MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: ACsrcMMXU#
data obj. data attribute
mag
mag.f
units
units.SIUnit
units.multiplier
db
zeroDb
TotPF
instMag
instMag.f
Mag
3
mag.f
units
units.SIUnit
units.multiplier
db
zeroDb
PFSign
setVal
Hz
instMag
instMag.f
mag
mag.f
units
units.SIUnit
units.multiplier
db
zeroDb
PPV
phsAB
phsAB.instCVal
phsAB.instCVal
.mag.f
phsAB.instCVal
.ang.f
phsAB.cVal
phsAB.cVal.mag.f FLOAT32
phsAB.cVal.ang.f FLOAT32
phsAB.units
phsAB.units
.SIUnit
phsAB.units
.multiplier
phsAB.db
phsAB.dbAng
phsAB.zeroDb
phsBC
phsBC.instCVal
3-174
LDevice inst: Meter
UR element: AC Source #
Type
FC UR Name
AnalogueValue
MX
FLOAT32
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
MMXU# TotVA DEADBAND
INT32U
CF
MV
AnalogueValue
MX
FLOAT32
SRC # Three Phase Power Factor
AnalogueValue
MX
FLOAT32
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
MMXU# TotPF DEADBAND
INT32U
CF
ENG
ENUMERATED
SP
MV
AnalogueValue
MX
FLOAT32
SRC # Frequency
AnalogueValue
MX
FLOAT32
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
MMXU# Hz DEADBAND
INT32U
CF
DEL
CMV
Vector
MX
FLOAT32
SRC # Phase AB Voltage
Magnitude
FLOAT32
SRC # Phase AB Voltage Angle
Vector
MX
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
MMXU# PPV.phsAB.db
INT32U
CF
MMXU# PPV.phsAB.dbAng
INT32U
CF
CMV
Vector
MX
CHAPTER 3: IEC 61850 COMMUNICATION
Description
instMag.f deadbanded
61, the code for primary volt amperes (VA)R
0, the code for a multiplier of 1
power cut-off level.
SRC # Three Phase Power Factor,
dimensionless
instMag.f deadbanded
65, the code for power factor
(dimensionless)
0, the code for a multiplier of 1
0
Sign convention for power factor (PF) is
fixed at Lead/Lag (usually named IEEE)
2, the code for Lead/Lag (usually named
IEEE, Enumeration name is "EEI" per
tissues standard )
SRC # Frequency, in Hz
instMag.f deadbanded
33, the code for hertz (1/s)
0, the code for a multiplier of 1
0
SRC # Phase-to-phase Voltage phasors,
in primary volts
UR range -180...+180 converted to 0...360 R
instCVal.mag.f deadbanded
instCVal.ang.f deadbanded
29, the code for primary volts (W/A)
0, the code for a multiplier of 1
voltage cut-off level.
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
R

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents