GE B30 Communications Manual page 315

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: NeAUnPTOC#
data obj. data attribute
Type
CompAop
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32
zeroDb
INT32
Table 3-72: Neutral current unbalance stage objects
LNName: NeAUn$PTOC#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.43 Neutral directional overcurrent (NeuDoc)
This element is instantiated in the following products: C70, D30, D60, F60, G30, G60, L30, L60, L90, M60, N60, T60.
Table 3-73: Neutral directional overcurrent data objects
LNName: NeuDocRDIR#
data obj. data attribute
Type
Dir
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
FwdOp
SPS
stVal
BOOLEAN
RvOp
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Neutral Current Unbalance element #
FC UR Name
MX
Comp Iop
MX
instMag.f deadbanded
exception
CF
CF
NeAUnPTOC#.CompAop.db
CF
LDevice inst: Prot
UR element: Neutral Current Unbalance element # Stage$
FC UR Name
ST
NTRL CUR # STG$ PKP
ST
ST
NTRL CUR # STG$ OP
NTRL CUR # BLK STG$ for group
γ (where $ refers to STAGE 1, 2, 3,
4)
LDevice inst: Prot
UR element: Neutral Directional Overcurrent element #
FC UR Name
ST
logical OR of operands NTRL DIR
OC# FWD and NTRL DIR OC#
REV
ST
ST
NTRL DIR OC# FWD
ST
NTRL DIR OC# REV
NEUTRAL DIR OC# BLOCK for
group γ.
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
Comp Iop in per unit
1, the code for dimensionless (per unit)
0, the code for a multiplier of 1
0
Description
NTRL CUR # STG$ PKP operands.
0, the code for unknown.
NTRL CUR # STG$ OP operands
NTRL CUR # BLK STG$ setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
NTRL DIR OC# FWD or NTRL DIR OC# REV
operands, which becomes On when
neutral directional overcurrent is flowing
in either forward or reverse direction
respectively
1 for forward 2 for backward 0 for none 3
for both
NTRL DIR OC# FWD operand
NTRL DIR OC# REV operand
NEUTRAL DIR OC# BLOCK setting for
setting group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
R/W/C
R
R
R
R
R
R
R
R
R/W/C
R
3
R/W/C
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
3-77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents