description of problem: The   setting indicates the C70 is not pro- PRODUCT SETUP INSTALLATION RELAY SETTINGS grammed. • How often the test is performed: On power up and whenever the ...

  • Page 429

    • What to do: Verify that all the items in the GOOSE data set are supported by the C70. The EnerVista UR Setup soft- ware will list the valid items. An IEC61850 client will also show which nodes are available for the C70.

  • Page 430

    How often the test is performed: Upon initiation of a contact output state change. • What to do: Verify the state of the output contact and contact the factory if the problem persists. MAINTENANCE ALERT: GGIO Ind xxx oscill 7-12 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 431

    Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the C70 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...

  • Page 432

    CPU type to know the cause of the problem. e) SFP X MODULE FAIL MESSAGES Description: A faulty SFP or unplugging the SFP would generate this self test. 7-14 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 433

    This self-test is initiated by low received signal levels at either the Brick or Process Card end, and by the sustained failure to receive poll responses from the proper Brick. GE Multilin C70 Capacitor Bank Protection and Control System 7-15...

  • Page 434

    Brick output failing to respond to an output command can only be detected while the command is active, and so in this case the target is latched. A latched target can be unlatched by pressing the faceplate reset key if the command has ended, however the output may still be non-functional. 7-16 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 435: General Operation

    However, this approach is seldom economic due to the large number of voltage transducers required. Thus, the C70 supports various other methods, the suitability of each dependant on the capacitor bank configuration, and on the VTs and CTs available.

  • Page 436

    However, as shown immediately above, string voltages can be determined for an ungrounded balanced bank using only phase-to-phase bus voltages. In the case of a grounded bank, we can calculate that the A-string voltage is: C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 437: Voltage Differential (ansi 87v)

    8.8 is implemented using primary voltage phasors. The protection operates when the operate signal is greater than the set pickup level for the set pickup delay. Identical relations apply to phases B and C. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 438

    Substituting equation 8.13, we have: ---------- - V × ------ - × ---------- - or dV (EQ 8.15) OP 1A OP 1A This can be written as: × Δ (EQ 8.16) OP 1A C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 439

    V can be taken as 1 when the system is normal (not faulted). Note however that under external fault conditions sensitivity may be much different from the non-fault sensitivity. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 440: Compensated Bank Neutral Voltage Unbalance (ansi 59nu)

    Commands chapter. The C70 sets the operate sig- nal to zero in equation 8.7 or 8.8 and solves for the match factor k using the average of several successive voltage mea- surements.

  • Page 441

    The unbalance ratio k-values that reflect the initial or inherent bank unbalance are chosen as: ------ - , k ------- (EQ 8.31) Therefore, as seen from the previous two equations, the initial operating signal will be zero. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 442

    ------------------------------------------------------------------------------------- ≅ ≅ ≅ ≅ For our purposes, , so . This results in: – ---------- - V ≅ -- - ------------------- - (EQ 8.38) -- - × ------- × – C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 443

    8.25 to zero and solve for the unbalance ratio k- values using the average of several successive measurements of the voltages. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 444: Phase Current Unbalance (ansi 60p)

    Sensitivity is the key performance parameter. The applied comparator uses a simple integration method in addition to the standard hysteresis approach, to deal with chattering of the operating signal at the boundary of operation. 8-10 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 445

    CT primary current rating. This places the string currents on the base same per-unit base used by the C70. Voltages are expressed in primary volts, capacitances in Farads, and frequency in radians per second. The differential current is the vector difference between the two currents: –...

  • Page 446: Neutral Current Unbalance (ansi 60n)

    However, with the two banks slightly mis-matched due to manu- facturing tolerances, a circulating zero-sequence current may be present. Compensation for this inherent unbalance cur- rent is available to increase the sensitivity of the function. 8-12 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 447

    BALANCED CASE The currents in the neutral current unbalance protection are driven by the individual admittances in each string: GE Multilin C70 Capacitor Bank Protection and Control System 8-13...

  • Page 448

    Also, convert from phase coordinates into sequence components as follows, and equation 8.60 becomes: a ˆ a ˆ I a ˆ I a ˆ (EQ 8.62) a ˆ a ˆ k a ˆ k a ˆ Substituting this into equation 8.54, we get: 8-14 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 449

    I converted to the differential source base. For example, I , where I rated rated base base is again the differential CT primary current rating, or with system normal: GE Multilin C70 Capacitor Bank Protection and Control System 8-15...

  • Page 450

    8.58 through 8.65. This results in the following changes. Equation 8.64 becomes: a ˆ a ˆ k (EQ 8.69) a ˆ a ˆ -------------------------- - -------------------------- - -------------------------- - Equation 8.65 becomes: 8-16 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 451

    In this situation, the base for ΔC(pu) is the capacitance of the string which has the element failure, so the larger bank will have a lower sensitivity than the smaller bank. GE Multilin C70 Capacitor Bank Protection and Control System 8-17...

  • Page 452

    8.1 OVERVIEW 8 THEORY OF OPERATION 8-18 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 453

    The capacitor units are built larger because the entire unit is not expected to fail. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 454: Fuseless Capacitors

    This design does not require as many capacitor units in parallel as an externally fused bank. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 455: Grounded Wye-connected Banks

    As long as no fuses have opened and no elements have shorted, the ratio of these two voltages will remain constant. The ratio changes with any capacitor failure in the phase, providing sensitive protection. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 456: Summary

    The following figure summarizes the grounded wye, ungrounded wye, delta, H-bridge, and tapped connection types for capacitor banks. Grounded wye Ungrounded wye Delta H-bridge Tapped 834756A1.CDR Figure 9–4: CAPACITOR BANK CONNECTIONS C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 457

    Capacitor unbalance protection is provided in many different ways, depending on the capacitor bank arrangement. The variety of unbalance protection schemes that may be applied with C70 for internally fused, externally fused, fuseless, or unfused shunt capacitor banks is indicated in Theory of operation chapter and is illustrated on the figures below.

  • Page 458

    The following figure illustrates a single capacitor bank, ungrounded, with a tap. In this case, two CT/VT modules are required. C70 CAPACITOR BANK RELAY 59NU 834758A1.CDR Figure 9–6: SINGLE BANK, UNGROUNDED, WITH A TAP C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 459

    The following figure illustrates parallel capacitor banks, ungrounded, no tap available, and with current unbalance protec- tion. In this case, two CT/VT modules are required. C70 CAPACITOR BANK RELAY 59NU 834760A1.CDR Figure 9–8: PARALLEL BANKS, UNGROUNDED, NO TAP AVAILABLE, CURRENT UNBALANCE PROTECTION GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 460

    CTs for each bank. In this case, two CT/VT modules are required. C70 CAPACITOR BANK RELAY 834762A1.CDR Figure 9–10: PARALLEL BANKS, GROUNDED, NO TAP, WITH CURRENT BALANCE PROTECTION AND HIGH-SIDE CTS C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 461

    (ground fault), a delay slightly longer than the upstream protection fault clearing time is required to avoid tripping due to a system fault. Longer delays increase the probability of catastrophic bank failure. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 462: Overvoltage

    To avoid nuisance tripping during transient overvoltage conditions, in some cases, tripping is delayed by a timer. The C70 relay provides inverse time overvoltage characteristics required to decrease tripping time for large overvoltages.

  • Page 463: Overcurrent

    Because this tripping is also not due to a fault within the capacitor bank (like system overvoltage tripping), the bank is not locked out. GE Multilin C70 Capacitor Bank Protection and Control System 9-11...

  • Page 464

    Figure 9–12: SAMPLE CAPACITOR BANK CONFIGURATION Based on the bank configuration, CT connections, and VTs connections, a C70 model is chosen with three CT/VT modules: two type 8L modules (in slots F and U) and one type 8V module (in slot M) to provide following protection functionality.

  • Page 465: Source Assignment

    The following sources must be assigned for the protection functions indicated. • Source 1 (bus) is assigned with CT and VT banks connected to the bus, providing a signal source for overcurrent, phase current unbalance, overvoltage, and undervoltage functions. GE Multilin C70 Capacitor Bank Protection and Control System 9-13...

  • Page 466: Bank Unbalance Calculations

    The maximum rated voltage across the healthy top section: × 81515.37 V 1890.34Ω × -------------------------- --------------------------------------------------------------- - 81340.40 V (EQ 9.12) 1894.92Ω The maximum rated voltage across the healthy bottom section: 9-14 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 467

    – – unbal 1845.33Ω 50 × 1890.34Ω × × × The following table summarizes the calculated values for the number of failed capacitors used to set the protection ele- ments. GE Multilin C70 Capacitor Bank Protection and Control System 9-15...

  • Page 468: Bank Voltage Differential Settings

    An 87V-2 differential element measuring the differential voltage between the upper capacitor string and bottom capaci- tor can for string 1. • An 87V-3 differential element measuring the differential voltage between the upper capacitor string and bottom capaci- tor can for string 2. 9-16 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 469

    VTs. These VTs must be blocked if one or both of them has a VT fuse failure condition. There- fore, as shown in the following figure, a blocking input for each element is created with FlexLogic™. GE Multilin C70 Capacitor Bank Protection and Control System 9-17...

  • Page 470: Bank Phase Current Unbalance Settings

    The pickup setting for the stage 1 phase current unbalance alarm element is programmed for one element failure. 60P alarm 0.9I 0.9 0.0209 pu × 0.019 pu (EQ 9.25) unbal f1_max 9-18 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 471: Bank Phase Overvoltage Settings

    × 59B pickup (stage 1) 1.25 1.125 pu × 59B pickup (stage 2) 0.9 1.5 1.35 pu (EQ 9.27) × 59B pickup (stage 3) 1.80 pu GE Multilin C70 Capacitor Bank Protection and Control System 9-19...

  • Page 472: Bank Phase Undervoltage Settings

    0.7 pu with a time delay of 1 second, based on maximum fault clearing time. The bank undervoltage element is blocked during VT fuse fail conditions. The following setting values are programmed in the EnerVista UR Setup software. 9-20 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 473: Bank Overcurrent Protection

    10% of the nominal bank phase current with a delay of 250 to 400 ms typically pro- vides adequate coordination for faults external to the bank and protection for internal rack faults. GE Multilin C70 Capacitor Bank Protection and Control System 9-21...

  • Page 474

    9.4 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9-22 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 475: Replace A Module

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the C70. 842812A1.CDR Figure 10–1: UR MODULE WITHDRAWAL AND INSERTION (ENHANCED FACEPLATE)

  • Page 476

    When the clips have locked into position, the module will be fully inserted. CPU connections must be individually disconnected from the module before the module can be removed from the chassis. NOTE NOTE 10-2 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 477: Replace Battery

    10. Reinstall the battery clip and the metal cover, and reinsert the power supply module into the unit. 11. Power on the unit. 12. Dispose of the old battery as outlined in the next section. GE Multilin C70 Capacitor Bank Protection and Control System 10-3...

  • Page 478

    10. Reinstall the battery clip and the metal cover, and reinsert the power supply module into the unit. 11. Power on the unit. 12. Dispose of the old battery as outlined in the next section. 10-4 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 479: Dispose Of Battery

    La batterie est marqué de ce symbole, qui comprennent les indications cadmium (Cd), plomb (Pb), ou mercure (Hg). Pour le recyclage, retourner la batterie à votre fournisseur ou à un point de collecte. Pour plus d'informations, voir: www.recyclethis.info. GE Multilin C70 Capacitor Bank Protection and Control System 10-5...

  • Page 480

    Baterija je označena s tem simbolom, ki lahko vključuje napise, ki označujejo kadmij (Cd), svinec (Pb) ali živo srebro (Hg). Za ustrezno recikliranje baterijo vrnite dobavitelju ali jo odstranite na določenem zbirališču. Za več informacij obiščite spletno stran: www.recyclethis.info. 10-6 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 481

    Latin America +55 11 3614 1700 Europe, Middle East, Africa +(34) 94 485 88 00 Asia +86-21-2401-3208 India +91 80 41314617 From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574 GE Multilin C70 Capacitor Bank Protection and Control System 10-7...

  • Page 482: Uninstall And Clear Files And Data

    You cannot erase directly the flash memory, but all records and settings in that memory can be deleted. Do this using the   command. SETTINGS PRODUCT SETUP CLEAR RELAY RECORDS 10-8 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 483: Repairs

    Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty. • Fax a copy of the shipping information to the GE Grid Solutions service department in Canada at +1 905 927 5098. Use the detailed return procedure outlined at https://www.gegridsolutions.com/multilin/support/ret_proc.htm...

  • Page 484: Storage

    Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range outlined in the Specifications. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. 10-10 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 485: Disposal

    European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove the modules as outlined earlier, dismantle the unit, and recycle the metal when possible. GE Multilin C70 Capacitor Bank Protection and Control System 10-11...

  • Page 486

    10.6 DISPOSAL 10 MAINTENANCE 10-12 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 487: A.1.1 Flexanalog Items

    Degrees Source 1 differential ground current angle 6208 SRC 2 Ia RMS Amps Source 2 phase A current RMS 6210 SRC 2 Ib RMS Amps Source 2 phase B current RMS GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 488

    Amps Source 4 phase A current RMS 6338 SRC 4 Ib RMS Amps Source 4 phase B current RMS 6340 SRC 4 Ic RMS Amps Source 4 phase C current RMS C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 489

    SRC 6 Ib RMS Amps Source 6 phase B current RMS 6468 SRC 6 Ic RMS Amps Source 6 phase C current RMS 6470 SRC 6 In RMS Amps Source 6 neutral current RMS GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 490

    SRC 1 V_2 Mag Volts Source 1 negative-sequence voltage magnitude 6699 SRC 1 V_2 Angle Degrees Source 1 negative-sequence voltage angle 6720 SRC 2 Vag RMS Volts Source 2 phase AG voltage RMS C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 491

    SRC 3 Vx RMS Volts Source 3 auxiliary voltage RMS 6816 SRC 3 Vx Mag Volts Source 3 auxiliary voltage magnitude 6818 SRC 3 Vx Angle Degrees Source 3 auxiliary voltage angle GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 492

    Volts Source 5 phase CA voltage RMS 6933 SRC 5 Vab Mag Volts Source 5 phase AB voltage magnitude 6935 SRC 5 Vab Angle Degrees Source 5 phase AB voltage angle C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 493

    SRC 1 Q Vars Source 1 three-phase reactive power 7178 SRC 1 Qa Vars Source 1 phase A reactive power 7180 SRC 1 Qb Vars Source 1 phase B reactive power GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 494

    SRC 4 Pc Watts Source 4 phase C real power 7272 SRC 4 Q Vars Source 4 three-phase reactive power 7274 SRC 4 Qa Vars Source 4 phase A reactive power C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 495

    Source 1 frequency 7554 SRC 2 Frequency Source 2 frequency 7556 SRC 3 Frequency Source 3 frequency 7558 SRC 4 Frequency Source 4 frequency 7560 SRC 5 Frequency Source 5 frequency GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 496

    Source 1 phase B voltage nineteenth harmonic 8108 SRC 1 Vb Harm[20] Source 1 phase B voltage twentieth harmonic 8109 SRC 1 Vb Harm[21] Source 1 phase B voltage twenty-first harmonic A-10 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 497

    Source 2 phase A voltage sixteenth harmonic 8155 SRC 2 Va Harm[17] Source 2 phase A voltage seventeenth harmonic 8156 SRC 2 Va Harm[18] Source 2 phase A voltage eighteenth harmonic GE Multilin C70 Capacitor Bank Protection and Control System A-11...

  • Page 498

    Source 2 phase C voltage thirteenth harmonic 8202 SRC 2 Vc Harm[14] Source 2 phase C voltage fourteenth harmonic 8203 SRC 2 Vc Harm[15] Source 2 phase C voltage fifteenth harmonic A-12 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 499

    Source 3 phase B voltage tenth harmonic 8249 SRC 3 Vb Harm[11] Source 3 phase B voltage eleventh harmonic 8250 SRC 3 Vb Harm[12] Source 3 phase B voltage twelfth harmonic GE Multilin C70 Capacitor Bank Protection and Control System A-13...

  • Page 500

    Source 4 phase A voltage seventh harmonic 8296 SRC 4 Va Harm[8] Source 4 phase A voltage eighth harmonic 8297 SRC 4 Va Harm[9] Source 4 phase A voltage ninth harmonic A-14 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 501

    Source 4 phase C voltage fourth harmonic 8343 SRC 4 Vc Harm[5] Source 4 phase C voltage fifth harmonic 8344 SRC 4 Vc Harm[6] Source 4 phase C voltage sixth harmonic GE Multilin C70 Capacitor Bank Protection and Control System A-15...

  • Page 502

    Source 5 phase B voltage total harmonic distortion (THD) 8390 SRC 5 Vb Harm[2] Source 5 phase B voltage second harmonic 8391 SRC 5 Vb Harm[3] Source 5 phase B voltage third harmonic A-16 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 503

    Source 5 phase C voltage twenty-third harmonic 8437 SRC 5 Vc Harm[24] Source 5 phase C voltage twenty-fourth harmonic 8438 SRC 5 Vc Harm[25] Source 5 phase C voltage twenty-fifth harmonic GE Multilin C70 Capacitor Bank Protection and Control System A-17...

  • Page 504

    Source 6 phase B voltage twentieth harmonic 8484 SRC 6 Vb Harm[21] Source 6 phase B voltage twenty-first harmonic 8485 SRC 6 Vb Harm[22] Source 6 phase B voltage twenty-second harmonic A-18 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 505

    Source 1 phase A current seventeenth harmonic 10257 SRC 1 Ia Harm[18] Source 1 phase A current eighteenth harmonic 10258 SRC 1 Ia Harm[19] Source 1 phase A current nineteenth harmonic GE Multilin C70 Capacitor Bank Protection and Control System A-19...

  • Page 506

    Source 1 phase C current fourteenth harmonic 10320 SRC 1 Ic Harm[15] Source 1 phase C current fifteenth harmonic 10321 SRC 1 Ic Harm[16] Source 1 phase C current sixteenth harmonic A-20 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 507

    Source 2 phase B current eleventh harmonic 10383 SRC 2 Ib Harm[12] Source 2 phase B current twelfth harmonic 10384 SRC 2 Ib Harm[13] Source 2 phase B current thirteenth harmonic GE Multilin C70 Capacitor Bank Protection and Control System A-21...

  • Page 508

    Source 3 phase A current eighth harmonic 10446 SRC 3 Ia Harm[9] Source 3 phase A current ninth harmonic 10447 SRC 3 Ia Harm[10] Source 3 phase A current tenth harmonic A-22 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 509

    Source 3 phase C current fifth harmonic 10509 SRC 3 Ic Harm[6] Source 3 phase C current sixth harmonic 10510 SRC 3 Ic Harm[7] Source 3 phase C current seventh harmonic GE Multilin C70 Capacitor Bank Protection and Control System A-23...

  • Page 510

    Source 4 phase B current second harmonic 10572 SRC 4 Ib Harm[3] Source 4 phase B current third harmonic 10573 SRC 4 Ib Harm[4] Source 4 phase B current fourth harmonic A-24 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 511

    Source 4 phase C current twenty-fourth harmonic 10627 SRC 4 Ic Harm[25] Source 4 phase C current twenty-fifth harmonic 10636 SRC 5 Ia THD Source 5 phase A current total harmonic distortion GE Multilin C70 Capacitor Bank Protection and Control System A-25...

  • Page 512

    Source 5 phase B current twenty-first harmonic 10690 SRC 5 Ib Harm[22] Source 5 phase B current twenty-second harmonic 10691 SRC 5 Ib Harm[23] Source 5 phase B current twenty-third harmonic A-26 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 513

    Source 6 phase A current eighteenth harmonic 10753 SRC 6 Ia Harm[19] Source 6 phase A current nineteenth harmonic 10754 SRC 6 Ia Harm[20] Source 6 phase A current twentieth harmonic GE Multilin C70 Capacitor Bank Protection and Control System A-27...

  • Page 514

    Source 6 phase C current fifteenth harmonic 10816 SRC 6 Ic Harm[16] Source 6 phase C current sixteenth harmonic 10817 SRC 6 Ic Harm[17] Source 6 phase C current seventeenth harmonic A-28 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 515

    RTD input 11 actual value 13563 RTD Ip 12 RTD input 12 actual value 13564 RTD Ip 13 RTD input 13 actual value 13565 RTD Ip 14 RTD input 14 actual value GE Multilin C70 Capacitor Bank Protection and Control System A-29...

  • Page 516

    60P 2 Raw Idiff B Phase current unbalance 2 raw phase B differential current actual value 13840 60P 2 Raw Idiff C Phase current unbalance 2 raw phase C differential current actual value A-30 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 517

    Neutral voltage unbalance 2 neutral-point Vx bus V0 magnitude 14082 59NU2Ntrl-p Vx Mag Neutral voltage unbalance 2 neutral-point Vx magnitude 14084 59NU2Vop Neutral voltage unbalance 2 neutral-point Vx operating voltage GE Multilin C70 Capacitor Bank Protection and Control System A-31...

  • Page 518

    V0 3rd Harmonic 1 Volts VTFF 1 V0 3rd Harmonic 41134 V0 3rd Harmonic 2 Volts VTFF 2 V0 3rd Harmonic 41136 V0 3rd Harmonic 3 Volts VTFF 3 V0 3rd Harmonic A-32 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 519

    GOOSE Analog In 30 IEC 61850 GOOSE analog input 30 45644 GOOSE Analog In 31 IEC 61850 GOOSE analog input 31 45646 GOOSE Analog In 32 IEC 61850 GOOSE analog input 32 GE Multilin C70 Capacitor Bank Protection and Control System A-33...

  • Page 520: A.1.2 Flexinteger Items

    9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 A-34 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 521: B.1.1 Introduction

    CRC: This is a two byte error checking code. The RTU version of Modbus includes a 16-bit cyclic redundancy check (CRC-16) with every packet which is an industry standard method used for error detection. If a Modbus slave device GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 522: B.1.4 Modbus Rtu Crc-16 Algorithm

    A C programming language implementation of the CRC algorithm will be provided upon request. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 523

    No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 524: B.2.1 Supported Function Codes

    NUMBER OF REGISTERS - low DATA #2 - high CRC - low DATA #2 - low CRC - high DATA #3 - high DATA #3 - low CRC - low CRC - high C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 525: B.2.3 Execute Operation (function Code 05h)

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 526: B.2.5 Store Multiple Settings (function Code 10h)

    EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 527: B.3.1 Obtaining Relay Files Via Modbus

    Familiarity with the data logger feature is required to understand this description. Refer to the Data Logger section of Chap- ter 5 for details. To read the entire data logger in binary COMTRADE format, read the following files. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 528

    To read from a specific record to another specific record, use the following filename: EVT.TXT xxxxx yyyyy (replace xxxxx with the starting record number and yyyyy with the ending record number) C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 529: B.4.1 Modbus Memory Map

    Virtual Input 13 State 0 to 1 F108 0 (Off) 040D Virtual Input 14 State 0 to 1 F108 0 (Off) 040E Virtual Input 15 State 0 to 1 F108 0 (Off) GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 530

    0 to 254 F001 0583 IEC103 Sync Timeout 1 to 1440 F001 IEC 103 Binary Inputs (Read/Write Setting) (96 modules) 0584 IEC103 Binary Input 1 FUN 0 to 255 F001 B-10 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 531

    0644 ...Repeated for Binary Input 49 0648 ...Repeated for Binary Input 50 064C ...Repeated for Binary Input 51 0650 ...Repeated for Binary Input 52 0654 ...Repeated for Binary Input 53 GE Multilin C70 Capacitor Bank Protection and Control System B-11...

  • Page 532

    IEC103 ASDU 1 Analog Param 2 0 to 65535 F600 070C IEC103 ASDU 1 Analog Factor 2 0 to 65.535 0.001 F001 1000 070D IEC103 ASDU 1 Analog Offset 2 -32768 to 32767 F002 B-12 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 533

    07D4 ...Repeated for IEC103 Command 22 07D8 ...Repeated for IEC103 Command 23 07DC ...Repeated for IEC103 Command 24 07E0 ...Repeated for IEC103 Command 25 07E4 ...Repeated for IEC103 Command 26 GE Multilin C70 Capacitor Bank Protection and Control System B-13...

  • Page 534

    3 (Bad) 1555 Remote Double-Point Status Input 5 State 0 to 3 F605 3 (Bad) Platform Direct Input/Output States (Read Only) 15C0 Direct Input States (6 items) 0 to 65535 F500 B-14 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 535

    16CE ...Repeated for Field Transducer 4 16D0 ...Repeated for Field Transducer 5 16D2 ...Repeated for Field Transducer 6 16D4 ...Repeated for Field Transducer 7 16D6 ...Repeated for Field Transducer 8 GE Multilin C70 Capacitor Bank Protection and Control System B-15...

  • Page 536

    Source 1 Auxiliary Voltage Angle -359.9 to 0 degrees F002 1A23 Source 1 Zero Sequence Voltage Magnitude 0 to 999999.999 0.001 F060 1A25 Source 1 Zero Sequence Voltage Angle -359.9 to 0 degrees F002 B-16 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 537

    Source 1 Vb THD 0 to 99.9 F001 1F9A Source 1 Vb Harmonics - 2nd to 25th (24 items) 0 to 99.9 F001 1FB2 Source 1 Vc THD 0 to 99.9 F001 GE Multilin C70 Capacitor Bank Protection and Control System B-17...

  • Page 538

    IEC 61850 GGIO5 uinteger Input 12 Operand F612 26DC IEC 61850 GGIO5 uinteger Input 13 Operand F612 26DD IEC 61850 GGIO5 uinteger Input 14 Operand F612 26DE IEC 61850 GGIO5 uinteger Input 15 Operand F612 B-18 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 539

    Oscillography Analog Values (Read Only) 3012 Oscillography Number of Triggers 0 to 32767 F001 User-Programmable Fault Report Commands (Read/Write Command) 3060 User Fault Report Clear 0 to 1 F126 0 (No) GE Multilin C70 Capacitor Bank Protection and Control System B-19...

  • Page 540

    0 to 65535 F618 Security (Read/Write Setting) 3329 Session Lockout 0 to 99 F001 332A Session Lockout Period 0 to 9999 F001 332B Load Factory Defaults 0 to 1 F126 0 (No) B-20 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 541

    –0.1000 to 0.1000 0.0001 F004 3459 Phase Current Unbalance Auto-set Kc 0 to 1 F126 0 (No) 345A ...Repeated for Phase Current Unbalance 2 3464 ...Repeated for Phase Current Unbalance 3 GE Multilin C70 Capacitor Bank Protection and Control System B-21...

  • Page 542

    34FF RTD Input 16 Value -32768 to 32767 °C F002 3500 RTD Input 17 Value -32768 to 32767 °C F002 3501 RTD Input 18 Value -32768 to 32767 °C F002 B-22 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 543

    0 to 99.9999 0.0001 F003 364A Voltage Differential 1 Differential Phase C Voltage 0 to 99.9999 0.0001 F003 364C ...Repeated for Voltage Differential 2 3658 ...Repeated for Voltage Differential 3 GE Multilin C70 Capacitor Bank Protection and Control System B-23...

  • Page 544

    3760 PTP GrandMaster ID 0 to 100 F073 3764 Real Time Clock Accuracy 0 to 999999999 F003 3766 PTP Port 1 State (3 items) 0 to 4 F625 0 (Disabled) B-24 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 545

    38A1 ...Repeated for Field Unit 2 38B2 ...Repeated for Field Unit 3 38C3 ...Repeated for Field Unit 4 38D4 ...Repeated for Field Unit 5 38E5 ...Repeated for Field Unit 6 GE Multilin C70 Capacitor Bank Protection and Control System B-25...

  • Page 546

    Field Shared Input 1 Events 0 to 1 F102 1 (Enabled) 3B09 ...Repeated for Field Shared Input 2 3B12 ...Repeated for Field Shared Input 3 3B1B ...Repeated for Field Shared Input 4 B-26 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 547

    ...Repeated for Field Shared Output 6 3E7E ...Repeated for Field Shared Output 7 3E8B ...Repeated for Field Shared Output 8 3E98 ...Repeated for Field Shared Output 9 3EA5 ...Repeated for Field Shared Output 10 GE Multilin C70 Capacitor Bank Protection and Control System B-27...

  • Page 548

    Setting Password Entry 0 to 4294967295 F202 (none) Passwords (Read Only) 4028 Command Password Status 0 to 1 F102 0 (Disabled) 4029 Setting Password Status 0 to 1 F102 0 (Disabled) B-28 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 549

    40A9 DNP Unsolicited Responses Function 0 to 1 F102 0 (Disabled) 40AA DNP Unsolicited Responses Timeout 0 to 60 F001 40AB DNP Unsolicited Responses Maximum Retries 1 to 255 F001 GE Multilin C70 Capacitor Bank Protection and Control System B-29...

  • Page 550

    DNP Object 1 Default Variation 1 to 2 F001 4141 DNP Object 2 Default Variation 1 to 3 F001 4142 DNP Object 20 Default Variation 0 to 3 F523 0 (1) B-30 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 551

    0 to 4294967295 F300 Trip and Alarm LEDs (Read/Write Setting) 42B0 Trip LED Input FlexLogic Operand 0 to 4294967295 F300 42B2 Alarm LED Input FlexLogic Operand 0 to 4294967295 F300 GE Multilin C70 Capacitor Bank Protection and Control System B-31...

  • Page 552

    PRP Status (Read Only) 4363 Total Received Port A 0 to 4294967295 F003 4365 Total Received Port B 0 to 4294967295 F003 4367 Total Mismatches Port A 0 to 4294967295 F003 B-32 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 553

    ...Repeated for VT Bank 6 Source Settings (Read/Write Setting) (6 modules) 4580 Source 1 Name 0 to 1 F206 “SRC 1" 4583 Source 1 Phase CT 0 to 63 F400 GE Multilin C70 Capacitor Bank Protection and Control System B-33...

  • Page 554

    F001 4C19 Reserved (7 items) F001 4C20 ...Repeated for User-Definable Display 2 4C40 ...Repeated for User-Definable Display 3 4C60 ...Repeated for User-Definable Display 4 4C80 ...Repeated for User-Definable Display 5 B-34 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 555

    4E84 Repeated for Field Unit 4 4E80 Repeated for Field Unit 5 4EDC Repeated for Field Unit 6 4F08 Repeated for Field Unit 7 4F34 Repeated for Field Unit 8 GE Multilin C70 Capacitor Bank Protection and Control System B-35...

  • Page 556

    575C ...Repeated for RTD Input 44 5770 ...Repeated for RTD Input 45 5784 ...Repeated for RTD Input 46 5798 ...Repeated for RTD Input 47 57AC ...Repeated for RTD Input 48 B-36 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 557

    ...Repeated for Phase Time Overcurrent 2 5928 ...Repeated for Phase Time Overcurrent 3 593C ...Repeated for Phase Time Overcurrent 4 5950 ...Repeated for Phase Time Overcurrent 5 5964 ...Repeated for Phase Time Overcurrent 6 GE Multilin C70 Capacitor Bank Protection and Control System B-37...

  • Page 558

    ...Repeated for Neutral Instantaneous Overcurrent 3 5C33 ...Repeated for Neutral Instantaneous Overcurrent 4 5C44 ...Repeated for Neutral Instantaneous Overcurrent 5 5C55 ...Repeated for Neutral Instantaneous Overcurrent 6 5C66 ...Repeated for Neutral Instantaneous Overcurrent 7 B-38 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 559

    0 to 1 F102 0 (Disabled) Setting Groups (Read Only) 5F7F Current Setting Group 0 to 5 F001 Setting Group Names (Read/Write Setting) 5F8C Setting Group 1 Name F203 (none) GE Multilin C70 Capacitor Bank Protection and Control System B-39...

  • Page 560

    Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 modules) 63C0 Negative Sequence Instantaneous OC 1 Function 0 to 1 F102 0 (Disabled) 63C1 Negative Sequence Instantaneous OC 1 Signal Source 0 to 5 F167 0 (SRC 1) B-40 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 561

    0 to 4294967295 F300 7047 Phase Overvoltage 1 Target 0 to 2 F109 0 (Self-reset) 7048 Phase Overvoltage 1 Events 0 to 1 F102 0 (Disabled) 7049 ...Repeated for Phase Overvoltage 2 GE Multilin C70 Capacitor Bank Protection and Control System B-41...

  • Page 562

    0 (3-Pole) 74A5 Disconnect Switch 1 Open 0 to 4294967295 F300 74A7 Disconnect Switch 1 Block Open 0 to 4294967295 F300 74A9 Disconnect Switch 1 Close 0 to 4294967295 F300 B-42 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 563

    F102 0 (Disabled) 77F9 Ohm Inputs 1 ID F205 "Ohm Ip 1 " 77FF Ohm Inputs 1 Reserved (9 items) 0 to 65535 F001 7808 ...Repeated for Ohm Inputs 2 GE Multilin C70 Capacitor Bank Protection and Control System B-43...

  • Page 564

    Auxiliary Overvoltage 1 Block 0 to 4294967295 F300 7FA7 Auxiliary Overvoltage 1 Target 0 to 2 F109 0 (Self-reset) 7FA8 Auxiliary Overvoltage 1 Events 0 to 1 F102 0 (Disabled) B-44 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 565

    0 to 4294967295 F300 Digital Elements (Read/Write Setting) (48 modules) 8A00 Digital Element 1 Function 0 to 1 F102 0 (Disabled) 8A01 Digital Element 1 Name F203 “Dig Element 1“ GE Multilin C70 Capacitor Bank Protection and Control System B-45...

  • Page 566

    8D9C ...Repeated for Digital Element 43 8DB2 ...Repeated for Digital Element 44 8DC8 ...Repeated for Digital Element 45 8DDE ...Repeated for Digital Element 46 8DF4 ...Repeated for Digital Element 47 B-46 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 567

    0 to 2 F522 0 (–1 to 1 mA) 9362 DCmA Output 1 Minimum –90 to 90 0.001 F004 9364 DCmA Output 1 Maximum –90 to 90 0.001 F004 1000 GE Multilin C70 Capacitor Bank Protection and Control System B-47...

  • Page 568

    9520 ...Repeated for Direct Input/Output 25 952C ...Repeated for Direct Input/Output 26 9538 ...Repeated for Direct Input/Output 27 9544 ...Repeated for Direct Input/Output 28 9550 ...Repeated for Direct Input/Output 29 B-48 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 569

    0 (Self-reset) 993E Breaker Restrike 1 Events 0 to 1 F102 0 (Disabled) 993F Reserved (2 items) F002 9941 ...Repeated for Breaker Restrike 2 9952 ...Repeated for Breaker Restrike 3 GE Multilin C70 Capacitor Bank Protection and Control System B-49...

  • Page 570

    9C9B Automatic Voltage Regulator 1 Power Factor Limit 0.50 to 1.00 0.01 F001 9C9C Automatic Voltage Regulator 1 var Open Mode 0 to 1 F537 1 (Minimize no. of ops.) B-50 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 571

    F001 1000 9D61 Neutral Voltage Unbalance 1 Stage 3 Pickup Delay 0 to 600.00 0.01 F001 9D62 Neutral Voltage Unbalance 1 Stage 4 Pickup Delay 0 to 600.00 0.01 F001 GE Multilin C70 Capacitor Bank Protection and Control System B-51...

  • Page 572

    Voltage Differential 1 Stage 3A Pickup 0.001 to 1.000 0.001 F001 9E4D Voltage Differential 1 Stage 4A Pickup 0.001 to 1.000 0.001 F001 9E4E Voltage Differential 1 Stage 1B Pickup 0.001 to 1.000 0.001 F001 B-52 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 573

    Selector 1 Power Up Mode 0 to 2 F084 0 (Restore) A292 Selector 1 Target 0 to 2 F109 0 (Self-reset) A293 Selector 1 Events 0 to 1 F102 0 (Disabled) GE Multilin C70 Capacitor Bank Protection and Control System B-53...

  • Page 574

    IEC 61850 Received Analog Settings (Read/Write Setting) (32 modules) AA00 IEC 61850 GOOSE Analog 1 Default Value –1000000 to 1000000 0.001 F060 1000 AA02 IEC 61850 GOOSE Analog Input 1 Mode 0 to 1 F491 0 (Default Value) B-54 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 575

    AC92 IEC 61850 Logical Node PTOVx Name Prefix (10 items) 0 to 65534 F206 (none) ACB6 IEC 61850 Logical Node PDISx Name Prefix (10 items) 0 to 65534 F206 (none) GE Multilin C70 Capacitor Bank Protection and Control System B-55...

  • Page 576

    ...Repeated for IEC 61850 GGIO4 Analog Input 32 IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting) B01C Default GOOSE/GSSE Update Time 1 to 60 F001 B01D IEC 61850 GSSE Function (GsEna) 0 to 1 F102 1 (Enabled) B-56 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 577

    0.001 to 100 0.001 F003 10000 B0F6 ...Repeated for Deadband 2 B12C ...Repeated for Deadband 3 B162 ...Repeated for Deadband 4 B198 ...Repeated for Deadband 5 B1CE ...Repeated for Deadband 6 GE Multilin C70 Capacitor Bank Protection and Control System B-57...

  • Page 578

    B394 ...Repeated for module number 13 B397 ...Repeated for module number 14 B39A ...Repeated for module number 15 B39D ...Repeated for module number 16 B3A0 ...Repeated for module number 17 B-58 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 579

    “Cont Ip 1“ BB06 Contact Input 1 Events 0 to 1 F102 0 (Disabled) BB07 Contact Input 1 Debounce Time 0 to 16 F001 BB08 ...Repeated for Contact Input 2 GE Multilin C70 Capacitor Bank Protection and Control System B-59...

  • Page 580

    BC98 ...Repeated for Contact Input 52 BCA0 ...Repeated for Contact Input 53 BCA8 ...Repeated for Contact Input 54 BCB0 ...Repeated for Contact Input 55 BCB8 ...Repeated for Contact Input 56 B-60 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 581

    BE48 ...Repeated for Virtual Input 3 BE54 ...Repeated for Virtual Input 4 BE60 ...Repeated for Virtual Input 5 BE6C ...Repeated for Virtual Input 6 BE78 ...Repeated for Virtual Input 7 GE Multilin C70 Capacitor Bank Protection and Control System B-61...

  • Page 582

    C0D0 ...Repeated for Virtual Input 57 C0DC ...Repeated for Virtual Input 58 C0E8 ...Repeated for Virtual Input 59 C0F4 ...Repeated for Virtual Input 60 C100 ...Repeated for Virtual Input 61 B-62 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 583

    C288 ...Repeated for Virtual Output 44 C290 ...Repeated for Virtual Output 45 C298 ...Repeated for Virtual Output 46 C2A0 ...Repeated for Virtual Output 47 C2A8 ...Repeated for Virtual Output 48 GE Multilin C70 Capacitor Bank Protection and Control System B-63...

  • Page 584

    Force VFD and LED 0 to 1 F126 0 (No) C432 Test Mode Initiate 0 to 4294967295 F300 Clear Commands (Read/Write) C434 Clear All Relay Records Command 0 to 1 F126 0 (No) B-64 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 585

    Control Pushbuttons (Read/Write Setting) (7 modules) C760 Control Pushbutton 1 Function 0 to 1 F102 0 (Disabled) C761 Control Pushbutton 1 Events 0 to 1 F102 0 (Disabled) C762 ...Repeated for Control Pushbutton 2 GE Multilin C70 Capacitor Bank Protection and Control System B-65...

  • Page 586

    ...Repeated for Direct Input 31 C90C ...Repeated for Direct Input 32 Direct Input/Output Alarms (Read/Write Setting) CAD0 Direct Input/Output Channel 1 CRC Alarm Function 0 to 1 F102 0 (Disabled) B-66 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 587

    0 to 1 F102 0 (Disabled) CFA4 Remote Input 1 Name 1 to 64 F205 “Rem Ip 1” CFAA ...Repeated for Remote Input 2 CFB4 ...Repeated for Remote Input 3 GE Multilin C70 Capacitor Bank Protection and Control System B-67...

  • Page 588

    D264 ...Repeated for Remote Output 18 D268 ...Repeated for Remote Output 19 D26C ...Repeated for Remote Output 20 D270 ...Repeated for Remote Output 21 D274 ...Repeated for Remote Output 22 B-68 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 589

    0 to 2 F001 D325 IEC 61850 GGIO2.CF.SPCSO6.ctlModel Value 0 to 2 F001 D326 IEC 61850 GGIO2.CF.SPCSO7.ctlModel Value 0 to 2 F001 D327 IEC 61850 GGIO2.CF.SPCSO8.ctlModel Value 0 to 2 F001 GE Multilin C70 Capacitor Bank Protection and Control System B-69...

  • Page 590

    0 to 2 F001 D35B IEC 61850 GGIO2.CF.SPCSO60.ctlModel Value 0 to 2 F001 D35C IEC 61850 GGIO2.CF.SPCSO61.ctlModel Value 0 to 2 F001 D35D IEC 61850 GGIO2.CF.SPCSO62.ctlModel Value 0 to 2 F001 B-70 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 591

    D51B ...Repeated for Contact Output 22 D52A ...Repeated for Contact Output 23 D539 ...Repeated for Contact Output 24 D548 ...Repeated for Contact Output 25 D557 ...Repeated for Contact Output 26 GE Multilin C70 Capacitor Bank Protection and Control System B-71...

  • Page 592

    D7EC ...Repeated for DCmA Inputs 5 D7FF ...Repeated for DCmA Inputs 6 D812 ...Repeated for DCmA Inputs 7 D825 ...Repeated for DCmA Inputs 8 D838 ...Repeated for DCmA Inputs 9 B-72 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 593

    (none) Setting File Template (Read Only Non-Volatile) ED07 Last Settings Change Date 0 to 4294967295 F050 Settings File Template (Read/Write Setting) ED09 Template Bitmask (750 items) 0 to 65535 F001 GE Multilin C70 Capacitor Bank Protection and Control System B-73...

  • Page 594: B.4.2 Data Formats

    UR_UINT32 TIME in SR format (alternate format for F050) 0 = Grounded, 1 = Ungrounded, 2 = Ungrounded without Vn First 16 bits are Hours/Minutes (HH:MM:xx.xxx). Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm. Minutes: 0 to 59 in steps of 1. B-74 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 595

    Phase Instantaneous Overcurrent 3 ENUMERATION: CONTACT OUTPUT OPERATION Phase Instantaneous Overcurrent 4 0 = Self-reset, 1 = Latched, 2 = Disabled Phase Instantaneous Overcurrent 5 Phase Instantaneous Overcurrent 6 Phase Instantaneous Overcurrent 7 GE Multilin C70 Capacitor Bank Protection and Control System B-75...

  • Page 596

    Ground Time Overcurrent 3 FlexElement 6 Ground Time Overcurrent 4 FlexElement 7 Ground Time Overcurrent 5 FlexElement 8 Ground Time Overcurrent 6 FlexElement 9 Negative Sequence Instantaneous Overcurrent 1 FlexElement 10 B-76 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 597

    Digital Element 20 Neutral current unbalance 1 Digital Element 21 Neutral current unbalance 2 Digital Element 22 Neutral current unbalance 3 Digital Element 23 Bank phase overvoltage 1 phase A GE Multilin C70 Capacitor Bank Protection and Control System B-77...

  • Page 598

    RTD Input 37 Breaker 2 RTD Input 38 Breaker 3 RTD Input 39 Breaker 4 RTD Input 40 Breaker 5 RTD Input 41 Breaker 6 RTD Input 42 Breaker restrike 1 B-78 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 599

    Any Self Tests Module Failure 11 IRIG-B Failure Module Failure 12 Port 1 Offline High ENET Traffic Port 2 Offline Relay Restart Port 3 Offline FGM Failure Port 4 Offline FGM Failure GE Multilin C70 Capacitor Bank Protection and Control System B-79...

  • Page 600

    Ethernet Port 5 Offline DNA-27 UserSt-30 Ethernet Port 6 Offline DNA-28 UserSt-31 Test Mode Isolated DNA-29 UserSt-32 Test Mode Forcible DNA-30 Dataset Item 1 Test Mode Disabled DNA-31 Dataset Item 2 B-80 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 601

    0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel, ENUMERATION: MEASUREMENT MODE 2 = 100 Ohm Nickel, 3 = 10 Ohm Copper 0 = Phase to Ground, 1 = Phase to Phase GE Multilin C70 Capacitor Bank Protection and Control System B-81...

  • Page 602

    ENUMERATION: CONFIGURABLE GOOSE Tx DATASET ITEMS F202 Value IEC 61850 Tx dataset item TEXT20: 20-CHARACTER ASCII TEXT None 10 registers, 16 Bits: 1st Char MSB, 2nd Char LSB GGIO1.ST.Ind1.q GGIO1.ST.Ind1.stVal B-82 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 603

    MMXU1.MX.VA.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU1.MX.PF.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU1.MX.PF.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU1.MX.PF.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU2.MX.TotW.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU2.MX.TotVAr.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU2.MX.TotVA.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU2.MX.TotPF.mag.f MMXU3.MX.A.phsB.cVal.mag.f MMXU2.MX.Hz.mag.f MMXU3.MX.A.phsB.cVal.ang.f MMXU2.MX.PPV.phsAB.cVal.mag.f MMXU3.MX.A.phsC.cVal.mag.f MMXU2.MX.PPV.phsAB.cVal.ang.f MMXU3.MX.A.phsC.cVal.ang.f MMXU2.MX.PPV.phsBC.cVal.mag.f MMXU3.MX.A.neut.cVal.mag.f MMXU2.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.A.neut.cVal.ang.f MMXU2.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.W.phsA.cVal.mag.f MMXU2.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.W.phsB.cVal.mag.f GE Multilin C70 Capacitor Bank Protection and Control System B-83...

  • Page 604

    MMXU4.MX.VAr.phsA.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f MMXU4.MX.VA.phsA.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f MMXU4.MX.PF.phsC.cVal.mag.f MMXU6.MX.PhV.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f MMXU6.MX.A.phsA.cVal.mag.f MMXU5.MX.TotVA.mag.f MMXU6.MX.A.phsA.cVal.ang.f MMXU5.MX.TotPF.mag.f MMXU6.MX.A.phsB.cVal.mag.f MMXU5.MX.Hz.mag.f MMXU6.MX.A.phsB.cVal.ang.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU6.MX.A.phsC.cVal.mag.f B-84 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 605

    ↓ GGIO4.MX.AnIn24.mag.f GGIO3.ST.Ind64q GGIO4.MX.AnIn25.mag.f GGIO3.ST.Ind64.stVal GGIO4.MX.AnIn26.mag.f GGIO3.MX.AnIn1.mag.f GGIO4.MX.AnIn27.mag.f GGIO3.MX.AnIn2.mag.f GGIO4.MX.AnIn28.mag.f GGIO3.MX.AnIn3.mag.f GGIO4.MX.AnIn29.mag.f GGIO3.MX.AnIn4.mag.f GGIO4.MX.AnIn30.mag.f GGIO3.MX.AnIn5.mag.f GGIO4.MX.AnIn31.mag.f GGIO3.MX.AnIn6.mag.f GGIO4.MX.AnIn32.mag.f GGIO3.MX.AnIn7.mag.f GGIO5.ST.UIntIn1.q GGIO3.MX.AnIn8.mag.f GGIO5.ST.UIntIn1.stVal GGIO3.MX.AnIn9.mag.f GGIO5.ST.UIntIn2.q GGIO3.MX.AnIn10.mag.f GGIO5.ST.UIntIn2.stVal GGIO3.MX.AnIn11.mag.f GGIO5.ST.UIntIn3.q GGIO3.MX.AnIn12.mag.f GGIO5.ST.UIntIn3.stVal GE Multilin C70 Capacitor Bank Protection and Control System B-85...

  • Page 606

    Instance GGIO3.ST.UIntIn9.q First GGIO3.ST.UIntIn9.stVal Second GGIO3.ST.UIntIn10.q Third GGIO3.ST.UIntIn10.stVal Fourth GGIO3.ST.UIntIn11.q Last GGIO3.ST.UIntIn11.stVal GGIO3.ST.UIntIn12.q GGIO3.ST.UIntIn12.stVal F241 ENUMERATION: NEUTRAL VOLTAGE UNBALANCE BUS 3V0 GGIO3.ST.UIntIn13.q GGIO3.ST.UIntIn13.stVal 0 = Calculated, 1 = Measured GGIO3.ST.UIntIn14.q B-86 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 607

    ENUMERATION: CAPACITOR BANK GROUNDING U1/AC5..7 Value Description U2/AC1..3 VT (ungrounded) U2/AC5..7 CTxR (grounded) U3/AC1..3 U3/AC5..7 U4/AC1..3 F256 U4/AC5..7 ENUMERATION: BRICK ORIGIN/DESTINATION U5/AC1..3 Value Description U5/AC5..7 None U6/AC1..3 U6/AC5..7 U7/AC1..3 U7/AC5..7 U8/AC1..3 GE Multilin C70 Capacitor Bank Protection and Control System B-87...

  • Page 608

    LED and bit 7 the bottom LED. A bit value of 1 indicates [24] MISCELLANEOUS EQUATION the LED is on, 0 indicates the LED is off. [26] TELEPROTECTION INPUTS [28] INSERT (via keypad only) 0 = Off, 1 = On B-88 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 609

    ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION CONTROL MODE Bitmask Default variation 0 = Voltage, 1 = Var F537 ENUMERATION: AUTOMATIC VOLTAGE REGULATOR VAR OPEN MODE 0 = Minimize uptime, 1 = Minimize number of operations GE Multilin C70 Capacitor Bank Protection and Control System B-89...

  • Page 610

    This 16-bit value corresponds to the Modbus address of the PIOC8.ST.Op.general selected FlexInteger parameter. Only certain values can be used as FlexIntegers. There is no operation executed even though they PIOC9.ST.Str.general are called FlexIntegers. PIOC9.ST.Op.general PIOC10.ST.Str.general PIOC10.ST.Op.general B-90 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 611

    PIOC30.ST.Str.general PIOC56.ST.Op.general PIOC30.ST.Op.general PIOC57.ST.Str.general PIOC31.ST.Str.general PIOC57.ST.Op.general PIOC31.ST.Op.general PIOC58.ST.Str.general PIOC32.ST.Str.general PIOC58.ST.Op.general PIOC32.ST.Op.general PIOC59.ST.Str.general PIOC33.ST.Str.general PIOC59.ST.Op.general PIOC33.ST.Op.general PIOC60.ST.Str.general PIOC34.ST.Str.general PIOC60.ST.Op.general PIOC34.ST.Op.general PIOC61.ST.Str.general PIOC35.ST.Str.general PIOC61.ST.Op.general PIOC35.ST.Op.general PIOC62.ST.Str.general PIOC36.ST.Str.general PIOC62.ST.Op.general PIOC36.ST.Op.general PIOC63.ST.Str.general PIOC37.ST.Str.general PIOC63.ST.Op.general GE Multilin C70 Capacitor Bank Protection and Control System B-91...

  • Page 612

    PTOC11.ST.Str.general PTRC3.ST.Op.general PTOC11.ST.Op.general PTRC4.ST.Tr.general PTOC12.ST.Str.general PTRC4.ST.Op.general PTOC12.ST.Op.general PTRC5.ST.Tr.general PTOC13.ST.Str.general PTRC5.ST.Op.general PTOC13.ST.Op.general PTRC6.ST.Tr.general PTOC14.ST.Str.general PTRC6.ST.Op.general PTOC14.ST.Op.general PTUV1.ST.Str.general PTOC15.ST.Str.general PTUV1.ST.Op.general PTOC15.ST.Op.general PTUV2.ST.Str.general PTOC16.ST.Str.general PTUV2.ST.Op.general PTOC16.ST.Op.general PTUV3.ST.Str.general PTOC17.ST.Str.general PTUV3.ST.Op.general PTOC17.ST.Op.general PTUV4.ST.Str.general PTOC18.ST.Str.general PTUV4.ST.Op.general B-92 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 613

    RBRF11.ST.OpEx.general CSWI3.ST.Pos.stVal RBRF11.ST.OpIn.general CSWI4.ST.Loc.stVal RBRF12.ST.OpEx.general CSWI4.ST.Pos.stVal RBRF12.ST.OpIn.general CSWI5.ST.Loc.stVal RBRF13.ST.OpEx.general CSWI5.ST.Pos.stVal RBRF13.ST.OpIn.general CSWI6.ST.Loc.stVal RBRF14.ST.OpEx.general CSWI6.ST.Pos.stVal RBRF14.ST.OpIn.general CSWI7.ST.Loc.stVal RBRF15.ST.OpEx.general CSWI7.ST.Pos.stVal RBRF15.ST.OpIn.general CSWI8.ST.Loc.stVal RBRF16.ST.OpEx.general CSWI8.ST.Pos.stVal RBRF16.ST.OpIn.general CSWI9.ST.Loc.stVal RBRF17.ST.OpEx.general CSWI9.ST.Pos.stVal RBRF17.ST.OpIn.general CSWI10.ST.Loc.stVal RBRF18.ST.OpEx.general CSWI10.ST.Pos.stVal GE Multilin C70 Capacitor Bank Protection and Control System B-93...

  • Page 614

    CSWI30.ST.Loc.stVal GGIO1.ST.Ind52.stVal CSWI30.ST.Pos.stVal GGIO1.ST.Ind53.stVal GGIO1.ST.Ind1.stVal GGIO1.ST.Ind54.stVal GGIO1.ST.Ind2.stVal GGIO1.ST.Ind55.stVal GGIO1.ST.Ind3.stVal GGIO1.ST.Ind56.stVal GGIO1.ST.Ind4.stVal GGIO1.ST.Ind57.stVal GGIO1.ST.Ind5.stVal GGIO1.ST.Ind58.stVal GGIO1.ST.Ind6.stVal GGIO1.ST.Ind59.stVal GGIO1.ST.Ind7.stVal GGIO1.ST.Ind60.stVal GGIO1.ST.Ind8.stVal GGIO1.ST.Ind61.stVal GGIO1.ST.Ind9.stVal GGIO1.ST.Ind62.stVal GGIO1.ST.Ind10.stVal GGIO1.ST.Ind63.stVal GGIO1.ST.Ind11.stVal GGIO1.ST.Ind64.stVal GGIO1.ST.Ind12.stVal GGIO1.ST.Ind65.stVal GGIO1.ST.Ind13.stVal GGIO1.ST.Ind66.stVal B-94 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 615

    GGIO1.ST.Ind105.stVal MMXU1.MX.VAr.phsB.cVal.mag.f GGIO1.ST.Ind106.stVal MMXU1.MX.VAr.phsC.cVal.mag.f GGIO1.ST.Ind107.stVal MMXU1.MX.VA.phsA.cVal.mag.f GGIO1.ST.Ind108.stVal MMXU1.MX.VA.phsB.cVal.mag.f GGIO1.ST.Ind109.stVal MMXU1.MX.VA.phsC.cVal.mag.f GGIO1.ST.Ind110.stVal MMXU1.MX.PF.phsA.cVal.mag.f GGIO1.ST.Ind111.stVal MMXU1.MX.PF.phsB.cVal.mag.f GGIO1.ST.Ind112.stVal MMXU1.MX.PF.phsC.cVal.mag.f GGIO1.ST.Ind113.stVal MMXU2.MX.TotW.mag.f GGIO1.ST.Ind114.stVal MMXU2.MX.TotVAr.mag.f GGIO1.ST.Ind115.stVal MMXU2.MX.TotVA.mag.f GGIO1.ST.Ind116.stVal MMXU2.MX.TotPF.mag.f GGIO1.ST.Ind117.stVal MMXU2.MX.Hz.mag.f GGIO1.ST.Ind118.stVal MMXU2.MX.PPV.phsAB.cVal.mag.f GGIO1.ST.Ind119.stVal MMXU2.MX.PPV.phsAB.cVal.ang.f GE Multilin C70 Capacitor Bank Protection and Control System B-95...

  • Page 616

    MMXU3.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.A.neut.cVal.ang.f MMXU3.MX.PPV.phsCA.cVal.mag.f MMXU4.MX.W.phsA.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.W.phsB.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU4.MX.VA.phsA.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU3.MX.A.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f MMXU3.MX.A.phsB.cVal.ang.f MMXU4.MX.PF.phsC.cVal.mag.f MMXU3.MX.A.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU3.MX.A.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f B-96 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 617

    MMXU6.MX.TotPF.mag.f GGIO4.MX.AnIn20.mag.f MMXU6.MX.Hz.mag.f GGIO4.MX.AnIn21.mag.f MMXU6.MX.PPV.phsAB.cVal.mag.f GGIO4.MX.AnIn22.mag.f MMXU6.MX.PPV.phsAB.cVal.ang.f GGIO4.MX.AnIn23.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f GGIO4.MX.AnIn24.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f GGIO4.MX.AnIn25.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f GGIO4.MX.AnIn26.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f GGIO4.MX.AnIn27.mag.f MMXU6.MX.PhV.phsA.cVal.mag.f GGIO4.MX.AnIn28.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f GGIO4.MX.AnIn29.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f GGIO4.MX.AnIn30.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f GGIO4.MX.AnIn31.mag.f MMXU6.MX.PhV.phsC.cVal.mag.f GGIO4.MX.AnIn32.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f XSWI1.ST.Loc.stVal MMXU6.MX.A.phsA.cVal.mag.f XSWI1.ST.Pos.stVal GE Multilin C70 Capacitor Bank Protection and Control System B-97...

  • Page 618

    GGIO1.ST.Ind14.stVal XSWI21.ST.Loc.stVal GGIO1.ST.Ind15.q XSWI21.ST.Pos.stVal GGIO1.ST.Ind15.stVal XSWI22.ST.Loc.stVal GGIO1.ST.Ind16.q XSWI22.ST.Pos.stVal GGIO1.ST.Ind16.stVal XSWI23.ST.Loc.stVal GGIO1.ST.Ind17.q XSWI23.ST.Pos.stVal GGIO1.ST.Ind17.stVal XSWI24.ST.Loc.stVal GGIO1.ST.Ind18.q XSWI24.ST.Pos.stVal GGIO1.ST.Ind18.stVal XCBR1.ST.Loc.stVal GGIO1.ST.Ind19.q XCBR1.ST.Pos.stVal GGIO1.ST.Ind19.stVal XCBR2.ST.Loc.stVal GGIO1.ST.Ind20.q XCBR2.ST.Pos.stVal GGIO1.ST.Ind20.stVal XCBR3.ST.Loc.stVal GGIO1.ST.Ind21.q XCBR3.ST.Pos.stVal GGIO1.ST.Ind21.stVal XCBR4.ST.Loc.stVal B-98 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 619

    GGIO1.ST.Ind41.q GGIO1.ST.Ind67.stVal GGIO1.ST.Ind41.stVal GGIO1.ST.Ind68.q GGIO1.ST.Ind42.q GGIO1.ST.Ind68.stVal GGIO1.ST.Ind42.stVal GGIO1.ST.Ind69.q GGIO1.ST.Ind43.q GGIO1.ST.Ind69.stVal GGIO1.ST.Ind43.stVal GGIO1.ST.Ind70.q GGIO1.ST.Ind44.q GGIO1.ST.Ind70.stVal GGIO1.ST.Ind44.stVal GGIO1.ST.Ind71.q GGIO1.ST.Ind45.q GGIO1.ST.Ind71.stVal GGIO1.ST.Ind45.stVal GGIO1.ST.Ind72.q GGIO1.ST.Ind46.q GGIO1.ST.Ind72.stVal GGIO1.ST.Ind46.stVal GGIO1.ST.Ind73.q GGIO1.ST.Ind47.q GGIO1.ST.Ind73.stVal GGIO1.ST.Ind47.stVal GGIO1.ST.Ind74.q GGIO1.ST.Ind48.q GGIO1.ST.Ind74.stVal GE Multilin C70 Capacitor Bank Protection and Control System B-99...

  • Page 620

    GGIO1.ST.Ind94.q GGIO1.ST.Ind120.stVal GGIO1.ST.Ind94.stVal GGIO1.ST.Ind121.q GGIO1.ST.Ind95.q GGIO1.ST.Ind121.stVal GGIO1.ST.Ind95.stVal GGIO1.ST.Ind122.q GGIO1.ST.Ind96.q GGIO1.ST.Ind122.stVal GGIO1.ST.Ind96.stVal GGIO1.ST.Ind123.q GGIO1.ST.Ind97.q GGIO1.ST.Ind123.stVal GGIO1.ST.Ind97.stVal GGIO1.ST.Ind124.q GGIO1.ST.Ind98.q GGIO1.ST.Ind124.stVal GGIO1.ST.Ind98.stVal GGIO1.ST.Ind125.q GGIO1.ST.Ind99.q GGIO1.ST.Ind125.stVal GGIO1.ST.Ind99.stVal GGIO1.ST.Ind126.q GGIO1.ST.Ind100.q GGIO1.ST.Ind126.stVal GGIO1.ST.Ind100.stVal GGIO1.ST.Ind127.q GGIO1.ST.Ind101.q GGIO1.ST.Ind127.stVal B-100 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 621

    MMXU1.MX.PF.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU2.MX.TotW.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU2.MX.TotVAr.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU2.MX.TotVA.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU2.MX.TotPF.mag.f MMXU3.MX.A.phsB.cVal.mag.f MMXU2.MX.Hz.mag.f MMXU3.MX.A.phsB.cVal.ang.f MMXU2.MX.PPV.phsAB.cVal.mag.f MMXU3.MX.A.phsC.cVal.mag.f MMXU2.MX.PPV.phsAB.cVal.ang.f MMXU3.MX.A.phsC.cVal.ang.f MMXU2.MX.PPV.phsBC.cVal.mag.f MMXU3.MX.A.neut.cVal.mag.f MMXU2.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.A.neut.cVal.ang.f MMXU2.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.W.phsA.cVal.mag.f MMXU2.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.W.phsB.cVal.mag.f MMXU2.MX.PhV.phsA.cVal.mag.f MMXU3.MX.W.phsC.cVal.mag.f MMXU2.MX.PhV.phsA.cVal.ang.f MMXU3.MX.VAr.phsA.cVal.mag.f MMXU2.MX.PhV.phsB.cVal.mag.f MMXU3.MX.VAr.phsB.cVal.mag.f GE Multilin C70 Capacitor Bank Protection and Control System B-101...

  • Page 622

    MMXU4.MX.VA.phsA.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f MMXU4.MX.PF.phsC.cVal.mag.f MMXU6.MX.PhV.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f MMXU6.MX.A.phsA.cVal.mag.f MMXU5.MX.TotVA.mag.f MMXU6.MX.A.phsA.cVal.ang.f MMXU5.MX.TotPF.mag.f MMXU6.MX.A.phsB.cVal.mag.f MMXU5.MX.Hz.mag.f MMXU6.MX.A.phsB.cVal.ang.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU6.MX.A.phsC.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.ang.f MMXU6.MX.A.phsC.cVal.ang.f MMXU5.MX.PPV.phsBC.cVal.mag.f MMXU6.MX.A.neut.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU6.MX.A.neut.cVal.ang.f B-102 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 623

    GGIO4.MX.AnIn27.mag.f PDIS4.ST.Op.general GGIO4.MX.AnIn28.mag.f PDIS5.ST.Str.general GGIO4.MX.AnIn29.mag.f PDIS5.ST.Op.general GGIO4.MX.AnIn30.mag.f PDIS6.ST.Str.general GGIO4.MX.AnIn31.mag.f PDIS6.ST.Op.general GGIO4.MX.AnIn32.mag.f PDIS7.ST.Str.general GGIO5.ST.UIntIn1.q PDIS7.ST.Op.general GGIO5.ST.UIntIn1.stVal PDIS8.ST.Str.general GGIO5.ST.UIntIn2.q PDIS8.ST.Op.general GGIO5.ST.UIntIn2.stVal PDIS9.ST.Str.general GGIO5.ST.UIntIn3.q PDIS9.ST.Op.general GGIO5.ST.UIntIn3.stVal PDIS10.ST.Str.general GGIO5.ST.UIntIn4.q PDIS10.ST.Op.general GGIO5.ST.UIntIn4.stVal PIOC1.ST.Str.general GGIO5.ST.UIntIn5.q PIOC1.ST.Op.general GE Multilin C70 Capacitor Bank Protection and Control System B-103...

  • Page 624

    PIOC21.ST.Str.general PIOC47.ST.Op.general PIOC21.ST.Op.general PIOC48.ST.Str.general PIOC22.ST.Str.general PIOC48.ST.Op.general PIOC22.ST.Op.general PIOC49.ST.Str.general PIOC23.ST.Str.general PIOC49.ST.Op.general PIOC23.ST.Op.general PIOC50.ST.Str.general PIOC24.ST.Str.general PIOC50.ST.Op.general PIOC24.ST.Op.general PIOC51.ST.Str.general PIOC25.ST.Str.general PIOC51.ST.Op.general PIOC25.ST.Op.general PIOC52.ST.Str.general PIOC26.ST.Str.general PIOC52.ST.Op.general PIOC26.ST.Op.general PIOC53.ST.Str.general PIOC27.ST.Str.general PIOC53.ST.Op.general PIOC27.ST.Op.general PIOC54.ST.Str.general PIOC28.ST.Str.general PIOC54.ST.Op.general B-104 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 625

    PTOC2.ST.Str.general PTOV4.ST.Op.general PTOC2.ST.Op.general PTOV5.ST.Str.general PTOC3.ST.Str.general PTOV5.ST.Op.general PTOC3.ST.Op.general PTOV6.ST.Str.general PTOC4.ST.Str.general PTOV6.ST.Op.general PTOC4.ST.Op.general PTOV7.ST.Str.general PTOC5.ST.Str.general PTOV7.ST.Op.general PTOC5.ST.Op.general PTOV8.ST.Str.general PTOC6.ST.Str.general PTOV8.ST.Op.general PTOC6.ST.Op.general PTOV9.ST.Str.general PTOC7.ST.Str.general PTOV9.ST.Op.general PTOC7.ST.Op.general PTOV10.ST.Str.general PTOC8.ST.Str.general PTOV10.ST.Op.general PTOC8.ST.Op.general PTRC1.ST.Tr.general PTOC9.ST.Str.general PTRC1.ST.Op.general GE Multilin C70 Capacitor Bank Protection and Control System B-105...

  • Page 626

    RBRF2.ST.OpEx.general RPSB1.ST.BlkZn.stVal RBRF2.ST.OpIn.general RREC1.ST.Op.general RBRF3.ST.OpEx.general RREC1.ST.AutoRecSt.stVal RBRF3.ST.OpIn.general RREC2.ST.Op.general RBRF4.ST.OpEx.general RREC2.ST.AutoRecSt.stVal RBRF4.ST.OpIn.general RREC3.ST.Op.general RBRF5.ST.OpEx.general RREC3.ST.AutoRecSt.stVal RBRF5.ST.OpIn.general RREC4.ST.Op.general RBRF6.ST.OpEx.general RREC4.ST.AutoRecSt.stVal RBRF6.ST.OpIn.general RREC5.ST.Op.general RBRF7.ST.OpEx.general RREC5.ST.AutoRecSt.stVal RBRF7.ST.OpIn.general RREC6.ST.Op.general RBRF8.ST.OpEx.general RREC6.ST.AutoRecSt.stVal RBRF8.ST.OpIn.general CSWI1.ST.Loc.stVal RBRF9.ST.OpEx.general CSWI1.ST.Pos.stVal B-106 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 627

    CSWI21.ST.Loc.stVal XSWI17.ST.Pos.stVal CSWI21.ST.Pos.stVal XSWI18.ST.Loc.stVal CSWI22.ST.Loc.stVal XSWI18.ST.Pos.stVal CSWI22.ST.Pos.stVal XSWI19.ST.Loc.stVal CSWI23.ST.Loc.stVal XSWI19.ST.Pos.stVal CSWI23.ST.Pos.stVal XSWI20.ST.Loc.stVal CSWI24.ST.Loc.stVal XSWI20.ST.Pos.stVal CSWI24.ST.Pos.stVal XSWI21.ST.Loc.stVal CSWI25.ST.Loc.stVal XSWI21.ST.Pos.stVal CSWI25.ST.Pos.stVal XSWI22.ST.Loc.stVal CSWI26.ST.Loc.stVal XSWI22.ST.Pos.stVal CSWI26.ST.Pos.stVal XSWI23.ST.Loc.stVal CSWI27.ST.Loc.stVal XSWI23.ST.Pos.stVal CSWI27.ST.Pos.stVal XSWI24.ST.Loc.stVal CSWI28.ST.Loc.stVal XSWI24.ST.Pos.stVal GE Multilin C70 Capacitor Bank Protection and Control System B-107...

  • Page 628

    Enumeration Role None F627 ENUMERATION: REDUNDANCY MODE Administrator Supervisor Enumeration Item Engineer None Operator Failover Observer F628 ENUMERATION: SECURITY BYPASS ACCESS Disables security on local access, remote access, or both. B-108 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 629

    ENUMERATION: SCADA PROTOCOL ↓ ↓ 0 = DNP 3.0, 1 = IEC 60870-5-104, 2 = IEC 60870-5-103 Virtual Input 64 F630 ENUMERATION: IEC 103 ASDU TYPE 0 = 3, 1 = 9 GE Multilin C70 Capacitor Bank Protection and Control System B-109...

  • Page 630

    B.4 MEMORY MAPPING APPENDIX B B-110 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 631: C.1.2 Communication Profiles

    LAN environment. Actual MMS protocol services are mapped to IEC 61850 abstract ser- vices in IEC 61850-8-1. The C70 relay supports IEC 61850 server services over TCP/IP. The TCP/IP profile requires the C70 to have an IP address to establish communications. These addresses are located in the ...

  • Page 632: C.1.3 File Transfer By Iec 61850

    APPENDIX C C.1.3 FILE TRANSFER BY IEC 61850 The C70 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as an example. In the AX-S4 61850 Explorer window, click the Tools menu and access the SISCO File Transfer Utility.

  • Page 633: C.2.1 Overview

    C.2.2 GGIO1: DIGITAL STATUS VALUES The GGIO1 logical node is available in the C70 to provide access to as many 128 digital status points and associated time- stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients.

  • Page 634: C.2.6 Mmxu: Analog Measured Values

    A limited number of measured analog values are available through the MMXU logical nodes. Each MMXU logical node provides data from a C70 current and voltage source. There is one MMXU available for each con- figurable source (programmed in the ...

  • Page 635

    The protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 is PIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the C70 protection elements, these flags take their values from the pickup and operate FlexLogic operands for the corresponding element.

  • Page 636: C.3.1 Buffered/unbuffered Reporting

    C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the C70. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of the two character strings programmed in the settings.

  • Page 637: C.3.6 Logical Node Name Prefixes

    A built-in TCP/IP connection timeout of two minutes is employed by the C70 to detect ‘dead’ connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the C70. This frees up the con- nection to be used by other clients.

  • Page 638: C.4.1 Overview

    MAC address for GSSE messages. If GSSE DESTINATION MAC ADDRESS a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the C70 will use the source Ether- net MAC address as the destination, with the multicast bit set.

  • Page 639

    The C70 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.

  • Page 640

    REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic equations or other settings. The C70 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.

  • Page 641: C.4.5 Ethernet Mac Address For Gsse/goose

    GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the C70 is configured to use an automated multicast MAC scheme. If the C70 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina- tion MAC will be the same as the local MAC address, but with the multicast bit set.

  • Page 642: C.5.1 Overview

    An ICD file is generated for the C70 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.

  • Page 643: C.5.2 Configuring Iec 61850 Settings

    Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the C70 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file.

  • Page 644: C.5.3 About Icd Files

    Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...

  • Page 645

    Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. GE Multilin C70 Capacitor Bank Protection and Control System C-15...

  • Page 646

    Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure C–4: ICD FILE STRUCTURE, IED NODE C-16 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 647

    Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure C–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE GE Multilin C70 Capacitor Bank Protection and Control System C-17...

  • Page 648: C.5.4 Creating An Icd File With Enervista Ur Setup

    The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file. The time to create an ICD file from the offline C70 settings file is typically much quicker than create an ICD file directly from the relay.

  • Page 649

    Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE GE Multilin C70 Capacitor Bank Protection and Control System C-19...

  • Page 650

    IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. C-20 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 651: C.5.6 Importing An Scd File With Enervista Ur Setup

    Figure C–9: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the C70 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item.

  • Page 652

    The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.

  • Page 653: C.6.1 Acsi Basic Conformance Statement

    Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion GE Multilin C70 Capacitor Bank Protection and Control System C-23...

  • Page 654: C.6.3 Acsi Services Conformance Statement

    PUBLISHER SERVER (CLAUSE 7) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 8) Associate Abort Release LOGICAL DEVICE (CLAUSE 9) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 10) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 11) GetDataValues SetDataValues GetDataDirectory GetDataDefinition C-24 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 655

    LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 18, ANNEX C) GOOSE-CONTROL-BLOCK (CLAUSE 18) SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK (ANNEX C) SendGSSEMessage GetReference GetGSSEElementNumber GetGsCBValues GE Multilin C70 Capacitor Bank Protection and Control System C-25...

  • Page 656

    (SendGOOSEMessage or SendGSSEMessage) NOTE c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) C-26 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 657: C.7.1 Logical Nodes Table

    GLOG: Generic log GSAL: Generic security application I: LOGICAL NODES FOR INTERFACING AND ARCHIVING IARC: Archiving IHMI: Human machine interface ISAF: Safety alarm function ITCI: Telecontrol interface ITMI: Telemonitoring interface GE Multilin C70 Capacitor Bank Protection and Control System C-27...

  • Page 658

    PSCH: Protection scheme PSDE: Sensitive directional earth fault PTEF: Transient earth fault PTOC: Time overcurrent PTOF: Overfrequency PTOV: Overvoltage PTRC: Protection trip conditioning PTTR: Thermal overload PTUC: Undercurrent PTUF: Underfrequency PTUV: Undervoltage C-28 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 659

    T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TANG: Angle TAXD: Axial displacement TCTR: Current transformer TDST: Distance TFLW: Liquid flow TFRQ: Frequency TGSN: Generic sensor THUM: Humidity TLVL: Media level TMGF: Magnetic field TMVM: Movement sensor GE Multilin C70 Capacitor Bank Protection and Control System C-29...

  • Page 660

    ZMOT: Motor ZREA: Reactor ZRES: Resistor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZSCR: Semi-conductor controlled rectifier ZSMC: Synchronous machine ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component C-30 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 661: D.1.1 Overview

    Xt = (8191/Xmax) * X - 4096 a = 2 * 4096/Xmax b = -4096 To calculate Xmax, one needs to know the rated value for the specific type of measurand. Xmax = 2.4 * Xrated GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 662: D.1.3 Interoperability Document

    Status indications in monitor direction INF Semantics  <16> Auto-recloser active  <17> Teleprotection active  <18> Protection active  <19> LED reset  <20> Monitor direction blocked  <21> Test mode C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 663

     <68> General trip  <69> Trip L  <70> Trip L  <71> Trip L  <72> Trip I>> (back-up operation)  <73> Fault location X in ohms  <74> Fault forward/line GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 664

     <244> Read value or attribute of a single entry  <245> End of general interrogation of generic data  <249> Write entry with confirmation  <250> Write entry with execution C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 665

     Private data Miscellaneous MEASURAND MAX MVAL = TIMES RATED VALUE Current L   Current L   Current L   Voltage L   Voltage L   GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 666

    APPENDIX D MEASURAND MAX MVAL = TIMES RATED VALUE Voltage L   Active power P   Reactive power Q   Frequency f   Voltage L   C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 667: E.1.1 Interoperability Document

    Not Present (Balanced Transmission Only)   Unbalanced Transmission One Octet  Two Octets  Structured  Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 668

     <18> := Packed start events of protection equipment with time tag M_EP_TB_1  <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1  <20> := Packed single-point information with status change detection M_SP_NA_1 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 669

    C_CS_NA_1  <104> := Test command C_TS_NA_1  <105> := Reset process command C_RP_NA_1  <106> := Delay acquisition command C_CD_NA_1  <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 670

    •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 671

    M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 672

    F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization:  Remote initialization Cyclic Data Transmission:  Cyclic data transmission Read Procedure:  Read procedure C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 673

     Mode B: Local freeze with counter interrogation  Mode C: Freeze and transmit by counter-interrogation commands  Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously  Counter read  Counter freeze without reset GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 674

    Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 675: E.1.2 Point List

    The IEC 60870-5-104 data points are configured through the    SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. See the Communications section of chapter 5 for details. IEC104 POINT LISTS GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 676

    E.1 OVERVIEW APPENDIX E E-10 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 677: F.1.1 Dnp V3.00 Device Profile

    Maximum Data Link Re-tries: Maximum Application Layer Re-tries:  None  None  Fixed at 3  Configurable  Configurable Requires Data Link Layer Confirmation:  Never  Always  Sometimes  Configurable GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 678

    FlexLogic. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 679

     16 Bits (Counter 8) Default Variation: 1  32 Bits (Counters 0 to 7, 9)  Point-by-point list attached  Other Value: _____  Point-by-point list attached Sends Multi-Fragment Responses:  Yes  No GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 680: F.1.2 Implementation Table

    17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the C70 is not restarted, but the DNP process is restarted. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 681

    17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the C70 is not restarted, but the DNP process is restarted. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 682

    17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the C70 is not restarted, but the DNP process is restarted. C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 683

    17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the C70 is not restarted, but the DNP process is restarted. GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 684: F.2.1 Binary Input Points

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 685: F.2.2 Binary And Control Relay Output

    Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 686: F.2.3 Counters

    Events Since Last Clear A counter freeze command has no meaning for counters 8 and 9. C70 Digital Counter values are represented as 32-bit integers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values.

  • Page 687: F.2.4 Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin C70 Capacitor Bank Protection and Control System F-11...

  • Page 688

    F.2 DNP POINT LISTS APPENDIX F F-12 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 689: G.1.1 Radius Server Configuration

    UR device for successful authentication, and the shortname is a short, optional alias that can be used in place of the IP address. client 10.0.0.2/24 { secret = testing123 shortname = private-network-1 In the <Path_to_Radius>\etc\raddb folder, create a file called dictionary.ge and add the following content. # ########################################################## GE VSAs ############################################################ VENDOR...

  • Page 690

    Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf file. Verify operation. Log in to the UR software as follows. In the login window, select Server as the Authentication Type, enter the user name entered (for example user name Tester and password "testpw").

  • Page 691: H.1.1 Revision History

    General revision, including updated branding from GE Digital Energy to GE Grid Solutions Delete Deleted EAC logo from title page and deleted EAC certification from Approvals specifications because document not translated into Russian Table H–3: MAJOR UPDATES FOR C70 MANUAL REVISION AA3 (Sheet 1 of 2) PAGE PAGE CHANGE...

  • Page 692

    H.1 CHANGE NOTES APPENDIX H Table H–3: MAJOR UPDATES FOR C70 MANUAL REVISION AA3 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (AA2) (AA3) 5-120 5-120 Update Updated FlexLogic operands table Update Updated FlexAnalog and FlexInteger tables Update Updated Modbus memory map and F codes Table H–4: MAJOR UPDATES FOR C70 MANUAL REVISION AA2...

  • Page 693

    Minor changes throughout document Delete Deleted CPU options U and V Update Updated Figure 1-1 Rear Nameplate Update Updated Figure 3-10 Rear Terminal View Table H–9: MAJOR UPDATES FOR C70 MANUAL REVISION Y1 (Sheet 1 of 2) PAGE PAGE CHANGE DESCRIPTION (X2) (Y1)

  • Page 694

    H.1 CHANGE NOTES APPENDIX H Table H–9: MAJOR UPDATES FOR C70 MANUAL REVISION Y1 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (X2) (Y1) Update Update Actual Values main menu to include Real Time Clock Synchronization submenu Added new section for Real Time Clock synchronizing consisting of the menu of settings and the...

  • Page 695: H.2.1 Standard Abbreviations

    F ..... Field MTA ....Maximum Torque Angle FAIL....Failure MTR ....Motor FD ....Fault Detector MVA ....MegaVolt-Ampere (total 3-phase) FDH....Fault Detector high-set MVA_A....MegaVolt-Ampere (phase A) FDL ....Fault Detector low-set GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 696

    RST ....Reset X ....Reactance RSTR ..... Restrained XDUCER..Transducer RTD ....Resistance Temperature Detector XFMR..... Transformer RTU ....Remote Terminal Unit RX (Rx) ..Receive, Receiver Z..... Impedance, Zone C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 697: H.3.1 Ge Multilin Warranty

    H.3.1 GE MULTILIN WARRANTY For products shipped as of 1 October 2013, GE Grid Solutions warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the GE Grid Solutions Terms and Conditions at https://www.gegridsolutions.com/multilin/warranty.htm...

  • Page 698

    H.3 WARRANTY APPENDIX H C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 699

    ............8-1 CLOCK BANKS ............. 5-6, 5-98, 5-99 setting date and time ............7-6 BATTERY settings ................. 5-64 disposal ................ 10-5 COMMANDS MENU ............7-1 failure ................7-11 replace ................10-3 GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 700

    DIRECT INPUTS and DIRECT OUTPUTS CURRENT METERING application example ........... 5-257, 5-258 actual values ..............6-14 configuration examples ......5-89, 5-91, 5-94, 5-95 specifications ..............2-21 settings ..........5-89, 5-94, 5-95, 5-256 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 701

    Modbus registers ..........B-47, B-49 IEC curves ..............5-154 pickup ................. 5-138 IEEE curves ..............5-153 scheme logic ............... 5-137 EQUIPMENT MISMATCH ERROR ........7-9 settings ..........5-136, 5-137, 5-140 specifications ..............2-20 GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 702

    RS485 ................3-24 Modbus registers ............B-39 settings ................5-96 settings ............... 5-178 INSTANTANEOUS OVERCURRENT specifications..............2-17 see PHASE, GROUND, and NEUTRAL IOC entries GROUP 1 SWITCH AFTER POWERUP ......5-142 INTER-RELAY COMMUNICATIONS ........2-25 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 703

    ............... 5-192 voltage ................2-21 specifications ..............2-19 METERING CONVENTIONS ..........6-12 NEGATIVE SEQUENCE TOC FlexLogic operands ............5-124 logic ................5-181 Modbus registers ............B-40 settings ............... 5-181 specifications ..............2-18 GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 704

    ORDERING ..........2-8, 2-9, 2-10, 2-11 see entry for ENERVISTA UR SETUP OSCILLATORY TRANSIENT TESTING ......2-27 PERMISSIVE FUNCTIONS ..........5-188 PER-UNIT QUANTITY ............5-4 PHASE ANGLE METERING ..........6-12 PHASE CURRENT METERING .........6-14 C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 705

    PRODUCT SETUP ............ 5-8, 5-18 RMS CURRENT ............... 2-21 PRODUCTION TESTS ............. 2-27 RMS VOLTAGE ..............2-21 PROTECTION ELEMENTS ..........5-4 RS232 configuration ..............1-9 specifications ..............2-25 wiring ................3-22 GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 706

    SIGNAL LOSS DETECTION FOR FIBER ......5-31 THERMAL OVERLOAD PROTECTION SIGNAL SOURCES Modbus registers ............B-43 description............... 5-5 settings ................ 5-242 metering ................ 6-14 specifications ..............2-20 settings ............... 5-101 TIME ................. 7-6 viii C70 Capacitor Bank Protection and Control System GE Multilin...

  • Page 707

    ................ 5-88 VTFF invoking and scrolling ............ 5-86 FlexLogic operands ............5-126 Modbus registers ..........B-29, B-34 see VT FUSE FAILURE settings ..............5-86, 5-88 specifications ..............2-21 WARNINGS ................ 1-1 GE Multilin C70 Capacitor Bank Protection and Control System...

  • Page 708

    WARRANTY ..............H-7 WITHDRAWAL FROM OPERATION ........10-8 WEB SERVER PROTOCOL ..........5-56 WEBSITE ................1-2 WIRE SIZE CT/VT ................3-10 G.703 interface .............. 3-28 ZERO SEQUENCE CORE BALANCE .........3-11 RS422 interface ............. 3-31 C70 Capacitor Bank Protection and Control System GE Multilin...

Comments to this Manuals

Symbols: 0
Latest comments: