GE B30 Communications Manual page 443

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: SelSwGAPC#
data obj. data attribute
Type
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef6
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.6.16 Target resetting (TgtRs)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-218: Target resetting data objects
LNName: TgtRsIHMI1
data obj. data attribute
Type
Mod
INC
stVal
ENUMERATED
ctlModel
CtlModels
Health
INS
stVal
ENUMERATED
RsOp
SPS
stVal
BOOLEAN
RsOpRem
SPS
stVal
BOOLEAN
RsOpLoc
SPS
stVal
BOOLEAN
RsOpPB
SPS
stVal
BOOLEAN
InRef1
ORG
GEORG
setSrcRef
ObjectReference SP
VISIBLE
STRING255
setSrcCB
ObjectReference SP
VISIBLE
STRING255
cdcNs
VISIBLE
STRING255
cdcName
VISIBLE
STRING255
3.5.6.17 Time of day timer (TmDay)
This element is instantiated in the following products: C70.
Table 3-219: Time of day timer data objects
LNName: TmDayGAPC#
data obj. data attribute
Type
Mod
INC
stVal
ENUMERATED
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Gen
UR element: Selector Switch element #
FC UR Name
SELECTOR # 3BIT A2 setting
SELECTOR #3BIT ACK setting
LDevice inst: Gen
UR element: Target Resetting
FC UR Name
ST
CF
ST
LPHD1.PhyHealth.stVal
ST
RESET OP
ST
RESET OP (COMMS)
ST
RESET OP (OPERAND)
ST
RESET OP (PUSHBUTTON)
RESET OPERAND
SP
Reference to the ultimate source
of value selected by setting
RESET OPERAND
SP
If reference is external to this
IED, mapped to the source's
GOOSE control block, else empty
string
EX
Name of the GE Multilin
namespace at the time of this
firmware release
EX
GEORG
LDevice inst: Gen
UR element: TIME OF DAY TIMER #
FC UR Name
ST
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
reference to the data attribute to input
source GoCB of input if via GOOSE
SELECTOR # 3BIT ACK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
This logical node's mode
1 (on)
0 (status only)
This logical node's health
RESET OP operand value
RESET OP (COMMS) operand value
RESET OP (OPERAND) operand value
RESET OP (PUSHBUTTON) operand value R
RESET OPERAND setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
This logical node's mode
1 (on)
R/W/C
R/C
R/C
R
R/C
R/C
3
R/W/C
R/Ctrl
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R/C
R/C
R
R
R/W/C
R/Ctrl
R
3-205