Technical data
10.7 Technical data, PM250 Power Module
Property
Climatic ambient conditions
1)
Mechanical ambient condi‐
tions
Protection against chemical
substances
Biological ambient condi‐
tions
Pollution
Cooling
Cooling air
Increased ruggedness regarding temperature range and relative humidity; therefore better than 3K3 according to EN
1)
60721-3-3
Observe the permissible ambient temperatures for the Control Unit and possibly the operator panel (IOP-2 or BOP‑2).
2)
Approvals
● UL, cUL, CE, c-tick, SEMI F47.
Use UL-certified fuses in order to comply with UL requirements.
504
Version
● Ambient operating temperature
For operation according to Low Overload: 0° C ... +40° C
For operation according to High Overload: 0° C ... +50° C
Restrictions for special ambient conditions (Page 510)
● Relative humidity: 5 ... 95%, condensation not permitted
● Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing
water and water jets are not permitted
● FSC ... FSF: Vibration levels permissible according to Class 3M1 to EN 60721-3-3
● FSC:
Shock, permissible according to Class 3M2 to EN 60721-3-3
● FSD ... FSF: Shock permissible according to Class 3M1 to EN 60721-3-3
Protected according to 3C2 to EN 60721‑3‑3
Suitable according to 3C2 to EN 60721‑3‑3
Suitable for environments with degree of pollution 2 according to EN 61800-5-1, condensation
not permitted
Forced air cooling AF, according to EN 60146
Clean and dry air
2)
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE