10.3 Technical data, PM230 Power Module
10.3.6

Current reduction depending on pulse frequency

Current derating depending on the pulse frequency
LO base
load
0.37
0.55
0.75
11.0
15.0
18.5
The permissible cable length to the motor also depends on the cable type and the selected pulse
frequency.
452
Output base-load current at a pulse frequency of
2 kHz
4 kHz
kW
A
A
--
1.30
--
1.70
--
2.20
1.1
--
3.10
1.5
--
4.10
2.2
--
5.90
3.0
--
7.70
4.0
--
10.20
5.5
--
13.20
7.5
--
18.00
--
26.00
--
32.00
--
38.00
22
--
45.00
30
--
60.00
37
--
75.00
45
--
90.00
55
--
110.0
75
--
145.0
6 kHz
8 kHz
10 kHz
A
A
A
1.11
0.91
0.78
1.45
1.19
1.02
1.87
1.54
1.32
2.64
2.17
1.86
3.49
2.87
2.46
5.02
4.13
3.54
6.55
5.39
4.62
8.67
7.14
6.12
11.22
9.24
7.92
15.30
12.60
10.80
22.10
18.20
15.60
27.20
22.40
19.20
32.30
26.60
22.80
38.25
31.50
27.00
51.00
42.00
36.00
63.75
52.50
45.00
76.50
63.00
54.00
93.50
77.00
66.00
123.3
101.5
--
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
12 kHz
14 kHz
A
A
0.65
0.59
0.85
0.77
1.10
0.99
1.55
1.40
2.05
1.85
2.95
2.66
3.85
3.47
5.10
4.59
6.60
5.94
9.00
8.10
13.00
11.70
16.00
14.40
19.00
17.10
22.50
20.25
30.00
27.00
37.50
33.75
45.00
40.50
55.00
49.50
--
--
Converter with the CU230P-2 Control Units
16 kHz
A
0.52
0.68
0.88
1.24
1.64
2.36
3.08
4.08
5.28
7.20
10.40
12.80
15.20
18.00
24.00
30.00
36.00
44.00
--

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120p

Table of Contents