CHAPTER 3: IEC 61850 COMMUNICATION
Data object
CDC
Semantics
name
SntpFail
SPS
SNTP server is not responding.
The SNTP FAILURE operand.
SPDTR
SPS
Motor switches from speed 2 to speed 1.
MOTOR SPD2 TR 2-1 OP operand.
Spt
MV
Set point value. The PID 1 Setpoint value.
Start
SPS
One-second pulse at set time of day timer # start time.
The TIME OF DAY 1 START operand.
Starting
SPS
Indicate the motor is starting.
The MOTOR STARTING operand.
StlGMP
SPS
Indicates status of IGMP connection for R-GOOSE multicast reception.
The R-RxGOOSE1 IGMP On operand.
Stop
SPS
One-second pulse at set time of day timer 1 stop time.
The TIME OF DAY 1 STOP operand.
StrAccTm1
MV
Indicates motor start acceleration time. START 1 ACCELERATION TIME in seconds. MAccTmPMSS
StrAlm
ACD
Indicates the detection of a fault or an unacceptable condition.
The RRTD RTD 1 ALARM PKP operand.
The RTD Ip 1 ALARM PKP operand.
The U/CURR ALARM PKP operand.
The UNDERPWR 1 ALARM PKP operand.
StrBia
ACD
B90 Start Biased indicates the detection of a fault or an unacceptable condition
by Biased Differential element
StrCls
SPS
Close start indicates the pickup of close command, and its operation is pending.
The AVR 1 CLOSE PKP operands.
StrEffA1
MV
Indicates motor start effective current.
START 1 EFFECTIVE CURRENT in x FLA.
StrHrLOTm
MV
Start/Hour Lockout Time in minutes
StrInd
SPS
An LED.
The LED PICKUP operand.
StrOpn
SPS
Open start indicates the pickup of open command, and its operation is pending.
AVR 1 OPEN PKP operands.
StrOutgoing
SPS
This Data Object indicates an unstable Power swing detection for outgoing Locus.
The POWER SWING OUTGOING operand.
StrPeak1
MV
Indicates motor start peak current.
START 1 PEAK CURRENT in x FLA.
StrPhs1
SPS
Indicates the detection of a fault or an unacceptable condition on a particular
phase-to-phase loop.
The PHS DIST Z1 PKP AB/BC/CA operand in Phase-To-Phase.
StrRec3p
SPS
Initiate a three-pole reclose.
The TRIP AR INIT 3-POLE operand.
StrTD1
INS
Represents UTC timestamp for motor acceleration Time/DATE in seconds elapsed
since 00:00:00, 1970/01/01.
The START 1 TIME/DATE actual value.
StrZ2GndDl
SPS
Start zone 2 ground timer.
The TRIP Z2GR TMR INIT operand.
StrZ2PhDl
SPS
Start zone 2 phase timer.
The TRIP Z2PH TMR INIT operand.
StubBusOp
SPS
The stub bus function is operated.
The STUB BUS OP operand, which becomes On when the Stub Bus function is
active.
SumHa3NVZroV MV
Sum of third harmonic neutral voltage and zero sequence voltage.
The STATOR GND 3RD HARM VN+V0 in volts.
SwFail
SPS
Autoreclose mode switching failed.
The AR MODE SWITCH FAIL operand.
SysExcp
SPS
System exception.
The SYSTEM EXCEPTION operand.
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Used in logical nodes...
LPHD
S2AcTmPMSS
PIDRegFPID
TmDayGAPC
MotThmPTTR
LGOS
TmDayGAPC
PRTDsSTMP, RRTDsSTMP,
UnCurPTUC, UnPwrPDUP
B_DifPDIF
AvrGAPC
MAccTmPMSS
StrRtePMRI
LEDsIHMI
AvrGAPC
PwrSwgRPSB
MAccTmPMSS
PhsDisPDIS
TrOutPTRC
MAccTmPMSS
TrOutPTRC
TrOutPTRC
LinDfPDIF
StatrPHIZ
Rec13pRREC
LPHD
3-221