CHAPTER 3: IEC 61850 COMMUNICATION
LNName: HThdMHAI#
data obj. data attribute
Type
phsθHar(n).units
Unit
phsθHar(n).units
ENUMERATED
.SIUnit
phsθHar(n).units
ENUMERATED
.multiplier
phsθHar(n).db
INT32U
phsθHar(n).zeroDb INT32U
numHar
INT16U
numCyc
INT16U
evalTm
INT16U
frequency
FLOAT32
rmsCyc
INT16U

3.5.6 General (Gen) logical device

The Ctrl logical device contains logical nodes that model UR FlexLogic, Virtual Outputs, non-volatile latches, FlexElements,
and recording (for example, oscillography) functions.
The Ctrl logical device is available when the Advanced IEC 61850 option is purchased with the UR device.
3.5.6.1 Logical node zero (LLN0)
LLN0 is instantiated in all UR family devices implementing the Gen logical device.
Table 3-203: LLN0 data objects
LNName: LLN0
data obj. data attribute
Type
Beh
ENS
stVal
ENUMERATED
stVal
ENUMERATED
Health
ENS
stVal
ENUMERATED
On
SPS
stVal
BOOLEAN
Off
SPS
stVal
BOOLEAN
Zero
MV
mag
AnalogueValue
mag.f
FLOAT32
Mod
ENC
ctlVal
ENUMERATED
stVal
ENUMERATED
ctlModel
CtlModels
sboTimeout
INT32U
sboClass
SboClasses
operTimeout
INT32U
GrRef
ORG
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Meter
UR element: Harmonics and THD metering
FC UR Name
CF
-2
CF
HThdMHAI#.HPhV.phsθHar(n).db
CF
CF
CF
CF
(1/ NOMINAL FREQUENCY) *
1000
CF
NOMINAL FREQUENCY
CF
LDevice inst: Gen
UR element: Nameplate information for the logical nodes
FC UR Name
ST
ST
LLN0.Beh.stVal of the Master
logical device
ST
LPHD1.PhyHealth.stVal
ST
ST
MX
ST
CF
LLN0.Mod.ctlModel
CF
CF
CF
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
1, the code for dimensionless
(percentage)
0
25
1
1
Description
This logical device's behavior
Only instantiated in the Master logical
device
Only instantiated in the Master logical
device
Only instantiated in the Master logical
device
Only instantiated in the Master logical
device
0.0
Only instantiated in the Master logical
device
2, the code for SBO control with normal
security according to IEC 61850-7-2.
30000
0 (operate-once)
0
Reference to root logical device
R/W/C
R
R
R
R/W/C
R
R
R
R
R
R
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R/Ctrl
R
R
R/C
R
R
R
R
3-193