Commissioning
5.3 Preparing for commissioning
For a control command at the respective digital input, the motor rotates with ±150 rpm. The
same ramp-up and ramp-down times as described above apply.
Figure 5-5
Minimum and maximum speed
● Minimum speed - factory setting 0 [rpm]
After the selection of a motor, during the quick commissioning, the inverter sets the
minimum speed to 20% of the rated speed.
The minimum speed is the lowest speed of the motor independent of the speed setpoint.
● Maximum speed - factory setting 1500 [rpm]
The inverter limits the motor speed to this value.
Operate the motor in the factory setting
We recommend that you execute quick commissioning. For quick commissioning, you must
adapt the inverter to the connected motor by setting the motor data in the inverter.
For basic applications, you can try to operate the drive with a rated power < 18.5 kW without
any other commissioning steps. Check whether the control quality of the drive without
commissioning is adequate for the requirements of the application.
152
Jogging the motor in the factory setting
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE