GE B30 Communications Manual page 282

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Table 3-28: B90 undervoltage data objects
LNName: B_UvPTUV#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
BlkRefγ
setSrcRef
3
setSrcCB
3.5.2.11 Breaker failure (BkrFa)
This element is instantiated in the following products: B30, C60, C70, D60, F60, G60, L30, L60, L90, M60, T60.
Table 3-29: Breaker failure data objects
LNName: BkrFaRBRF#
data obj. data attribute
InRefγ02
setSrcRef
setSrcCB
BlkRefγ
setSrcRef
setSrcCB
InRefγ03
setSrcRef
setSrcCB
InRefγ04
setSrcRef
setSrcCB
InRefγ05
setSrcRef
setSrcCB
InRefγ06
setSrcRef
setSrcCB
InRefγ07
setSrcRef
setSrcCB
InRefγ08
setSrcRef
setSrcCB
OpIn
general
3-44
LDevice inst: Prot
UR element: B90 Undervoltage element # function
Type
FC UR Name
ACD
BOOLEAN
ST
UNDERVOLTAGE # PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
UNDERVOLTAGE # OP
SPS
BOOLEAN
ST
UNDERVOLTAGE # DPO
ORG
ObjectReference SP
UNDERVOLTAGE # BLK for group
γ.
ObjectReference SP
LDevice inst: Prot
UR element: Breaker Control element #
Type
FC UR Name
ORG
ObjectReference SP
3-POLE INITIATE input
ObjectReference SP
ORG
ObjectReference SP
BF# BLOCK.
ObjectReference SP
ORG
ObjectReference SP
BF# BKR POS1 φA/3P.
ObjectReference SP
ORG
ObjectReference SP
BF# BKR POS2 φA/3P.
ObjectReference SP
ORG
ObjectReference SP
BF# BKR POS1 φB.
ObjectReference SP
ORG
ObjectReference SP
BF# BKR POS1 0C.
ObjectReference SP
ORG
ObjectReference SP
BF# BKR POS2 φB.
ObjectReference SP
ORG
ObjectReference SP
BF# BKR POS2 φC.
ObjectReference SP
ACT
BOOLEAN
ST
re-trip operand BKR FAIL #
RETRIP
CHAPTER 3: IEC 61850 COMMUNICATION
Description
UNDERVOLTAGE # PKP operands
0, the code for unknown. It is unknown as
the element is non-directional
UNDERVOLTAGE # OP operand
UNDERVOLTAGE # DPO operand, which is
the inverse of UNDERVOLTAGE PKP
UNDERVOLTAGE # BLK setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
BF# 3-POLE INITIATE setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BLOCK setting for setting group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS1 φA/3P setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS2 φA/3P setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS1 φB setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS1 φC setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS2 φB setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BKR POS2 φC setting for setting
group γ
reference to the data attribute to input
source GoCB of input if via GOOSE
BKR FAIL # RETRIP operands
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R

Hide quick links: