CHAPTER 3: IEC 61850 COMMUNICATION
LNName: PctDifPDIF1
data obj. data attribute
Type
general
BOOLEAN
dirGeneral
ENUMERATED
phsA
BOOLEAN
dirPhsA
ENUMERATED
phsB
BOOLEAN
dirPhsB
ENUMERATED
phsC
BOOLEAN
dirPhsC
ENUMERATED
RefWindin
INS
g
stVal
INT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
DifAClc
WYE
phsθ
CMV
phsθ.instCVal
Vector
phsθ.instCVal.mag
FLOAT32
.f
phsθ.instCVal.ang
FLOAT32
.f
phsθ.cVal
Vector
phsθ.cVal.mag.f
FLOAT32
phsθ.cVal.ang.f
FLOAT32
phsθ.units
Unit
phsθ.units.SIUnit ENUMERATED
phsθ.units
ENUMERATED
.multiplier
phsθ.db
INT32U
phsθ.dbAng
INT32U
phsθ.zeroDb
INT32U
angRef
ENUMERATED
DifA2ndH
WYE
phsθ
CMV
phsθ.instCVal
Vector
phsθ.instCVal.mag
FLOAT32
.f
phsθ.instCVal.ang
FLOAT32
.f
phsθ.cVal
Vector
phsθ.cVal.mag.f
FLOAT32
phsθ.cVal.ang.f
FLOAT32
phsθ.units
Unit
phsθ.units.SIUnit ENUMERATED
phsθ.units
ENUMERATED
.multiplier
phsθ.db
INT32U
phsθ.dbAng
INT32U
phsθ.zeroDb
INT32U
angRef
ENUMERATED
DifA5thH
WYE
phsθ
CMV
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Transformer Percent Differential function
FC UR Name
ST
logical OR of phsA, phsB & phsB
ST
ST
XFMR PCNT DIFF PKP A
ST
ST
XFMR PCNT DIFF PKP B
ST
ST
XFMR PCNT DIFF PKP C
ST
ST
REFERENCE WINDING
CF
MX
DIFF PHASOR Iθd magnitude, in
pu
DIFF PHASOR
MX
DIFF PHASOR Iθd magnitude, in
pu, with deadband
DIFF PHASOR
CF
CF
PctDifPDIF1.DifAClc.phsθ.db
CF
PctDifPDIF1.DifAClc.phsθ.dbAng
CF
CF
MX
DIFF 2ND HARM Iθd magnitude,
in %
DIFF 2ND HA
MX
DIFF 2ND HARM Iθd magnitude,
in %, with deadband
DIFF 2ND HA
CF
CF
PctDifPDIF1.DifA2ndH.phsθ.db
CF
PctDifPDIF1.DifA2ndH.phsθ.dbAn
g
CF
CF
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
0
0
0
0
Number of winding used as the reference
winding for ratio compensation
1, the code for dimensionless
0, the code for a multiplier of 1
Phase differential currents
UR range -180...+180 converted to 0...360 R
UR range -180...+180 converted to 0...360 R
1, the code for dimensionless
-2, the code for a multiplier of Centi
4
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
Phase differential currents
UR range -180...+180 converted to 0...360 R
UR range -180...+180 converted to 0...360 R
1, the code for dimensionless
0, the code for a multiplier of 1
0
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
Phase differential currents
R/W/C
R
R
R
R
R
R
R
R
R
R
R
3
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
R
R
3-109