MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: Bkr0XCBR#
data obj. data attribute
phsC
OpCls
general
BadSt1
stVal
ClsSt1
stVal
OpnSt1
stVal
Dsc
stVal
3
Alm
stVal
MnlOpn
stVal
MnlCls
stVal
AnyPoleOp
n
stVal
OnePoleOp
n
stVal
OutOfSrv
stVal
TagOn
stVal
TagOff
stVal
SbstCls
stVal
SbstOpn
stVal
BypsOn
stVal
BypsOff
stVal
RecBlk
stVal
RecEna
stVal
Pos
stVal
stSeld
pulseConfig
pulseConfig
.cmdQual
pulseConfig.onDur INT32U
pulseConfig
.offDur
3-154
LDevice inst: System
UR element: Breaker Control element #
Type
FC UR Name
BOOLEAN
ST
BREAKER # TRIP C
ACT
BOOLEAN
ST
BREAKER # ON CMD
SPS
BOOLEAN
ST
BREAKER # BAD STATUS
SPS
BOOLEAN
ST
BREAKER # CLOSED
SPS
BOOLEAN
ST
BREAKER # OPEN
SPS
BOOLEAN
ST
BREAKER # DISCREP
SPS
BOOLEAN
ST
BREAKER # TROUBLE
SPS
BOOLEAN
ST
BREAKER # MNL OPEN
SPS
BOOLEAN
ST
BREAKER # MNL CLS
SPS
BOOLEAN
ST
BREAKER # ANY P OPEN
SPS
BOOLEAN
ST
BREAKER # ONE P OPEN
SPS
BOOLEAN
ST
BREAKER # OOS
SPS
BOOLEAN
ST
BREAKER # TAG ON
SPS
BOOLEAN
ST
BREAKER # TAG OFF
SPS
BOOLEAN
ST
BREAKER # SUBD CLSD
SPS
BOOLEAN
ST
BREAKER # SUBD OPEN
SPS
BOOLEAN
ST
BREAKER # BYPASS ON
SPS
BOOLEAN
ST
BREAKER # BYPASS OFF
SPS
BOOLEAN
ST
BREAKER # BLK RCLS
SPS
BOOLEAN
ST
BREAKER # ENA RCLS
DPC
CODED ENUM
ST
BOOLEAN
ST
PulseConfig
CF
ENUMERATED
INT32U
CHAPTER 3: IEC 61850 COMMUNICATION
Description
BREAKER # ON CMD (close) operand
BREAKER # BAD STATUS operand
BREAKER # CLOSED operand
BREAKER # OPEN operand
BREAKER # DISCREP operand, which is
breaker pole discrepancy status
BREAKER # TROUBLE operand, which is
breaker pole discrepancy, bad-status, or
BREAKER # EXT ALARM
BREAKER # MNL OPEN operand
BREAKER # MNL CLS operand
BREAKER # ANY P OPEN operand
BREAKER # ONE P OPEN operand
BREAKER # OOS operand
BREAKER # TAG ON operand
BREAKER # TAG OFF operand
BREAKER # SUBD CLSD operand
BREAKER # SUBD OPEN operand
BREAKER # BYPASS ON operand
BREAKER # BYPASS OFF operand
BREAKER # BLK RCLS operand
BREAKER # ENA RCLS operand
Breaker position control and status
The controllable data status is "selected" R
0 (pulse)
2
0
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/Ctrl
R
R
R
R
R

Hide quick links: