GE B30 Communications Manual page 487

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
G2 IMPLEMENTATION MODEL FOR GOOSE CONFIGURATION VIA SCL
<Address>
<P type="MAC-Address">01-0C-CD-01-00-01</P>
<P type="APPID">3001</P>
<P type="VLAN-ID">010</P>
<P type="VLAN-PRIORITY">7</P>
</Address>
<MinTime>5</MinTime>
<MaxTime>5000</MaxTime>
</GSE>
</ConnectedAP>
</SubNetwork>
</Communication>
<IED name="E1Q1BP1">
<Services>
<GSESettings appID="Conf" cbName="Conf" datSet="Conf"/>
3
<GOOSE max="1"/>
</Services>
<AccessPoint name="S1">
<Server>
<Authentication none="true"/>
<LDevice inst="LD1">
<LN0 inst="" lnClass="LLN0" lnType="LN0">
<DataSet name="GOOSE1DS">
<FCDA ldInst="LD1" prefix="" lnClass="PIOC" lnInst="1" doName="Op" fc="ST" daName="general"/>
</DataSet>
<GSEControl name="GoCB1" datSet="GOOSE1DS" appID="E1Q1BP1LD1_GOOSE1"/>
</LN0>
<LN lnClass="LPHD" inst="1" lnType="LPHD" />
<LN lnClass="PIOC" inst="1" lnType="PIOC">
<DOI name="Op" desc="Instantaneous Overcurrent Operated" />
</LN>
<LN lnClass="GGIO" prefix="ConOut" lnType="GGIO"
inst="1">
<DOI name="InRef1" desc="Contact Output Control">
<DAI name="setSrcRef"><Val></Val></DAI>
<DAI name="setSrcCB"><Val></Val></DAI>
</DOI>
</LN>
<LN prefix="" lnClass="LGOS" inst="1" lnType="LGOS">
<DOI name="GoCBRef">
<DAI name="setSrcRef"><Val></Val></DAI>
</DOI>
</LN>
</LDevice>
</Server>
</AccessPoint>
</IED>
<DataTypeTemplates>
...
In this simple case, the rest of this file is the same as the ICD file.
CID file for E1Q2BP1 (Subscribing IED)
<?xml version="1.0" encoding="UTF-8"?>
UR FAMILY – COMMUNICATIONS GUIDE
3-249

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents