Siemens SINAMICS G120 Operating Instructions Manual page 227

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

AK
3
4
5
6
7
8
The required element of the parameter is specified in IND (2nd word).
1)
The required element of the indexed parameter is specified in IND (2nd word).
2)
Table 6-28
No.
00 hex
01 hex
02 hex
03 hex
04 hex
05 hex
06 hex
07 hex
0B hex
0C hex
11 hex
14 hex
65 hex
66 hex
68 hex
6A hex
6B hex
86 hex
87 hex
C8 hex
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Description
Transfer descriptive element
Transfer parameter value (field, word)
Transfer parameter value (field, double word)
Transfer number of field elements
Inverter cannot process the request.
In the most significant word of the parameter channel, the inverter sends an error number to
the control, refer to the following table.
No master controller status / no authorization to change parameters of the parameter channel
interface
Error numbers for response identifier 7
Description
Illegal parameter number (access to a parameter that does not exist)
Parameter value cannot be changed (change request for a parameter value that cannot be
changed)
Lower or upper value limit exceeded (change request with a value outside the value limits)
Incorrect subindex (access to a subindex that does not exist)
No array (access with a subindex to non-indexed parameters)
Incorrect data type (change request with a value that does not match the data type of the
parameter)
Setting not permitted, only resetting (change request with a value not equal to 0 without
permission)
Descriptive element cannot be changed (change request to a descriptive element error value
that cannot be changed)
No master control (change request but with no master control, see also p0927.)
Keyword missing
Request cannot be executed due to the operating state (access is not possible for temporary
reasons that are not specified)
Inadmissible value (change request with a value that is within the limits but which is illegal
for other permanent reasons, i.e. a parameter with defined individual values)
Parameter number is currently deactivated (depending on the mode of the inverter)
Channel width is insufficient (communication channel is too small for response)
Illegal parameter value (parameter can only assume certain values)
Request not included / task is not supported (the valid request identifications can be found
in table "Request identifications controller → inverter")
No change access for a controller that is enabled. (The operating state of the inverter pre‐
vents a parameter change)
Write access only for commissioning (p0010 = 15) (operating state of the inverter prevents
a parameter change)
Know-how protection active, access locked
Change request below the currently valid limit (change request to a value that lies within the
"absolute" limits, but is however below the currently valid lower limit)
6.5 Drive control via PROFIBUS or PROFINET
1)
2)
2)
Advanced commissioning
227