CHAPTER 3: IEC 61850 COMMUNICATION
LNName: PhAUn$PTOC#
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.56 Phase directional (PhsDir)
This element is instantiated in the following products: B30, C70, D30, D60, F60, G30, G60, L30, L60, L90, M60, N60, T60.
Table 3-101: Phase directional data objects
LNName: PhsDirRDIR#
data obj. data attribute
Type
Dir
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
phsA
BOOLEAN
dirPhsA
ENUMERATED
phsB
BOOLEAN
dirPhsB
ENUMERATED
phsC
BOOLEAN
dirPhsC
ENUMERATED
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.57 Phase distance (PhsDis)
This element is instantiated in the following products: D30, D60, G60, L60, L90, T60.
Table 3-102: Phase distance data objects
LNName: PhsDisPDIS#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
StrPhsφ
SPS
stVal
BOOLEAN
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Phase Current Unbalance element # Stage $
FC UR Name
ST
Logical OR of data attributes
phsA, phsB, phsC
ST
CUR BAL # STG$A OP
ST
CUR BAL # STG$B OP
ST
CUR BAL # STG$C OP
CUR UNBL # BLK STG$ for group
γ.
LDevice inst: Prot
UR element: Phase Directional element # (ANSI 67P)
FC UR Name
ST
PH DIR # BLK
ST
ST
PH DIR # BLK A
ST
ST
PH DIR # BLK B
ST
ST
PH DIR # BLK C
ST
PHASE DIR # BLOCK for group γ. reference to the data attribute to input
LDevice inst: Prot
UR element: Phase Distance Z# settings
FC UR Name
ST
PH DIST Z# PKP
ST
ST
PHS DIST Z# OP
ST
PHS DIST Z# PKP θ
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
CUR BAL # OP operands (including
individual three phases of this stage).
CUR UNBL # BLK STG$ setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
PH DIR # BLK operand, which becomes
On when phase current is flowing in the
set direction
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
0, the code for unknown
0, the code for unknown
0, the code for unknown
PHASE DIR # BLOCK setting for setting
group γ.
source GoCB of input if via GOOSE
Description
PHS DIST Z# PKP operand in Phase-To-
Phase
1(Forward) if PHS DIST Z DIR value is
Forward, 2 (backward) if PHS DIST Z1 DIR
value is Reverse, and otherwise 0
(unknown).
PHS DIST Z# OP operand in Phase-To-
Phase
PHS DIST Z# PKP θ operand in Phase-To-
Phase
R/W/C
R
R
R
R
R
R
R/C
R/C
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
3-93