Replacing The Control Unit Without Data Backup; Replacing The Control Unit With Know-How Protection Active - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Corrective maintenance
9.2 Replacing inverter components
9.2.3

Replacing the Control Unit without data backup

If you do not backup the settings, then you must recommission the drive after replacing the
Control Unit.
Procedure
To replace the Control Unit without backed-up settings, proceed as follows:
1. Disconnect the line voltage to the Power Module and (if installed) the external 24 V supply
or the voltage for the digital outputs of the Control Unit.
2. Remove the signal cables of the Control Unit.
3. Remove the defective Control Unit.
4. Mount the new Control Unit on the Power Module.
5. Reconnect the signal cables of the Control Unit.
6. Switch on the line voltage again.
7. Recommission the drive.
The Control Unit replacement has been completed after the drive has been successfully
commissioned.
9.2.4

Replacing the Control Unit with know-how protection active

Replacing devices with know-how protection without copy protection
In the case of know-how protection without copy protection, the inverter settings can be
transferred to another inverter using a memory card.
Replacing devices with know-how protection with copy protection
The know-how protection with copy protection hides the inverter settings and also prevents
the duplication of the inverter settings.
If the inverter settings can neither be copied nor forwarded, a recommissioning is required
after inverter replacement.
To avoid the recommissioning, you must use a Siemens memory card, and the machine
manufacturer must have an identical prototype machine that it uses as sample.
There are two options for replacing the device:
422
Saving setting on memory card (Page 371)
Transferring the setting from the memory card (Page 375)
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120p

Table of Contents