Advanced commissioning
6.3 Adapt the default setting of the terminal strip
Parameters p0777 ... p0780 are assigned to an analog output via their index, e.g. parameters
p0777[0] ... p0770[0] belong to analog output 0.
Table 6-7
Parameter
p0777
p0778
p0779
p0780
Setting the characteristic
You must define your own characteristic if none of the default types match your particular
application.
Example:
Via analog output 0, the inverter should convert a signal in the value range 0 % ... 100 % into
an output signal 6 mA ... 12 mA.
Procedure
Defining the function of an analog output
You define the analog output function by interconnecting parameter p0771 with a connector
output of your choice. Parameter p0771 is assigned to the particular analog output via its index,
e.g. parameter p0771[0] is assigned to analog output 0.
Table 6-8
CO
r0021
r0024
r0025
A complete list of the connector outputs is provided in the List Manual.
Additional information is provided in the parameter list and in function diagram 2261 of the List
Manual.
208
Parameters for the scaling characteristic
Description
x coordinate of the 1st characteristic point [% of p200x]
p200x are the parameters of the reference variables, e.g. p2000 is the reference speed.
y coordinate of the 1st characteristic point [V or mA]
x coordinate of the 2nd characteristic point [% of p200x]
y coordinate of the 2nd characteristic point [V or mA]
Connector outputs (CO) of the inverter (selection)
Meaning
Actual speed smoothed
Output frequency, smoothed
Output voltage smoothed
Set the following parameters to set the characteristic to
match the example:
1. Set p0776[0] = 2
This defines analog output 0 as a current output.
2. Set p0777[0] = 0.0 (x1)
3. Set p0778[0] = 6.0 (y1)
4. Set p0779[0] = 100.0 (x2)
5. Set p0780[0] = 12.0 (y2)
CO
Meaning
r0026
DC link voltage smoothed
r0027
Absolute actual current smoothed
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE