Appendix
A.4 Interconnecting signals in the converter
Parameter
p20159 = 5000.00
p20158 = 722.0
p20030[0] = 20160
p20030[1] = 722.1
p0840 = 20031
Explanation of the application example using the ON/OFF1 command
Parameter p0840[0] is the input of the "ON/OFF1" block of the inverter. Parameter r20031 is
the output of the AND block. To interconnect ON/OFF1 with the output of the AND block, set
p0840 = 20031.
Figure A-8
536
Description
Setting the delay time [ms] of the time module: 5 seconds
Connect the status of DI 0 to the input of the time block
r0722.0 = Parameter that displays the status of digital input 0.
Interconnecting the time block to the 1st AND input
Interconnecting the status of DI 1 to the 2nd AND input
r0722.1 = Parameter that displays the status of digital input 1.
Interconnect the AND output to ON/OFF1
Interconnecting blocks by setting p0840[0] = 20031
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE