Technical data
10.6 Technical data, PM240-2 Power Module
Table 10-69 PM240-2, PT, frame size E, 500 V to 690 V 3 AC
Article No. without filter
Article No. with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
approx. 1.2 kW through the heatsink
1)
Table 10-70 PM240-2, IP20, frame size F, 500 V ... 690 V 3 AC
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
500
6SL3211-1PH26-2UL0
6SL3211-1PH26-2AL0
55 kW
59 A
62 A
45 kW
54 A
52 A
3NA3824-6 (80A)
80 A
1.30 kW
1)
1.31 kW
1)
83 l/s
31 kg
32.5 kg
6SL3210-1PH28-0UL0
6SL3210-1PH28-0AL0
75 kW
78 A
80 A
55 kW
66 A
62 A
3NA3830-6 (100 A)
100 A
1.37 kW
1.38 kW
153 l/s
60 kg
64 kg
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
6SL3210-1PH31-0UL0
6SL3210-1PH31-0AL0
90 kW
97 A
100 A
75 kW
85 A
80 A
3NA3132-6 (125 A)
125 A
1.74 kW
1.76 kW
153 l/s
60 kg
64 kg
Converter with the CU230P-2 Control Units
6SL3210-1PH31-2UL0
6SL3210-1PH31-2AL0
110 kW
111 A
115 A
90 kW
106 A
100 A
3NA3136-6 (160 A)
150 A
1.95 kW
1.97 kW
153 l/s
60 kg
64 kg