GE B30 Communications Manual page 104

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MEMORY MAP
Products
Address Register name
"
6335
"
6336
"
6337
"
6338
"
6339
2
"
633A
"
633B
"
633C
"
633D
"
633E
"
633F
"
6340
"
6341
"
6342
"
6343
"
6344
"
6345
"
6346
"
6348
"
6349
"
634A
"
6364
Capacitor Bank Overvoltage Actuals (Read Only) (3 Modules)
C70
6390
"
6391
"
6392
"
6393
"
6396
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 or 3 Modules)
C70, D30, D60,
63C0
F35, F60, L30,
L60, L90, T60
"
63C1
"
63C2
"
63C3
"
63C4
"
63C5
"
63C7
2-84
Bank Phase Overvoltage 1 Curve Time
Multiplier
Bank Phase Overvoltage 1 Stage 1A Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 2A Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 3A Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 4A Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 1B Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 2B Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 3B Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 4B Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 1C Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 2C Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 3C Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 4C Pickup 0.8 to 2
Bank Phase Overvoltage 1 Stage 1 Pickup
Delay
Bank Phase Overvoltage 1 Stage 2 Pickup
Delay
Bank Phase Overvoltage 1 Stage 3 Pickup
Delay
Bank Phase Overvoltage 1 Dropout Delay
Bank Phase Overvoltage 1 Block
Bank Phase Overvoltage 1 Target
Bank Phase Overvoltage 1 Events
...Repeated for Bank Phase Overvoltage 2
...Repeated for Bank Phase Overvoltage 3
Bank Overvoltage 1 Phase A Operate
Voltage
Bank Overvoltage 1 Phase B Operate
Voltage
Bank Overvoltage 1 Phase C Operate
Voltage
...Repeated for Bank Overvoltage 2
...Repeated for Bank Overvoltage 3
Negative Sequence Instantaneous OC 1
Function
Negative Sequence Instantaneous OC 1
Signal Source
Negative Sequence Instantaneous
Overcurrent 1 Pickup
Negative Sequence Instantaneous
Overcurrent 1 Delay
Negative Sequence Instantaneous OC 1
Reset Delay
Negative Sequence Instantaneous
Overcurrent 1 Block
Negative Sequence Instantaneous
Overcurrent 1 Target
CHAPTER 2: MODBUS COMMUNICATION
Range
Units
Step
1 to 10
---
0.01
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 600
s
0.01
0 to 600
s
0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 65.535
pu
0.001 F001
0 to 65.535
pu
0.001 F001
0 to 65.535
pu
0.001 F001
0 to 1
---
1
0 to 5
---
1
0.02 to 30
pu
0.001 F001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 4294967295
---
1
0 to 2
---
1
UR FAMILY – COMMUNICATIONS GUIDE
Format
Default
F001
100
1050
1100
1200
1050
1050
1100
1200
1050
1050
1100
1200
1050
F001
6000
F001
1000
F001
200
F001
25
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
0
0
0
F102
0 (Disabled)
F167
0 (SRC 1)
1000
F001
0
F001
0
F300
0
F109
0 (Self-reset)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents