MEMORY MAP
Products
Address Register name
"
6958
Motor Learned Data (Read/Write Setting)
M60
6960
"
6961
"
6962
Motor Learned Data Actual Values (Read Only)
2
M60
6963
"
6964
"
6966
"
6967
"
6968
"
6969
"
696A
"
696C
RTD Inputs (Read/Write Setting) (48 Modules)
All except B90
6970
"
6971
"
6977
"
6978
"
6979
"
697A
"
697B
"
697C
"
697D
"
697E
"
697F
"
6980
"
6982
"
6983
"
6984
"
6998
"
69AC
"
69C0
"
69D4
"
69E8
"
69FC
"
6A10
"
6A24
"
6A38
"
6A4C
"
6A60
"
6A74
"
6A88
2-98
Reserved (8 items)
Motor Learned Data Starts to Learn
Motor Learned Data Calculation Period
Reserved
Motor Learned Data Records Number
Motor Learned Data Last Cleared Date
Motor Learned Data Last Acceleration
Time
Motor Learned Data Last Starting Current
Motor Learned Data Last Thermal Capacity
Used
Motor Learned Data Last Average Motor
Load
Motor Learned Data Last Run Time After
Start
Reserved
RTD Input 1 Function
RTD Input 1 ID
RTD Input 1 Type
RTD Input 1 Application
RTD Input 1 Alarm Temperature
RTD Input 1 Alarm Pickup Delay
RTD Input 1 Trip Temperature
RTD Input 1 Trip Pickup Delay
RTD Input 1 Trip Reset Delay
RTD Input 1 Trip Voting
RTD Input 1 Open
RTD Input 1 Block
RTD Input 1 Target
RTD Input 1 Events
...Repeated for RTD Input 2
...Repeated for RTD Input 3
...Repeated for RTD Input 4
...Repeated for RTD Input 5
...Repeated for RTD Input 6
...Repeated for RTD Input 7
...Repeated for RTD Input 8
...Repeated for RTD Input 9
...Repeated for RTD Input 10
...Repeated for RTD Input 11
...Repeated for RTD Input 12
...Repeated for RTD Input 13
...Repeated for RTD Input 14
...Repeated for RTD Input 15
CHAPTER 2: MODBUS COMMUNICATION
Range
Units
Step
---
---
---
1 to 5
---
1
1 to 90
minutes 1
---
---
---
0 to 250
---
1
0 to 4294967295
---
---
0 to 655.35
s
0.01
0 to 40
× FLA
0.01
0 to 65535
%
1
0 to 40
× FLA
0.01
0 to 4294967295
hr
1
---
---
---
0 to 1
---
1
---
---
---
0 to 3
---
1
0 to 5
---
1
1 to 249
°C
1
0 to 600
s
0.01
1 to 249
°C
1
0 to 600
s
0.01
0 to 600
s
0.01
0 to 48
---
1
0 to 2
---
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
UR FAMILY – COMMUNICATIONS GUIDE
Format
Default
F001
0
F001
1
F001
15
F001
0
F001
0
F050
0
F001
0
F001
0
F001
0
F001
0
F050
0
F001
0
F102
0 (Disabled)
F205
"RTD Ip 1"
F174
0 (100 ohm
Platinum)
F550
0 (None)
F001
130
F001
0
F001
130
F001
0
F001
0
F551
0
F552
0 (None)
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents