GE B30 Communications Manual page 387

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: LosLifSPTR1
data obj. data attribute
Type
instMag.f
FLOAT32
mag
Analogue Value MX
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32
zeroDb
INT32
LosLife
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
Analogue Value MX
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32
zeroDb
INT32
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.3.30 User-programmable fault report (UFlt)
This element is instantiated in the following products: B30 B90 C70 G30 G60 M60 N60 T35 T60.
Table 3-167: User-programmable fault report data objects
LNName: UFltRFLO#
data obj. data attribute
Type
Mod
INC
stVal
ENUMERATED
ctlModel
CtlModels
Health
INS
stVal
ENUMERATED
FltZ
CMV
cVal
Vector
cVal.mag.f
FLOAT32
cVal.ang.f
FLOAT32
FltDiskm
MV
mag
Analogue Value MX
mag.f
FLOAT32
InRef1
ORG
GEORG
setSrcRef
ObjectReference SP
VISIBLE
STRING255
setSrcCB
ObjectReference SP
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Ctrl
UR element: Loss of Life Function
FC UR Name
DAILY RATE LOL
instMag.f on deadband
exception
CF
CF
LosLifSPTR1.LosLifeRte.db
CF
MX
XFMR LIFE LOST
instMag.f on deadband
exception
CF
CF
LosLifSPTR1.LosLife.db
CF
LOSS OF LIFE BLOCK for group γ.reference to the data attribute to input
LDevice inst: ctrl
UR element: USER PROGRAMMABLE FAULT REPORT # settings
FC UR Name
ST
CF
ST
LPHD1.PhyHealth.stVal
MX
PRE-FAULT # TRIGGER.
SP
Reference to the ultimate source
of value selected by setting PRE-
FAULT # TRIGGER.
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
4, the code for second
0 is multiplier for 1
0
XFMR LIFE LOST actual Values.
4, the code for second
0 is multiplier for 1
0
LOSS OF LIFE BLOCK for setting group γ. R
source GoCB of input if via GOOSE
Description
This logical node's mode
1 (on)
0 (status only)
This logical node's health
Mandatory data attribute which in this
case is fixed at zero
0
0
Mandatory data object which in this case
is fixed at zero
0
PRE-FAULT # TRIGGER.
reference to the data attribute to input
source GoCB of input if via GOOSE
R/W/C
R
R
R
R
R
R
R/W/C
R
R
R
R
3
R
R
R
R
R
R/W/C
R
R/C
R/C
R/W/C
R/Ctrl
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R/C
3-149

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents