GE B30 Communications Manual page 111

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
66E7
Reserved (4 items)
Generator Unbalance (Read/Write Grouped Setting)
G30, G60
66F0
Generator Unbalance Function
"
66F1
Generator Unbalance Source
"
66F2
Generator Unbalance Inom (rated full load
current of the machine)
"
66F3
Generator Unbalance Stage 1 Pickup
"
66F4
Generator Unbalance Stage 1 K value
"
66F5
Generator Unbalance Stage 1 Tmin
"
66F6
Generator Unbalance Stage 1 Tmax
"
66F7
Generator Unbalance Stage 1 K Reset
"
66F8
Generator Unbalance Stage 2 Pickup
"
66F9
Generator Unbalance Stage 2 Pickup Delay 0 to 1000
"
66FA
Generator Unbalance Block
"
66FC
Generator Unbalance Target
"
66FD
Generator Unbalance Events
"
66FE
Reserved (3 items)
Stator Ground Source (Read/Write Grouped Setting)
G30, G60
670A
Stator Ground Source
Subharmonic Stator Ground (Read/Write Grouped Setting)
G60
6710
Subharmonic Stator Ground Function
"
6711
Subharmonic Stator Ground Stage 1 Pickup 1 to 20
"
6712
Subharmonic Stator Ground Stage 1 Pickup
Delay
"
6713
Subharmonic Stator Ground Stage 2 Pickup 1 to 20
"
6714
Subharmonic Stator Ground Stage 2 Pickup
Delay
"
6715
Subharmonic CT Angle Compensation
"
6718
Subharmonic Stator Ground OC Pickup
"
6719
Subharmonic Stator Ground OC Delay
"
671A
Subharmonic Stator Ground Volt Supv
"
671B
Subharmonic Stator Ground Curr Supv
"
671C
Subharmonic Stator Ground Block
"
671E
Subharmonic Stator Ground Events
"
671F
Subharmonic Stator Ground Target
Stator Ground (Read/Write Grouped Setting)
G30, G60
6720
Stator Ground Function
"
6721
Stator Ground Stage 1 Pickup
"
6722
Stator Ground Stage 1 Pickup Delay
"
6723
Stator Ground Stage 1 Supv
"
6724
Stator Ground Stage 2 Pickup
"
6725
Stator Ground Stage 2 Pickup Delay
"
6726
Stator Ground Stage 2 Supv
"
6727
Stator Ground Block
"
6729
Stator Ground Target
"
672A
Stator Ground Event
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 65535
---
1
0 to 1
---
1
0 to 5
---
1
0 to 1.25
pu
0.001 F001
0 to 100
%
0.01
0 to 100
---
0.01
0 to 50
s
0.001 F001
0 to 1000
s
0.1
0 to 1000
s
0.1
0 to 100
%
0.01
s
0.1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 65535
---
1
0 to 5
---
1
0 to 1
---
1
kOhm
1
0.1 to 600
s
0.1
kOhm
1
0.1 to 600
s
0.1
-30 to 30
degrees 0.1
0.001 to 1
pu
0.001 F001
0.1 to 600
s
0.01
0 to 0.1
pu
0.001 F001
0 to 0.1
pu
0.001 F001
0 to 4294967295
---
---
0 to 1
---
1
0 to 2
---
1
0 to 1
---
1
0 to 0.9
pu
0.001 F001
0 to 600
s
0.01
0.001 to 0.1
pu
0.000
1
0 to 0.9
pu
0.001 F001
0 to 600
s
0.01
0.001 to 0.1
pu
0.000
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
MEMORY MAP
Format
Default
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
800
F001
800
F001
100
250
F001
6000
F001
2400
F001
300
F001
50
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F167
0 (SRC 1)
F102
0 (Disabled)
F001
10
F001
100
F001
3
F001
10
F002
0
10
F001
100
0
0
F300
0
F102
0 (Disabled)
F109
0 (Self-reset)
F102
0 (Disabled)
150
F001
100
F001
57
150
F001
0
F001
45
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
2-91
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents