CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
7A8D
...Repeated for Underfrequency 4
"
7A9C
...Repeated for Underfrequency 5
"
7AAB
...Repeated for Underfrequency 6
Thermal Model (Read/Write Grouped Setting)
M60
7AE0
Thermal Model Function
"
7AE1
Thermal Model Curve
"
7AE2
Thermal Model TD Multiplier
"
7AE3
Thermal Model Bias K Factor
"
7AE4
Thermal Model Time Constant Running
"
7AE5
Thermal Model Time Constant Stopped
"
7AE6
Thermal Model Hot Cold Ratio
"
7AE7
Thermal Model RTD Bias
"
7AE8
Thermal Model RTD Bias Minimum
"
7AE9
Thermal Model RTD Bias Center
"
7AEA
Thermal Model RTD Bias Maximum
"
7AEB
Thermal Model Start Inhibit Margin
"
7AEC
Thermal Model Block
"
7AEE
Thermal Model Events
"
7AEF
Thermal Model Target
"
7AF0
Thermal Model Curve Effect
"
7AF1
Speed 2 Thermal Model Curve
"
7AF2
Speed 2 Thermal Model TD Multiplier
"
7AF3
Reserved
"
7AF4
Thermal Model IEC Curve K Factor
"
7AF5
Thermal Model IEC Curve Time Constant
Voltage Dependent Overload (Read/Write Grouped Setting)
M60
7B00
Voltage Dependent Overload Function
"
7B01
Voltage Dependent Overload Minimum
Motor Volts
"
7B02
Voltage Dependent Overload Voltage Loss 0 to 4294967295
"
7B04
VD Overload Stall Current at Minimum Volts 1.5 to 20
"
7B05
VD Overload Safe Stall Time at Minimum
Volts
"
7B06
VD Overload Acceleration Intersect at
Minimum Volts
"
7B07
VD Overload Stall Current at 100% Voltage 1.5 to 20
"
7B08
VD Overload Safe Stall Time at 100%
Voltage
"
7B09
VD Overload Acceleration Intersect at
100% Voltage
"
7B0A
Speed 2 Voltage Dependent Overload
Function
"
7B0B
Speed 2 VD Overload Minimum Motor Volts 60 to 99
"
7B0C
Speed 2 Voltage Dependent Overload
Voltage Loss
"
7B0E
Speed 2 VD Overload Stall Current at
Minimum Volts
"
7B0F
Speed 2 VD Overload Safe Stall Time at
Minimum Volts
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
0 to 5
---
1
0 to 600
---
0.01
0 to 19
---
1
1 to 65000
min
1
1 to 65000
min
1
0.01 to 1
---
0.01
0 to 1
---
1
0 to 250
°C
1
0 to 250
°C
1
0 to 250
°C
1
0 to 25
%
1
0 to 4294967295
---
1
0 to 1
---
1
0 to 2
---
1
0 to 1
---
1
0 to 5
---
1
0 to 600
---
0.01
0 to 600
---
0.01
1 to 1.5
---
0.05
0 to 1000
min.
1
0 to 1
---
1
60 to 99
%
1
---
1
× FLA
0.01
0.1 to 1000
s
0.1
1.5 to 20
× FLA
0.01
× FLA
0.01
0.1 to 1000
s
0.1
1.5 to 20
× FLA
0.01
0 to 1
---
1
%
1
0 to 4294967295
---
1
× FLA
1.5 to 20
0.01
0.1 to 1000
s
0.1
MEMORY MAP
Format
Default
F102
0 (Disabled)
F099
0 (Motor)
F001
100
F001
0
F001
15
F001
30
F001
100
F102
0 (Disabled)
F001
40
F001
130
F001
155
F001
0
F300
0
F102
0 (Disabled)
F109
0 (Self-reset)
F096
0 (Cutoff)
F099
0 (Motor)
F001
100
F001
100
F001
110
F001
45
F102
0 (Disabled)
F001
80
F300
0
F001
450
F001
200
F001
400
F001
600
F001
100
F001
500
F102
0 (Disabled)
F001
80
F300
0
F001
450
F001
200