Default setting 101: "Universal application"
DO 0: p0730, ...,
DO 2: p0732
Additional settings:
● Fixed speed setpoint 1: p1001 = 800 rpm
● Fixed speed setpoint 2: p1002 = 1000 rpm
● Fixed speed setpoint 3: p1003 = 1200 rpm
● If several of the DI 3 ... DI 5 = high, the inverter adds the corresponding fixed speeds.
● Fixed speed setpoint 15 for essential service mode (ESM): p1015 = 1500 rpm
● "Flying restart" is enabled: p1200 = 1
● Automatic restart is active. After a power failure, the inverter automatically acknowledges possible
Designation in the BOP-2: P_F 6PA
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
AO 0: p0771[0], AO 1: p0771[1] DI 0: r0722.0, ..., DI 5: r0722.5
faults and switches on the motor: p1210 = 26
4.5 Connecting the interfaces for the inverter control
Installing
AI 0: r0755[0]
121