Table 10-44 PM240-2, IP20, frame size D, 200 V ... 240 V 3 AC
Article No. without filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss
Required cooling air flow
Weight
Table 10-45 PM240-2, PT, Frame Size D, 200 V ... 240 V 3 AC
Article No. without filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight
approx. 0.72 kW through the heatsink
1)
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
6SL3210-1PC24-2UL0
11 kW
40 A
42 A
7.5 kW
36 A
35 A
3NA3822 (63 A)
60 A
0.45 kW
55 l/s
17 kg
6SL3211-1PC26-8UL0
18.5 kW
64 A
68 A
15 kW
56 A
54 A
3NA3830 (100 A)
90 A
0.82 kW
1)
55 l/s
19.5 kg
10.6 Technical data, PM240-2 Power Module
6SL3210-1PC25-4UL0
15 kW
51 A
54 A
11 kW
43 A
42 A
3NA3824 (80 A)
70 A
0.61 kW
55 l/s
17 kg
Technical data
6SL3210-1PC26-8UL0
18.5 kW
64 A
68 A
15 kW
56 A
54 A
3NA3830 (100 A)
90 A
0.82 kW
55 l/s
17 kg
483