GE B30 Communications Manual page 327

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-93: Phase comparison advanced fault detector rate of change of negative sequence current (for FDH) data
objects
LNName: PhCmp4FXOT1
data obj. data attribute
Type
InRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
StrVal
ASG
setMag
AnalogueValue
setMag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
minVal
AnalogueValue
minVal.f
FLOAT32
maxVal
AnalogueValue
maxVal.f
FLOAT32
stepSize
AnalogueValue
stepSize.f
FLOAT32
Op
ACT
general
BOOLEAN
Table 3-94: Phase comparison advanced fault detector positive sequence current (excluding FDH) data objects
LNName: PhCmp1PIOC1
data obj. data attribute
Type
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
Op
ACT
general
BOOLEAN
Table 3-95: Phase comparison advanced fault detector positive sequence current (for FDH) data objects
LNName: PhCmp2PIOC1
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
Table 3-96: Phase comparison advanced fault detector negative sequence current (excluding FDH) data objects
LNName: PhCmp3PIOC1
data obj. data attribute
Type
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
Op
ACT
general
BOOLEAN
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: RATE OF CHANGE OF NEG SEQ CURRENT element specific to
FDH element as a part of Phase comparison function
FC UR Name
NEG SEQ FDH SUPV setting
SG
NEG SEQ di/dt FDH PICKUP
CF
CF
CF
CF
ST
87PC di2/dt FDH OP
LDevice inst: Prot
UR element: Positive Sequence Current element (except FDH element
specifics) as a part of Phase comparison function
FC UR Name
POS SEQ I_1 BLK setting
ST
87PC I_1 FDL OP
LDevice inst: Prot
UR element: Positive Sequence Current element specific to FDH element
as a part of Phase comparison function
FC UR Name
ST
87PC I_1 FDH OP
LDevice inst: Prot
UR element: Negative Sequence Current element (except FDH element
specifics) as a part of Phase comparison function
FC UR Name
NEG SEQ I_2 BLK setting
ST
87PC I_2 FDL OP
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
NEG SEQ FDH SUPV setting of setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
NEG SEQ di/dt FDH PICKUP setting
1 is code for dimensionless
0, the code for a multiplier of 1
0.01
5.00
0.01
87PC di2/dt FDH OP operand
Description
POS SEQ I_1 BLK setting of setting group
γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
87PC I_1 FDL OP operand
Description
87PC I_1 FDH OP operand
Description
NEG SEQ I_2 BLK setting of setting group
γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
87PC I_2 FDL OP operand
R/W/C
R
R/C
R/C
R
R
R
R
R
3
R
R
R
R
R
R
R
R
R
R/W/C
R
R/C
R/C
R
R
R/W/C
R
R
R/W/C
R
R/C
R/C
R
R
3-89

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents