Connecting The Inverter With The Pm230 Power Module - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing
4.4 Connecting the line supply and motor
4.4.6

Connecting the inverter with the PM230 Power Module

Figure 4-18
PM230 Power Module connection overview
Table 4-27
Connection, cross-section and tightening torque for PM230 Power Modules
Inverters
FSA
Line supply, motor
FSB
FSC
FSD
Line supply, motor
FSE
FSF
Connections for frame sizes FSA ... FSC
94
Connection
Plug connector with
screw terminals
Cable lug
Cross-section, tightening torque
Metric
1 ... 2.5 mm
, 0.5 Nm
2
1.5 ... 6 mm
, 0.6 Nm
2
6 ...16 mm
, 1.3 Nm
2
10 ... 35 mm
, 6 Nm
2
25 ... 50 mm
, 6 Nm
2
35 ... 120 mm
, 13 Nm
2
The Power Modules are equipped with withdraw‐
able plug connectors that cannot be inadvertently
interchanged.
To remove a plug connector, you must release it
by pressing on the red lever.
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Imperial
16 ... 14 AWG, 4.5 lbf in
16 ... 10 AWG, 5.5 lbf in
10 ... 6 AWG, 12 lbf in
7 ... 2 AWG, 53 lbf in
3 ... 1 AWG, 53 lbf in
2 ... 4/0 AWG, 115 lbf in
Converter with the CU230P-2 Control Units
Stripped
insulation
length
8 mm
8 mm
10 mm
--
--
--

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120p

Table of Contents