Siemens SINAMICS G120 Operating Instructions Manual page 507

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Article no.
HO base load output
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Weight
Table 10-76 PM250, IP20, Frame size F, 3-ph. AC 380 V ... 480 V
Article no.
LO base load output
LO base load input current
LO base load output current
HO base load output
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Weight
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
6SL3225-0BE33-0AA0
30 kW
56 A
60 A
3NA3830
100 A, Class J
3NE1821-0
1.04 kW
22 l/s
21 kg
6SL3225-0BE34-5AA0
55 kW
102 A
110 A
45 kW
84 A
90 A
3NA3836
160 A, Class J
3NE1824-0
1.5 kW
94 l/s
51 kg
10.7 Technical data, PM250 Power Module
6SL3225-0BE33-7AA0
37 kW
70 A
75 A
3NA3832
125 A, Class J
3NE1822-0
1.2 kW
39 l/s
21 kg
6SL3225-0BE35-5AA0
75 kW
135 A
145 A
55 kW
102 A
110 A
3NA3140
200 A, Class J
3NE1825-0
2.0 kW
94 l/s
51 kg
Technical data
6SL3225-0BE37-5AA0
90 kW
166 A
178 A
75 kW
135 A
145 A
3NA3144
250 A, Class J
3NE1827-0
2.4 kW
117 l/s
51 kg
507