CHAPTER 3: IEC 61850 COMMUNICATION
LNName: CPhOvPTOV#
data obj. data attribute
Type
phsC.cVal
Vector
phsC.cVal.mag.f
FLOAT32
phsC.units
Unit
phsC.units.SIUnit ENUMERATED
phsC.units
ENUMERATED
.multiplier
phsC.db
INT32U
phsC.zeroDb
INT32U
Table 3-33: Capacitor bank phase overvoltage stage data objects
LNName: CPhOv$PTOV#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
phsA
BOOLEAN
dirPhsA
ENUMERATED
phsB
BOOLEAN
dirPhsB
ENUMERATED
phsC
BOOLEAN
dirPhsC
ENUMERATED
Op
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
3.5.2.15 Compensated overvoltage (CompOv)
This element is instantiated in the following products: D60, L60, L90.
Table 3-34: Compensated overvoltage function data objects
LNName: CmpOv0PTOV1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: BANK OVERVOLTAGE element #
FC UR Name
MX
CF
CF
CPhOvPTOV#.OpV.phsC.db
CF
(VOLTAGE CUT-OFF LEVEL) / 275 *
100 000
LDevice inst: Prot
UR element: BANK OVERVOLTAGE element # Stage $
FC UR Name
ST
Logical OR of data attributes
phsA, phsB and phsC
ST
ST
BANK OV # STG $A PKP
ST
ST
BANK OV # STG $B PKP
ST
ST
BANK OV # STG $C PKP
ST
ST
Logical OR of data attributes
phsA, phsB and phsC
ST
BANK OV # STG $A OP
ST
BANK OV # STG $B OP
ST
BANK OV # STG $C OP
LDevice inst: Prot
UR element: Compensated Overvoltage functions
FC UR Name
ST
COMP OV PKP
ST
ST
COMP OV OP
ST
COMP OV DPO
COMPENSATED OV BLK for
group γ.
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
instCVal.mag.f deadbanded
1, the code for dimensionless (per unit)
0, the code for a multiplier of 1
Description
BANK OV # STG $ PKP operands
(including individual three phases), which
indicates Op will operate when delay
expires.
0, the code for unknown.
0, the code for unknown.
0, the code for unknown.
0, the code for unknown.
BANK OV # STG $ OP per phase operands
(including individual three phases of each
stage)
Description
COMP OV PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
COMP OV OP operand
COMP OV DPO operand, which is the
inverse of COMP OV PKP
COMPENSATED OV BLK setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
R/W/C
R
R
R
R
R
R/W/C
R
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
3-49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents