Commissioning
5.5 Quick commissioning with a PC
Motor identification:
● [1]: Recommended setting. Measure the motor data at standstill and with the motor rotating.
The inverter switches off the motor after the motor data identification has been completed.
● [2]: Measure the motor data at standstill. The inverter switches off the motor after the motor
data identification has been completed.
Recommended setting for the following cases:
– You have selected "Speed control" as control mode, however the motor cannot freely
– You have set "U/f control" as control mode.
● [3]: Measure the motor data while it is rotating. The inverter switches off the motor after the
motor data identification has been completed.
● [11]: The same setting as [1]. The motor accelerates to the currently set setpoint after the
motor data identification.
● [12]: The same setting as [2]. The motor accelerates to the currently set setpoint after the
motor data identification.
Calculating the motor parameters: Select "Complete calculation".
Set the check mark for "RAM to ROM (save data in the drive)" to save your data in the inverter
so that it is not lost when the power fails.
Select "Finish".
Figure 5-19
Figure 5-20
You have completed quick commissioning.
184
rotate, e.g. for mechanically limited traversing sections.
Exiting quick commissioning in STARTER
Exiting quick commissioning in Startdrive
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE