General Technical Data, 200 V Inverters - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
10.6 Technical data, PM240-2 Power Module
10.6.2

General technical data, 200 V inverters

Property
Line voltage
Line supply configurations
Line impedance
Power factor λ
Output voltage
Input frequency
Output frequency
Inrush current
Overvoltage category ac‐
cording to EN 61800-5-1
Pulse frequency
Short-circuit current rating
(SCCR) and branch protec‐
tion
Braking methods
Degree of protection ac‐
cording to EN 60529
Protection class according
to EN 61800-5-1
Touch protection accord‐
ing to EN 50274
Cooling in compliance with
EN 60146
478
Version
FSA ... FSC
200 V ... 240 V 1-ph. AC ± 10%
200 V ... 240 V 3-ph. AC ± 10%
FSD ... FSF
200 V ... 240 V 3-ph. AC ± 10% (in operation -20% < 1 min)
Grounded TN/TT line supplies or non-grounded IT line supplies
Connecting the line supply and motor (Page 83)
FSA ... FSC
2% ≤ Uk < 4%. For Uk < 2%, we recommend a line reactor, or a Power Module
with the next higher power rating.
FSD ... FSF
No restrictions
FSA ... FSC
0.7 without line reactor for Uk ≥ 2%
0.85 with line reactor for Uk < 2%
FSD ... FSF
0.95
0 V ... 0.95 3-ph. AC × input voltage
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
< LO base load input current
III for line supplies
4 kHz (factory setting),
Adjustable as follows in 2 kHz steps:
• 2 kHz ... 16 kHz for devices with an LO base load output from 0.55 kW ... 30 kW.
• 2 kHz ... 8 kHz for devices with an LO base load output 37 kW and higher
If you increase the pulse frequency, the inverter reduces the maximum output current.
≤ 100 kA rms
Branch protection and short-circuit strength according to UL and IEC
support.industry.siemens.com/cs/ww/en/view/109479152)
DC braking, compound braking, dynamic braking with integrated braking chopper
IP20
IP55
PT devices outside the control cabinet
The inverters are devices with protection class I
DGUV regulation 3 when used for the intended purpose
Forced air cooling AF
0.55 kW ... 4 kW - LO
0.37 kW ... 3 kW - HO
0.55 kW ... 7.5 kW - LO
0.37 kW ... 5.5 kW - HO
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE