Siemens SINAMICS G120 Operating Instructions Manual page 454

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
10.4 Technical Data, PM240P-2 Power Module
Property
Installation altitude
Climatic ambient conditions
1)
Mechanical ambient condi‐
tions
Protection against chemical
substances
Biological environmental
conditions
Pollution
Cooling
Cooling air
Increased ruggedness regarding temperature range and relative humidity; therefore better than 3K3 according to EN
1)
60721-3-3
Observe the permissible ambient temperatures for the Control Unit and possibly the operator panel (IOP-2 or BOP‑2).
2)
454
Version
Up to 1000 m above sea level without derating,
> 1000 m
Restrictions for special ambient conditions (Page 510)
● Frame sizes FSD ... FSF temperature range
in operation acc. to LO: -20° C ... +40° C
in operation acc. to HO: -20° C ... +50° C
for higher temperatures
Restrictions for special ambient conditions (Page 510)
● Relative humidity: 5 ... 95%, condensation not permitted
● Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing
water and water jets are not permitted
● Vibration levels permissible according to Class 3M1 to EN 60721-3-3
● Shock permissible according to Class 3M1 to EN 60721-3-3
Protected according to 3C2 to EN 60721‑3‑3
Suitable according to 3B1 to EN 60721‑3‑3
Suitable for environments with degree of pollution 2 according to EN 61800-5-1
Forced air cooling AF, according to EN 60146
Clean and dry air
2)
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE